DV2900 DV2910 DV2920 DV2930
20-LED light tower
14
9 Parameter setting
Parameters can be set before installation or during operation.
If you change parameters during operation, this will influence the function of the plant.
u
Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.
Depending on the parameter setting, the parameters available in the menu may change.
Requirements for parameter setting via the IO-Link interface:
ü
A suitable parameter setting software, e.g. ifm moneo|configure
ü
The Input Output Device Description (IODD) for the device, see
ü
One IO-Link master
u
Connect the IO-Link master to a parameter setting software.
u
Set the port of the master to the IO-Link operating mode.
u
Connect the device to a free port of the IO-Link master.
w
The unit switches to IO-Link mode.
u
Change parameter settings in the software.
u
Write parameter settings to the unit.
Notes on parameter setting
Ò
Manual of the parameter setting software
9.1 Identification
Under [Identification], individual identifiers can be assigned to the device via the following parameters:
9.1.1 Application-specific tag
Customer-specific application description, max. 32 characters long.
Default value: “ *** ” / can be freely defined by the customer
9.1.2 Function tag
Customer-specific function tag of the unit, max. 32 characters long.
Default value: “ *** ” / can be freely defined by the customer
9.1.3 Location tag
Customer-specific location tag of the unit, max. 32 characters long.
Default value: “ *** ” / can be freely defined by the customer
9.2 Parameter
The type of signalling is configured under [Parameters].