After mounting, wiring and setting check whether the unit operates
correctly.
When the supply voltage is applied, all LEDs light and go off one after
the other.* The unit is then ready for operation.
*During this time the output is switched according to the programming: ON
with the NO function and OFF with the NC function.
Failure indication
: In the case of a short circuit the function indicati-
on and the red LED row are lit alternately.
Technical data
ENGLISH
29
Installation and set-up / Operation / Maintenance
Operating voltage [V] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 ... 36 DC
1)
Current rating [mA]. . . . . . . . . . . . . . . . . . . . . 400; short-circuit protection;
reverse polarity protection / overload protection
Voltage drop [V] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 2.5
Current consumption [mA] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 100
Liquids
Medium temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
Setting range [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ... 300
Greatest sensitivity [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ... 60
Max. temperature gradient of medium [K/min] . . . . . . . . . . . . . . . . . . . 300
Response time [s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ... 2
Power-on delay time [s] . . . . . . . . . . . . . . . . . . . . . . . 15, optically indicated
Pressure rating [bar] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
(only for the flow monitor, not for the adapter)
Operating temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 67 (IEC 60529) / (UL50)
Shock resistance [g]. . . . . . . . . . . . . . . . . . . . 50 (DIN / IEC 68-2-27, 11 ms)
Vibration resistance [g] . . . . . . . . . . . . . . 20 (DIN / IEC 68-2-6, 55-2000 Hz)
Housing material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PBT-GF 20
Sensor material . . . . . . . . . . . . . . . . . . . . . . . . . . . stainless steel (316S12);
O-ring: FPM 31x1.5 sw 80° Shore A
1)
to EN50178, SELV, PELV;
referring to UL: see page 26 (Electrical connection).