Process and dialogue module PDM360 NG-12
17
6 Set-up
6.1 General
As delivered the device is prepared for programming with CODESYS version 2�3
or higher�
Factory setting:
IP address: 192�168�82�247
Subnet mask: 255�255�255�0
The user is responsible for the safe function of the application programs
which he created himself� If necessary, he must additionally carry out
an approval test by corresponding supervisory and test organisations
according to the national regulations�
6.2 First steps
►
Connect the device to the notebook/PC via the Ethernet interface�
►
Switch on the notebook/PC; check the IP settings of the notebook/PC and
change them if necessary�
Internet protocol: TCP/IP
IP address: 192�168�82�xxx (except for �247, s�a�)
Subnet mask: 255�255�255�0
Gateway IP address: 192�168�100�1
►
Switch on the operating voltage to the dialogue module�
> Shortly after switch-on of the unit the start image is shown for approx� 10 to 15
seconds�
During this time booting is running in the background�
After booting the set-up program opens automatically�
6.3 Set-up
The set-up allows the setting of the device parameters�
The menu items are selected using the function keys or via a connected USB
keyboard�
Function keys
USB keyboard
Description
Left
SELECT
TAB
Select menu item
SAVE
F3
Save entries
Right
UP
Arrow up
Increase value or variable
DOWN
Arrow down
Decrease value or variable
ENTER
ENTER
Open selected menu item
EXIT
ESC
Leave set-up
Leave menu item
Entries will not be saved