5
UK
liability for consequences of misuse by the operator� Improper installation and
use of the measurement devices results in a loss of the warranty claims�
3 Functions and features
The unit monitors the standard volume flow of compressed air in industrial use�
It detects the 4 process categories flow velocity, volumetric flow quantity, con-
sumed quantity, medium temperature�
• Applications: compressed air systems in industrial use�
• All indications apply for standard volume flow to DIN ISO 2533, i�e� volume flow
at 1013 hPa, 15 °C and 0 % relative air humidity�
• The unit can be set to different standard conditions (→ 9.5.5 and 9.5.6).
• The general operating conditions of compressed air equipment apply�
• Pressure Equipment Directive (PED): Devices with a measuring section comply
with art� 3 sec� (3) of the Directive 97/23/EC and are designed and manufac-
tured for stable gases of the fluid group 2 in accordance with sound engineer-
ing practice�
4 Function
4.1 Processing of the measured signals
• The unit displays the current process values�
• It generates 2 output signals according to the parameter setting�
OUT1: 4 selection options
Switching signal for volumetric flow limit value ����������������������������������� (→ 9.2.1)
or switching signal for flow velocity limit value ������������������������������������ (→ 9.2.1)
or pulse sequence for quantity meter ������������������������������������������������� (→ 9.3.1)
or switching signal for preset counter ������������������������������������������������� (→ 9.3.2)
OUT2: 6 selection options
Switching signal for volumetric flow limit value ����������������������������������� (→ 9.2.2)
or switching signal for flow velocity limit value ������������������������������������ (→ 9.2.2)
or switching signal for temperature limit value ������������������������������������ (→ 9.4.1)
or analogue signal for volumetric flow quantity ����������������������������������� (→ 9.2.3)
or analogue signal for flow velocity ����������������������������������������������������� (→ 9.2.3)
or analogue signal for temperature ����������������������������������������������������� (→ 9.4.2)
Instead of an output OUT2 (Pin2) can be used as an input
for an external reset signal: ���������������������������������������������������������������� (→ 9.3.5)