18
Switching status of the outputs
Output function
Object distance (D)
Output status
[Hno]
D < [SPx]
Closed
D > [SPx]
Open
[Hnc]
D < [SPx]
Open
D > [SPx]
Closed
Example of output function [Hno]
Sampling rate 15 Hz, distance to the object 1200 mm, grey value (18 % remission):
Hysteresis = ± 8 mm (repeatability → 10.3.3 table) x factor 1.5 = 12 mm
-Reset point 1200 mm + (12 mm) = 1212 mm
-Set point 1200 mm - (12 mm) = 1188 mm
10.2.5 Setting of the switch point for hysteresis function OUT1
►
Select the output function [Hno] or [Hnc] at [OU1]�
►
Confirm with [MODE/ENTER]�
►
Select [SP1] and set the switch point�
►
Confirm with [MODE/ENTER]�
10.2.6 Window function
It is possible to define a window for the object recognition for each of the two
outputs (OUT1 / OUT2)�
Switches off when the object is detected
[nSPx] = switch point "near"; [FSPx] = switch point "far"; FE = window
If the measured value is between the switch point "near" [nSPx] and the switch
point "far" [FSPx], the output is open (when [OUx] = [Fnc])�