4.7 Volumetric flow or temperature monitoring / analogue func-
tion
Current output
MEW
AEP
ASP
12
80
100
110
-40
-20
-50
[°C]
[%]
-130
-120
0
100
120
130
[mA]
Characteristics of the analogue output according to the standard IEC 60947-5-7
1: Output current
2: Volumetric flow quantity
3: Temperature
4: Display range
5: Measuring range
6: Range between analogue start point and analogue end point
7: The unit is in the error state (FOU = OFF)
8: The process value transmitted in an analogue way is therefore below the display range
9: Curve of the analogue signal at factory setting
10: Curve of the analogue signal with shifted ASP and AEP
11: The process value transmitted in an analogue way is therefore above the display range
12: The unit is in the error state (FOU = ON)�
ASP = analogue start point: determines at which measured value the output signal is
4 mA�
AEP = analogue end point: determines at which measured value the output signal is
20 mA�
VMR = final value of the measuring range
= 100 %
Minimum distance between ASP and AEP = 20 % of the measuring range�
In the set scaling range the output signal is between 4 and 20 mA�