45
ifm
Programming Manual BasicController relay CR0431 v03.03.00
05 / 2018
Configurations
Function configuration of the inputs and outputs
>
Configure the software filters of the inputs
15418
Via the input FILTER in the FB
INPUT
(
) a software filter can be configured which filters the
measured input voltage at the analogue inputs.
The filter behaves like a low-pass filter; the filter frequency is set with the value entered in FILTER. For
FILTER, values from 0...8 are permitted.
Table: limit frequency software low-pass filter at the analogue input
FILTER
Filter frequency [Hz]
Step response [ms] for ...
Remarks
0…70 %
0…90 %
0…99 %
0
Filter deactivated
1
120
2
4
7
2
47
5
9
17
3
22
10
18
35
4
10
19
36
72
recommended
5
5
38
73
146
6
2.5
77
147
293
7
1.2
154
294
588
8
0.7
308
589
1177
The following statements of the step response are relevant:
• Input analogue:
0...90 % and 0...99 %
• Input binary: 0...70 %
Figure: course of time binary signal at the input upon switch-on / switch-off
Содержание BasicController CR0431
Страница 228: ...228 10 Notizen Notes Notes...