17
UK
10 Operation
After power on of the supply voltage the unit is in the Run mode (= normal operati-
on)� It carries out its measurement and evaluation functions and generates output
signals according to the set parameters�
Operating indicators → 7 Operating and display elements.
10.1 Read the set parameter values
► Press [Mode/Enter] briefly to scroll the parameters�
► Press [Set] briefly to indicate the corresponding parameter value for 15 s� After
another 15 s the unit returns to the Run mode�
10.2 Fault indication
[OL]
overload pressure (measuring range exceeded)
[UL]
underpressure range (measuring range below the minimum value)
[SC1]
short circuit in OUT1*
[SC2]
short circuit in OUT2*
[SC]
short circuit in both switching outputs*
*The output concerned is switched off as long as the short circuit exists�
This faults are indicated even if the display is deactivated�
11 Technical data and scale drawing
Technical data and scale drawing at www.ifm.com → Data sheet search → Enter
the article number�
11.1 Setting ranges
SP1 / SP2
rP1 / rP2
ASP
AEP
ΔP
min
max
min
max
min
max
min
max
PY2954
bar
-0�88 10�00 -0�94 9�94 -1�00 7�26
1�50 10�00 0�02
PSI
-12�8 145�0 -13�6 144�2 -14�6 105�2 21�8 145�0
0�2
MPa -0�088 1�000 -0�094 0�994 -0�100 0�726 0�150 1�000 0�002
ΔP = increments