Configuration
Modbus
>
8.3.3
Read input data of several IO-Link ports
8702
Register area for compact access to the input data of the IO-
Link ports X01…X04 and X05...X08: →
Input Data
(
The area contains the following data:
Combined digital inputs - clamp 2 / clamp 4 (DI) of the IO-Link ports
Status information of the IO-Link ports
Status information of the IO-Link devices
Combined input data - IO-Link of the IO-Link ports
Observe the general rules for access to the Modbus registers (
→
Rules for accessing the Modbus
register
(
The parameter "Invalid Data" indicates whether the read IO-Link input data is valid.
► Together with the input data, also read and evaluate the corresponding status information
of the IO-Link devices!
Register area
Contents
Access
Start
address
Length
(words)
197
1
Port X01…X04: Digital Input - clamp 2 / clamp 4 (DI)
r
198
1
Port X01…X04: Status Information IO-Link Ports
r
199
1
Port X01…X04: Status Information IO-Link Devices
r
2n
Port X01…X04: Compact Input Data - IO-Link (4n bytes)
r
297
1
Port X05…X08: Digital Input - clamp 2 / clamp 4 (DI)
r
298
1
Port X05…X08: Status Information IO-Link Ports
r
299
1
Port X05...X08: Status Information IO-Link Devices
r
2n
Port
X05…X08: Compact Input Data - IO-Link (4n bytes)
r
r = read only
n = [2,4,8,16,32]; is determined by parameters [Process Data Length] (
→
Configuration Area
(