Operating and display elements 

 

 

 

7.2

 

LED indicators 

22024 

The device only has the following LED indicators: 

 

7.2.1

 

Status LEDs 

22034 

The RDY LED shows the status of the gateway. 

The BF LED (Bus Failure) shows the status of the Profinet connection. 

The SF LED (System Failure) shows the status of the system. 

  

Status LED 

Description 

RDY 

green 

on 

Gateway functions properly 

flashes 1 Hz 

Error 

flashes 5 Hz 

Firmware update 

off 

Gateway does not function; Unit reboots 

BF 

red 

on 

Bus error 

flashes 1 Hz 

No connection to the Profinet controller 

off 

error-free 

SF 

red 

on 

 

Error in gateway 

 

At least 1 IO-Link device sends warning / alarm (temperature, 
over/under current, over/under voltage, shortcut) 

off 

error-free 

 

  

 

7.2.2

 

Ethernet interface 

22027 

Each Ethernet interface (X21, X22) has 2 LEDs (LNK and ACT). The LEDs indicate the status of the 
Ethernet connection. 

   

Status LED 

Description 

LNK 

green 

on 

Ethernet connection established 

off 

No Ethernet connection 

ACT 

yellow 

flashes 

Data is transmitted via the Ethernet interface. 

off 

No data transmission 

  

Содержание AL1101

Страница 1: ...Operating Instructions IO Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 ifm firmware 1 1 22 or higher LR DEVICE 1 1 0 87 or higher IO Link 1 1 2 English 7391103_00_UK 2017 05 31 ...

Страница 2: ...it 10 3 Functions and features 11 3 1 Permitted use 11 3 2 Prohibited use 11 4 Function 12 4 1 Communication parameter setting evaluation 13 4 1 1 IO Link 14 4 1 2 Profinet 14 4 1 3 Parameter setting 14 4 1 4 Visual indication 14 4 2 Digital inputs 15 4 3 IO Link supply 15 5 Mounting 16 5 1 Mount the device 16 6 Electrical connection 17 6 1 Profinet ports 18 6 2 IO Link ports 18 6 2 1 Input circui...

Страница 3: ...SD file 43 8 4 2 Add the device to the Profinet network 44 8 4 3 Configure communication profile 46 8 4 4 Configure IO Link ports 47 8 4 5 Configure the Profinet interface 48 8 5 Profinet Configure IO Link devices 49 8 6 Profinet Programmers notes 49 8 6 1 Read and write I M datasets 49 8 6 2 Detect diagnostics and alarms 50 8 6 3 Configure IO Link devices 50 9 Operation 51 9 1 Identify device 52 ...

Страница 4: ...tandardLine 4 Ports IP 69K AL1101 2017 05 31 Content 12 1 10 Accessories 64 12 1 11 Electrical connection 64 12 2 Profinet 65 12 2 1 Parameter data 66 12 2 2 Cyclic data 69 12 2 3 Acyclic data 72 13 Index 74 14 ifm weltweit ifm worldwide ifm à l échelle internationale 77 ...

Страница 5: ... Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Preliminary note 1 Preliminary note Legal and copyright information 6 Purpose of the document 6 Symbols and styles used 6 Modification history 7 14801 ...

Страница 6: ...eckhoff Automation GmbH Germany IO Link www io link com is the property of the PROFIBUS Nutzerorganisation e V Germany ISOBUS is the property of the AEF Agricultural Industry Electronics Foundation e V Deutschland www aef online org Microsoft is the property of the Microsoft Corporation USA www microsoft com PROFIBUS is the property of the PROFIBUS Nutzerorganisation e V Germany www profibus com P...

Страница 7: ...rating Instructions IO Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Preliminary note 1 4 Modification history 21676 Version Topic Date 00 New creation of document 31 05 2017 ...

Страница 8: ...Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Safety instructions 2 Safety instructions General 9 Required background knowledge 9 Warnings used 9 Safety symbols on the device 10 Tampering with the unit 10 213 ...

Страница 9: ...rators and machinery Observe these operating instructions Adhere to the warning notes on the product 2 2 Required background knowledge 22046 This document is intended for specialists Specialists are people who based on their relevant training and experience are capable of identifying risks and avoiding potential hazards that may be caused during operation or maintenance of the product The document...

Страница 10: ...bol is shown consult the corresponding section in the operating instructions 2 5 Tampering with the unit 11242 WARNING Tampering with the units can affect the safety of operators and machinery Tampering with the units is not allowed In case of non compliance our liability and warranty expire Do not open the devices Do not insert any objects into the devices Prevent metal foreign bodies from penetr...

Страница 11: ...7 05 31 Functions and features 3 Functions and features Permitted use 11 Prohibited use 11 18761 3 1 Permitted use 7610 The device is designed for use without a control cabinet in the food industry 3 2 Prohibited use 22053 The device may not be used beyond the limits of the technical data Technical data p 61 ...

Страница 12: ...rating Instructions IO Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Function 4 Function Communication parameter setting evaluation 13 Digital inputs 15 IO Link supply 15 7482 ...

Страница 13: ...structions IO Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Function 4 1 Communication parameter setting evaluation IO Link 14 Profinet 14 Parameter setting 14 Visual indication 14 7485 ...

Страница 14: ...n of the process and parameter data between the connected IO Link devices and the higher level Profinet controller 4 1 3 Parameter setting 7771 The device provides the following configuration options Parameter setting of the IO Link master of the AL1101 with parameter setting software LR DEVICE and or Profinet projection software Parameter setting of the connected IO Link devices sensors actuators...

Страница 15: ...e on pin 2 of the IO Link ports X01 X04 All inputs refer to the potential of the device supply pin 3 4 3 IO Link supply 7623 The device has 4 supplies for IO Link devices sensors actuators The IO Link ports X01 X04 are ports class A Every supply provides short circuit monitoring The device ensures fire protection for the connected IO Link devices by providing a power restricted circuit at the IO L...

Страница 16: ...16 22016 5 1 Mount the device 15540 Disconnect the system from power before installation For installation choose a flat mounting surface Please observe the maximum tightening torque Fix the unit to the mounting surface using 2 M5 mounting screws and washers Tightening torque 1 8 Nm Ground the unit via the two mounting screws of the upper mounting lugs ...

Страница 17: ... suitable for operation on SELV PELV voltages Observe the information concerning IO Link circuits IO Link circuits p 19 The device contains components that can be damaged or destroyed by electrostatic discharge ESD Observe the required safety measures against electrostatic discharge The IP rating depends on the individual protection ratings of the unit the applied connection elements and the corre...

Страница 18: ...g software LR DEVICE laptop PC with installed monitoring software LR SmartObserver Tightening torque 0 6 0 8 Nm For the connection use M12 connectors with protection rating IP 69K or higher z B EVF531 Cover the unused sockets with M12 protective caps art no E12542 verschließen Tightening torque 0 6 0 8 Nm 6 2 IO Link ports 8526 Ports X01 X04 For use as IO Link port class A Connect the connector of...

Страница 19: ...sockets 4 pin 2 provide a type 2 behaviour according to standard EN61131 2 the connected electronics must be rated for this electrically 6 2 2 IO Link circuits 1863 The IO Link ports of the device meet the requirements of the IO Link specification 1 0 bis 1 1 2 The power supply of the connected IO Link devices may only take place via the AL1101 Further information Technical data p 61 ...

Страница 20: ...542 Disconnect power Connect the device via M12 socket X31 to 24 V DC 20 30 V SELV PELV according to EN61010 1 secondary circuit with maximum 30 V DC derived from applied voltage up to 300 V of overvoltage category II Tightening torque 0 6 0 8 Nm Maximum cable length 25 m To connect the device use M12 connectors with protection rating IP 69K or higher z B EVF481 ...

Страница 21: ... Operating Instructions IO Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Operating and display elements 7 Operating and display elements Overview 22 LED indicators 23 5440 ...

Страница 22: ...rating and display elements 7 1 Overview 22025 Status LEDs RDY BF und SF Status LEDs p 23 Status LEDs LNK and ACT of the Profinet ports 1 X21 and 2 X22 Ethernet interface p 23 Status LED US of the power supply X31 Voltage supply p 24 Status LEDs IOL and DI of the IO Link ports Class A X01 X04 IO Link ports Class A p 24 ...

Страница 23: ...s properly flashes 1 Hz Error flashes 5 Hz Firmware update off Gateway does not function Unit reboots BF red on Bus error flashes 1 Hz No connection to the Profinet controller off error free SF red on Error in gateway At least 1 IO Link device sends warning alarm temperature over under current over under voltage shortcut off error free 7 2 2 Ethernet interface 22027 Each Ethernet interface X21 X22...

Страница 24: ...d or the applied supply voltage is too low 7 2 4 IO Link ports Class A 22029 Each IO Link port Class A X01 X04 has 2 LEDs marked as IOL and DI The LEDs indicate the status of the IO Link port Status LED Description IOL yellow on Interface configured as DI DO Pin 4 C Q ON off Interface configured as DI DO Pin 4 C Q OFF green on IO Link transmission functions properly flashes 1 Hz Interface configur...

Страница 25: ...e StandardLine 4 Ports IP 69K AL1101 2017 05 31 Configuration 8 Configuration Remarks 26 LR DEVICE Configure the device 31 LR DEVICE Configure IO Link devices 40 Profinet Configure the device 42 Profinet Configure IO Link devices 49 Profinet Programmers notes 49 22367 ...

Страница 26: ...ns IO Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Configuration 8 1 Remarks Supported configuration options 27 Connection possibilities 27 Offline parameter setting 30 VPN connection 30 22369 ...

Страница 27: ...nterfaces X21 and X22 the AL1101 can be simultaneously connected with the Profinet control level PLC and the IT infrastructure level monitoring parameter setting The following connection possibilities exist Operation without Profinet connection 4364 Operation as independent IO Link master with connected IO Link devices As an option several IO Link masters can be coupled via the Profinet interfaces...

Страница 28: ...O master as Profinet IO device As an option several IO Link masters can be coupled via the Ethernet interfaces X21 and X22 The complete monitoring of the process data and processing of alarms takes place via Profinet mechanisms Parameter setting IO Link master Profinet projection software IO Link device Profinet projection software acyclic services Monitoring Profinet projection software Topology ...

Страница 29: ...he AL1101 can be connected via the two Ethernet interfaces X21 and X22 simultaneously with the Profinet control level PLC and the IT infrastructure level monitoring parameter setting Parameter setting IO Link master LR DEVICE and or Profinet projection software IO Link device LR DEVICE and or Profinet projection software Monitoring LR SmartObserver and or Profinet projection software Topology exam...

Страница 30: ...vices without being connected to the AL1101 The configuration created in this way can be stored as a file lrp and loaded to the device and activated at a later date Further information about offline parameter setting Operating instructions of the parameter setting software LR DEVICE 8 1 4 VPN connection 22762 An active VPN connection blocks the access of the parameter setting software LR DEVICE to...

Страница 31: ...R DEVICE Further information about operation and functions of the LR DEVICE parameter setting software Use the help function of the parameter setting software LR DEVICE In order to configure the AL1101 with the LR DEVICE Put AL1101 into operation Set up p 32 Under ONLINE Click on the AL1101 LR DEVICE shows the following sections Section Functions All all available functions Network Configure the E...

Страница 32: ...e device 2 Set network parameters Under ONLINE Click on AL1101 LR DEVICE shows all current network settings Set the following parameters as required Parameters Description Possible values IP address IP address of the device e g 172 18 65 50 Subnet mask Subnet mask of the IP network e g 255 255 255 0 IP gateway address IP address of the network gateway e g 172 18 65 0 Profinet name Device name in t...

Страница 33: ...order ro Profinet has read and write access rights to parameters and process data Profinet has read access rights to events alarms LR DEVICE only has read access rights to parameters process data and events alarms LineRecorder only LR DEVICE has read and write access rights to parameters to parameters and process data LR DEVICE has read access rights to events alarms Profinet has no access rights ...

Страница 34: ...ngs Set the following parameters as required Parameters Description Possible values IP address IP address of the device e g 172 18 65 50 Subnet mask Subnet mask of the IP network e g 255 255 255 0 IP gateway address IP address of the gateway e g 172 18 65 1 Profinet name Name of the device in the Profinet network e g al1xxx MAC address MAC address of the device The value is fixed observe the restr...

Страница 35: ... 35100 Source ID SmartObserver Source identifier with which the process data of the device is indicated in the SmartObserver String32 Port x LR events Operating mode of the IO Link port x 1 4 Disabled Cyclic transfer of the process data Enabled Event based transfer of the process data Port x LR cycle time ms Cycle time of the IO Link interface for cyclic transmission of the process data between th...

Страница 36: ...the operating mode of each IO Link port separately at any time Select Port x menu The page shows the current settings Set the following parameters as required Name Description Possible values Port x mode Operating mode of the IO Link port x 1 4 IO Link Operation as IO Link interface DI Operation as digital input DO Operation as digital output Disabled Interface deactivated Port x IO Link Cycle tim...

Страница 37: ...D and device ID No data storage Type compatible V1 0 device IO Link device is compatible with the V1 0 IO Link standard Verification whether it is an IO Link device of the same type validation via vendor ID and device ID No data storage Type compatible V1 1 device IO Link device is compatible with the V1 1 IO Link standard Verification whether it is an IO Link device of the same type validation vi...

Страница 38: ... ID and device ID The IO Link master saves the parameter values of the connected IO Link device once When connecting an IO Link device with factory settings the parameter values stored in the IO Link master are restored automatically on the IO Link device Port x IO Link Vendor ID ID of the manufacturer that is to be validated 0 65535 ID of the manufacturer of the IO Link device ifm electronic 310 ...

Страница 39: ...guration 8 2 7 Reset IO Link master to factory settings 12740 When resetting the AL1101 all parameters are reset to the Factory settings p 59 To reset the device to factory settings Select Setup menu The page shows the current settings Click on Factory Reset to reset the AL1101 LR DEVICE sets the AL1101 factory settings ...

Страница 40: ...th one of the following values Profinet LineRecorder LineRecorder only 1 Select IO Link master Start LR DEVICE Update IODD file library OR Import IODD file of the IO Link device manually Scan network for devices LR DEVICE recognises all IO Link masters of the Profinet network 2 Add IO Link device Under ONLINE Click on the required AL1101 LR DEVICE automatically detects the IO Link devices connecte...

Страница 41: ...ion LR DEVICE shows AL1101 in OFFLINE section 2 Add IO Link device to configuration Under OFFLINE Click on AL1101 LR DEVICE shows the available parameters of the AL1101 Click on the symbol at the required port The dialogue window Gerät auswählen appears Select the required IO link device from the list Click on OK to add the selected IO Link device to the device configuration IO Link device appears...

Страница 42: ...igure communication profile 46 Configure IO Link ports 47 Configure the Profinet interface 48 22758 On the field bus side the device can be configured with the following options Profinet projection software STEP 7 version 5 5 SP 4 or higher Profinet projection software TIA portal Further information about operation and functions of the Profinet parameter setting software Use the help function of t...

Страница 43: ...hardware catalogue Download GSD file of the AL1101 from the ifm website Start STEP 7 application HW Config Select Options Install GSD files The Install GSD files window appears Click on Browse Select the GSD file of the AL1101 and click on OK to adopt the file The selected GSD file appears in the list Select the GSD file in the list and click on Install STEP 7 installs the GSD file and adds the AL...

Страница 44: ...troller Requirements Profinet has read and write permission on the AL1101 Configure communication profile p 33 The GSD file of the AL1101 is installed Install GSD file p 43 1 Create open project Create new Profinet project OR Open an existing Profinet project Configure Profinet connection 2 Add the AL1101 to project Open STEP 7 application HW Config Program window shows the hardware structure of t...

Страница 45: ...th Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Configuration 3 Add IO Link ports Move the 4 Ports node via drag drop from the hardware catalogue to slot 1 of the AL1101 Step 7 shows available IO Link interfaces Save the project ...

Страница 46: ...ine 1 1 IO Link Master The window Properties IO Link master appears Select Paramerters tab Set the following parameter as required Communication Profile Parameter of the IO Link master p 66 Click on Hinzufügen to save the changes If parameter Communication Profile Profinet LineRecorder Different parameter settings in the Profinet projection software and the LR DEVICE may cause undesired system beh...

Страница 47: ...hows the current configuration of the AL1101 2 Add Profinet module Open hardware catalogue Draw the required Profinet module of the AL1101 from the hardware catalogue to the slot The device editor shows the slot with the selected Profinet module 3 Set parameters of the Profinet module Double click on the added slot Window Properties appears Select Paramerters tab The page shows the current paramet...

Страница 48: ...ears 2 Search AL1101 Click on Durchsuchen button Browse Network window appears Click on Start button STEP 7 browses the Profinet network for devices List shows found devices Select AL1101 in list and click OK to adopt the device The MAC address shows the MAC address of the AL1101 3 Set IP address and network mask Click on the Use IP parameters selection field in group Set IP configuration Enter th...

Страница 49: ...pplication Read device information of the AL1101 Read diagnostics and alarms Set parameters of the connected IO Link devices The following sections show the available options Further information about the functional operational blocks Help function of the Profinet projection software 8 6 1 Read and write I Mdatasets 2261 Symbol function block Meaning Remarks GET_IM_DATA FB Function block for readi...

Страница 50: ...iagnostic and alarms p 73 8 6 3 Configure IO Link devices 2260 Symbol function block Description Remarks IO_LINK_DEVICE FB5001 Acyclic access to the parameters of an IO Link device Input parameters CAP Access point for function AL1101 0xB400 PORT HW ID Slot sub slot of the IO Link port with connected IO Link device Port X01 1 Port X02 2 Port X03 3 Port X04 4 IOL_INDEX and IOL_SUBINDEX depends on t...

Страница 51: ... with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Operation 9 Operation Identify device 52 Read device information 52 Reboot the device 55 Error detection and elimination 55 Firmware update 56 Exchange IO Link device 57 22368 ...

Страница 52: ...for devices LR DEVICE detects the device Click on the selection field next to the device name The status LEDs on the unit flash asynchronously 9 2 Read device information 12741 In order to get information about the current status of the hardware and software components of the device the user can use the following possibilities Web interface Read device and diagnostic information p 53 LR DEVICE Rea...

Страница 53: ...ink interface MasterCycleTime Cycle time Vendor ID ID of the manufacturer of the IO Link device Device ID ID of the IO Link device Name Article number of the IO Link device For ifm articles This article number is stored along with a link to the produkt page on the ifm website Serial Serial number of the IO Link device LR Interval Cycle time for the communication with the SmartObserver Version info...

Страница 54: ...e of the device IO Link master StandardLine Profinet 4 ports IP 69K Device status Current status of the slave no information about the condition OK no errors no warning no information OK no errors no warning information Warning Error 9 2 3 Profinet Read writedeviceinformation 22783 I M0 provide the user with device specific basic information This ensures reliable identification of the device the d...

Страница 55: ...he network for devices LR DEVICE recognises the AL1101 Under ONLINE Click on AL1101 Select the Setup section LR DEVICE shows available parameters Click on Restart to restart the device LR DEVICE restarts the AL1101 9 4 Error detection and elimination 11610 In order to recognise and eliminate errors the user can use the following resource Status LED of the unit LED indicators p 23 Acyclic alarms an...

Страница 56: ...the device Requirements File with new firmware has been downloaded Ethernet connection between laptop PC and device is established 1 Call up web interface Start web browser Enter the following into the address field of the browser and confirm with ENTER IP Adresse des Geräts update Web browser shows the Firmware Update page 2 Load new firmware to AL1101 Click on Datei auswählen Dialogue window app...

Страница 57: ...standard 1 1 or higher 1 Set data storage Set the following parameters of the IO Link port Validation Data Storage Type compatible V1 1 device with Restore OR Port x IO Link Validation Data Storage Type compatible V1 1 device with Restore Save changes 2 Exchange IO Link device Disconnect old IO Link device from AL1101 Connect new IO Link device with the same IO Link port of the AL1101 IO Link mast...

Страница 58: ...1 2017 05 31 Maintenance 10 Maintenance 21577 The operation of the unit is maintenance free Clean the surface of the unit when necessary Do not use any caustic cleaning agents for this After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations ...

Страница 59: ...e 4 Ports IP 69K AL1101 2017 05 31 Factory settings 11 Factory settings 22671 In the factory settings the device has the following parameter settings Parameters Factory setting IP address 0 0 0 0 Subnet mask 0 0 0 0 IP gateway address 0 0 0 0 Profinet name blank Data Storage empty ...

Страница 60: ...60 ifm Operating Instructions IO Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Appendix 12 Appendix Technical data 61 Profinet 65 7156 ...

Страница 61: ... StandardLine 4 Ports IP 69K AL1101 2017 05 31 Appendix 12 1 Technical data Application 62 Electrical data 62 Inputs outputs 62 Inputs 62 Outputs 62 Interfaces 63 Operating conditions 63 Approvals tests 63 Mechanical data 64 Accessories 64 Electrical connection 64 9011 ...

Страница 62: ...to SELV PELV Current Consumption mA 300 3900 US Protection class III Sensor supply US Max current load total A 3 6 12 1 3 Inputs outputs 23711 Inputs outputs Total number of inputs and outputs 8 configurable 12 1 4 Inputs 22820 Inputs Number of digital inputs 8 IO Link Port Class A 4 x 2 Switching level high V 11 30 DC Switching level low V 0 5 DC Digital inputs protected against short circuits ye...

Страница 63: ...s 0 0 0 0 Subnet mask 0 0 0 0 Gateway IP address 0 0 0 0 MAC address see type label IO Link Master Transmission type COM 1 COM 2 COM 3 IO Link revision V1 1 Number of ports class A 4 12 1 7 Operating conditions 22823 Operating conditions Applications Indoor use Ambient temperature C 25 60 Storage temperature C 25 85 Max perm relative air humidity 90 Max height above sea level m 2000 Protection rat...

Страница 64: ...less steel 1 4404 316L 12 1 10 Accessories 23707 Accessories Accessories supplied Protective cap 1 x M12 stainless steel E12542 12 1 11 Electrical connection 22826 Voltage supply IN X31 Connector M12 Wiring 1 24 V DC US 2 3 GND US 4 Ethernet IN OUT X21 X22 Connector M12 Wiring 1 TX 2 RX 3 TX 4 RX 5 Process connection IO Link Ports Class A X01 X0 IOL_AnzPorts Connector M12 Wiring 1 24 V DC US 2 DI ...

Страница 65: ...65 ifm Operating Instructions IO Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Appendix 12 2 Profinet Parameter data 66 Cyclic data 69 Acyclic data 72 22433 ...

Страница 66: ...ss data and events diagnostic messages of the IO Link master and the connected IO Link devices Profinet LineRecorder Profinet and LR DEVICE have read and write access rights to parameters and process data Profinet and LR DEVICE have read access rights to events alarms Profinet LineRecorder ro Profinet has read and write access rights to parameters and process data Profinet has read access rights t...

Страница 67: ...ard and behaviour of the AL1101 when a new IO Link device is connected to the IO Link port no check and clear no verification of the vendor ID and device ID no data storage Type compatible V1 0 device IO Link device is compatible with the V1 0 IO Link standard Verification whether it is an IO Link device of the same type validation via vendor ID and device ID no data storage Type compatible V1 1 d...

Страница 68: ...memory of the AL1101 is empty When connecting an IO Link device with factory settings the parameter values stored in the IO Link master are restored automatically on the IO Link device Vendor ID VID ID of the manufacturer that is to be validated 0 65535 ID of the manufacturer of the IO Link device ifm electronic 310 Device ID ID of the IO Link device that is to be validated 0 16777215 ID of the IO...

Страница 69: ...69 ifm Operating Instructions IO Link Master with Profinet interface StandardLine 4 Ports IP 69K AL1101 2017 05 31 Appendix 12 2 2 Cyclic data Profinet modules 70 PQI Port Qualifier Information 71 22429 ...

Страница 70: ...ut and output data and PQI IO Link 1I 15O PQI 1 byte input and 15 bytes output data and PQI IO Link 32I PQI 32 bytes input data and PQI IO Link 16I PQI 16 bytes input data and PQI IO Link 8I PQI 8 bytes input data and PQI IO Link 4I PQI 4 bytes input data and PQI IO Link 2I PQI 2 bytes input data and PQI IO Link 1I PQI 1 bytes input data and PQI IO Link 32O PQI 32 bytes output data and PQI IO Link...

Страница 71: ...I2 DI4 Legend DI4 Signal status of the digital input on Pin 4 if used FALSE TRUE OFF ON DI2 Signal status of the digital input on Pin 2 if used FALSE TRUE OFF ON DA Device Available shows if the IO Link device has been recognised and if the device is in the preoperate or in the operate state FALSE TRUE no device device recognised DE Device Error shows if an error or a warning occurred Note The use...

Страница 72: ...s e g x y z in Vx y z r 3 Revision Counter Revision counter is incremented with each parameter change r 2 Profile ID ID of sub module profile Slot 0 0x0000 r 2 Profile Specific Type additional value for profile ID 0 if not used r 2 IMVersion I M version default value 0x0101 r 2 IMSupported Suported I M datasets 0x1110 for I M1 3 r 2 r only read I M1 Slot 0 22765 Variable Description Access Size Ta...

Страница 73: ...ad Diagnostic and alarms 22784 ECD code Name Description Type 0x02 EVNT_CODE_M_PDU_CHECK Receive frame with CRC error Alarm 0x1B EVNT_CODE_S_RETRY Repetitions detected Alarm 0x1E EVNT_CODE_P_SHORT Short circuit on C Q cable detected Diagnostics 0x1F EVNT_CODE_P_SENSOR Error in the sensor supply Diagnostics 0x20 EVNT_CODE_P_ACTOR Error in the actuator supply Diagnostics 0x21 EVNT_CODE_P_POWER Error...

Страница 74: ...eit ifm worldwide ifm à l échelle internationale 77 Input circuit 19 Inputs 62 Inputs outputs 62 Install GSD file 43 Interfaces 63 IO Link 14 IO Link circuits 19 IO Link ports 18 IO Link ports Class A 24 IO Link supply 15 L LED indicators 23 Legal and copyright information 6 LR DEVICE Configure IO Link devices 40 Configure the device 31 Read device information 54 M Maintenance 58 Mechanical data 6...

Страница 75: ...S Safety instructions 8 Safety symbols on the device 10 Set device validation and data storage 37 Set the operating mode of the IO Link ports 36 Set up 32 Status LEDs 23 Supported configuration options 27 Symbols and styles used 6 T Tampering with the unit 10 Technical data 61 V Visual indication 14 Voltage supply 24 VPN connection 30 W Warnings used 9 Web interface Read device and diagnostic info...

Страница 76: ......

Страница 77: ...ampton Middlesex TW12 2HD Tel 44 208 213 0000 ifm electronic Monoprosopi E P E 15125 Amaroussio Tel 30 210 6180090 ifm electronic kft 9028 Györ Tel 36 96 518 397 ifm electronic s a 20041 Agrate Brianza MI Tel 39 039 68 99 982 Astragal Ltd Azur 58001 Tel 972 3 559 1660 ifm electronic India Branch Office Kolhapur 416234 Tel 91 231 267 27 70 efector co ltd Chiba shi Chiba 261 7118 Tel 81 043 299 2070...

Отзывы: