18
LED
Colour
Description
FAULT Red
Error
ON when an internal fault was detected�
Flashing when an external fault was detected�
1 x
Manual/automatic configuration error
2 x
Switches in incorrect position (frequency selectors)
3 x
Feedback circuit error
4 x
Sensor error (function or wiring)
5 x
Current > 500 mA on output S33, S44, Y1, Y7 or Y8
Flashing alternately with ENA, CONF, IN1/2 and K1/2 when a sensor
is not connected�
IN1
IN2
K1
K2
FAULT
ENA
ON
CONF
IN1
IN2
K1
K2
FAULT
ENA
ON
CONF
IN1
IN2
K1
K2
FAULT
ENA
ON
CONF
IN1
IN2
K1
K2
FAULT
ENA
ON
CONF
IN1/2
Yellow
Input IN1/2
ON when a HIGH signal was detected on the input IN1 or IN2�
K1/2
Green
Relay K1/2
ON when the safety output relay K1 or K2 is switched on�
6.2 Switches
Switches
Description
S1
SP x 10 Switch point selection (increments of 10)
S2
SP x 1
Switch point selection (increments of 1)
S3
DD110S SP multi Unit (rpm/Hz) and multiplier of the selected switch point
DD111S SP x 0�1 Switch point selection (increments of 0�1)
To select the switch point, the 3 switches must be in the "P" (DD110S) or
"P/0" (DD111S) position before the device is switched on�