Current output 4 ... 20 mA
Factory setting
Measuring range scaled
m
mm
18
MEW = final value of the measuring range
In the set measuring range the output signal is between 4 and 20 mA�
Faults are also displayed:
Too much light or object too near: 3�5 mA for a rising edge ([ASP] < [AEP]), 20�5 mA for a
falling edge ([ASP] > [AEP])�
Object too far or no object present:
20�5 mA for a rising edge; 3�5 mA for a falling edge�
Voltage output 0 ... 10 V
Factory setting
Measuring range scaled
m
mm
18
MEW = final value of the measuring range
In the set measuring range the output signal is between 0 and 10V�