![IFM DP2200 Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/ifm/dp2200/dp2200_operating-instructions-manual_620770008.webp)
DP2200
Analogue threshold display
8
4.2.2 Application example
2
3
4
5
6
7
bar
4...20 mA
24 V DC
Fieldbus
4...20 mA
1
Fig. 3: Application example with IO-Link master
1:
Analogue sensor (e.g. pressure sensor)
2:
Threshold display
3:
Fully bidirectional IO-Link communication
• Remote display: reading and displaying the measured
current
• Remote parameter setting: reading and changing the
parameter setting
4:
Looping through an analogue input signal
5:
IO-Link master
6:
Fieldbus (e.g. Profibus, Profinet etc.)
7:
PLC
4.2.3 Functionality
In the IO-Link SIO mode, the device has the same functionality as a stand-alone device. The
measured value is also displayed.
Additionally, the device converts the measured current and transmits the value via IO-Link connection
to the PLC.
4.2.4 IO Device Description (IODD)
You will find the IODDs required for configuration of the IO-Link device as well as detailed information
about the process data structure, diagnostic information and parameter addresses at