20
Further setting options
(
→
page 27)
• The HI-Teach is sufficient for the majority of waterbased applicati-
ons. Optional: adjustment to minimum flow (
LO-Teach
).
• Set the switch point and the trigger point (for fast reaction to
rapid changes in flow velocity.
• Manual adjustment to maximum flow.
• Manual adjustment to maximum flow / monitoring and optical
indication of excess flow.
• Manual adjustment to minimum flow / flow standstill.
• Activate / deactivate the function for remote adjustment.
•
Installation
Mounting
→
page 24, electrical connection
→
page 26.
•
HI-Teach
Apply the operating voltage.
After approx.
15 s
the unit is ready.
Allow the medium to flow through the system at the required
maximmum flow rate (HI)
.
•
The unit is ready for normal operation.
Press the
Learn/Set
button and
keep it pressed.
The green LEDs on the right and
on the left flash,
after 5 s the LED bar (green) fills
from left to right
(release the button as soon as
the first LEDs light).
LED 9 flashes for approx. 15 s,
then the indication goes off
briefly.
The unit stores the current flow
as maximum flow and passes
into the operating mode.
LO
HI
LO
HI
HI
LO
>5...<10
M
S
Brief adjustment instructions