9.5.2 Reset all parameters to factory setting
►
Select [rES]�
►
Touch [Set] and keep it touched until [----] is displayed�
►
Touch [Mode/Enter] briefly�
It is recommended to take down your own settings in the table before
�
10 Operation
After power on, the unit is in the Run mode (= normal operating mode)� It carries
out its measurement and evaluation functions and provides output signals
according to the set parameters�
Operating indicators
(→ 7 Operating and display elements)
Reset the lag indicator (if [LED] = [HInd] or [LInd]):
►
Touch [Set] for 1 second�
> The two lag indicator LEDs jump to the current position of the pointer�
10.1 Read set parameters
►
Touch [Mode/Enter] until the requested parameter is displayed�
►
Touch [Set] briefly�
> The unit displays the corresponding parameter value for about 15 s� After
another 15 s it returns to the Run mode�
10.2 Error indications
[OL]
Overload pressure (measuring range exceeded)�
[UL]
Underload pressure (below measuring range)�
[SC1]
Short circuit in OUT1� The output is switched off as long as the short circuit
persists�
[Err]
Flashing: internal error, invalid entry�
The messages SC1 and Err are displayed even if the display is switched off�