Device Manual IO-Link Master with Modbus interface CabinetLine 8 Ports IP 20 (AL1940)
05 / 2018
Configuration
IoT Core
8.2.1
Configure IoT interface
16540
The parameters of the IoT port X23 are saved in the
iotsetup
substructure. The user can access the
following data points:
Name
Description
Access
iotsetup/accessrights
Access rights to the IO-Link master
0 = IoT
1 = IoT (read only)
2 = IoT only
rw
iotsetup/smobip
IP address of the LR SMARTOBSERVER
rw
iotsetup/smobport
Port number of the LR SMARTOBSERVER
rw
iotsetup/smobinterval
Cycle time for data transmission to LR SMARTOBERVER (value in
milliseconds)
rw
iotsetup/network/dhcp
Configuration of the IP settings of the IoT port
0 = STATIC_IP/OFF
1 = DHCP/ON
rw
iotsetup/network/ipaddress
IP address of the IoT port
rw
iotsetup/network/subnetmask
Subnet mask of the network segment
rw
iotsetup/network/ipdefaultgateway
IP address of the network gateway
rw
rw ... read and write
Data point [iotsetup/accessrights]:
Different parameter settings in the Modbus projection software and the IoT applications can
result in undesired system behaviour. The values set in the Modbus projection software apply.