7 Electrical connection

The device must be connected by a qualified electrician.

Device of protection class III (PC III).

The electrical supply must only be made via PELV/SELV circuits.

u

Disconnect power before connecting the device.

ATTENTION

The IP rating indicated in the data sheet is only guaranteed if the M12 connectors are firmly
screwed. The device can be damaged by insufficiently tightened M12 connectors.

u

Screw the M12 connector to the device applying 1 to 1.5 Nm.

7.1 Wiring

PWR voltage supply

u

Connect the device to a voltage supply using an M12 connection cable.

Pin assignment

Wiring

4

2

1

3

5

1

24 V DC

2

Digital input / output 2

3

0 V

4

Digital input / output 1

5

not connected

Ethernet

u

Connect the device to a PC using a suitable M12 Ethernet connection cable.

Pin assignment

Wiring

1

2

3

4

1

TD+

2

RD+

3

TD-

4

RD-

For trouble-free operation:

u

use a shielded M12 Ethernet connection cable.

The following parameters are preset at the factory:

Parameter

Preset

IP address

192.168.0.79

Gateway address

192.168.0.100

Subnet mask

255.255.255.0

Auto-negotiation

On

DHCP

Off

The settings can be changed via the unit's web server or via a connected PC.

Содержание DTE601

Страница 1: ...Operating instructions RFID compact unit DTE601 DTE602 DTE604 DTE605 11450406 00 06 2022 GB...

Страница 2: ...or ID tags 10 6 3 Avoiding interference 10 6 4 Mechanical design 11 6 5 Mounting options 11 6 5 1 Installation with angle bracket E80335 11 6 5 2 Installation with mounting device E80336 11 6 5 3 Inst...

Страница 3: ...e property of AS International Association www as interface net CAN is the property of Robert Bosch GmbH Germany www bosch de CAN is the property of CiA CAN in Automation e V Germany www can cia org C...

Страница 4: ...3 applies to the software either version 3 of the License or at your option any later version The following disclaimer of the software developers applies to the software components that are subject to...

Страница 5: ...the architect of the system Read this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environment...

Страница 6: ...th the control level via PROFINET IO only DTE602 communication with the control level via EtherNet IP only DTE604 communication with the control level via EtherNet TCP IP only DTE605 communication wit...

Страница 7: ...D compact unit Package insert general information Package insert radio approval The device is supplied without installation and connection accessories Available accessories www ifm com The optimum fun...

Страница 8: ...adiated power is specified in ERP Effective Radiated Power and in EIRP Effective Isotropic Radiated Power for the devices The respective value can be converted using the following formula P dBm EIRP P...

Страница 9: ...RFID compact unit DTE601 DTE602 DTE604 DTE605 9 DTE605 Article number DTE605 Function RFID compact unit Type designation DTRHF HLRWITUS03 Type rectangular...

Страница 10: ...n instructions for ID tags For installation in and on metal use the ID tags provided for this purpose Position the ID tag in the area of the sensing face When doing so the angle of aperture and the op...

Страница 11: ...installation please use the threaded sleeves on the back of the device w The required screws are not supplied with the device 6 5 1 Installation with angle bracket E80335 6 5 2 Installation with moun...

Страница 12: ...TE602 DTE604 DTE605 RFID compact unit 12 6 5 3 Installation with fixing bars E80337 6 6 Mounting distances Operating mode Distance side A Distance front B Read and write at 100 transmitter power 850 m...

Страница 13: ...ng distances between the devices should be as large as possible u Use the RSSI filter u Use the devices in alternating operation u Switch the HF field of the device on off 6 7 Positioning of the ID ta...

Страница 14: ...applying 1 to 1 5 Nm 7 1 Wiring PWR voltage supply u Connect the device to a voltage supply using an M12 connection cable Pin assignment Wiring 4 2 1 3 5 1 24 V DC 2 Digital input output 2 3 0 V 4 Di...

Страница 15: ...hes at 8 Hz u As soon as the LEDs of the signal bar yellow flash at 8 Hz disconnect the unit u Remove the bridge u Connect the device to the voltage supply w The Ethernet parameters are reset 7 2 Conn...

Страница 16: ...Ds of the signal bar are on w The response of the LEDs of the signal bar is adjustable LED LINK ACT ETH 1 ETH 2 LED green LED yellow State Note off off No connection to an Ethernet counterpart Link st...

Страница 17: ...st Starting phase of the device LED BF LED red LED green State Note off off no voltage supply Check the voltage supply off flashes PROFINET IO controller is in STOP mode off on PROFINET IO controller...

Страница 18: ...n was not estab lished u Check the configuration of the device via EtherNet IP scanner off on Connection exists At least one EtherNet IP connection to the device was established flashes off Timeout of...

Страница 19: ...shed there is no data ex change off on Connection to the host controller is established data exchange takes place flashes off Connection to the host controller is established no valid configuration Ch...

Страница 20: ...u Contact ifm in case of malfunction u Do not open the housing as the unit does not contain any components which can be maintained by the user The unit must only be repaired by the manufacturer u Cle...

Страница 21: ...ct unit DTE601 DTE602 DTE604 DTE605 21 10 Approvals standards The EU Declaration of Conformity approvals and country specific certificates are available at www ifm com Notes relevant for approval Pack...

Отзывы: