18
13 Technical data
AC422S
Use as an AS-i Ethernet/IP gateway with safe preprocessing
4 safe local inputs (two-channel) and 2 safe local semiconductor outputs
Electrical data
Number of AS-i masters
2
Operating voltage [V]
18...32 DC (AUX)
Current consumption from 24 V DC and
AS-i [mA]
< 750 (24 V) / < 10 from AS-i 1 /
< 10 from AS-i 2
Electrical separation
yes
Inputs
Circuits
DC PNP (type 2 to IEC 61131-2)
Sensor supply
to SELV/PELV
Voltage range [V]
24 DC (18...32 DC)
Input current [mA]
7
Outputs
Output function
Transistor PNP (according to IEC 61131-2)
Voltage range [V]
24 DC (18...32 DC)
External supply
to SELV/PELV
Max. current load per output [mA]
500
Max. inductance [mH]
400
Max. switching frequency [Hz]
25
Utilisation category
DC-13 (according to IEC 60947-5-1)
Electrically isolated
yes
Short-circuit protection
yes
Interfaces
Programming interface
Ethernet
Data interface
Ethernet/IP (IP = Industrial Protocol),
100 Mbaud
Environmental conditions
Ambient temperature [°C]
0...50, for UL application: max. 45
Storage temperature [°C]
-20...70
Max. perm. relative air humidity [%]
95, non-condensing
Height above sea level [m]
< 2000
Содержание AC422S