Operating instructions

Monitor 

FR-2 / FR-2N

7390954 / 00

 

01 / 2013

UK

Содержание ecomot200 FR-2

Страница 1: ...Operating instructions Monitor FR 2 FR 2N 7390954 00 01 2013 UK...

Страница 2: ...4 1 Display stand by mode 9 5 Installation 9 5 1 Installation of the device 9 5 2 Installation of the sensors 10 6 Electrical connection 10 6 1 Terminal connection 10 6 2 Voltage supply power 10 6 2...

Страница 3: ...Programming example DT1 Delay Time output 1 19 8 2 Notes on programming 20 8 2 1 RUN mode 20 8 2 2 Time Out function 20 8 2 3 Numerical entries 20 8 2 4 Factory Reset 21 8 2 5 KEY function locking 21...

Страница 4: ...elf with operating conditions installation and operation Keep this document during the entire duration of use of the device Adhere to the warning notes and safety instructions 1 1 Symbols used Instruc...

Страница 5: ...the operating elements and at the terminals for the supply of connected sensors The wiring of all signals in connection with the SELV circuit of the device must also comply with the SELV criteria saf...

Страница 6: ...f the additional internal heating the operating elements and the housing walls can have high perceptible temperatures when touched in hot environments 2 7 Tampering with the device In case of malfunct...

Страница 7: ...otors 4 Switching outputs 5 Signals depending on the selected switching functions WARNING The device is not approved for safety related tasks in the field of operator protection Using an electrical co...

Страница 8: ...ted PRG Programming mode setting of the parameter values KEY Locking 1b Actual values and parameter values 5 digit numerical Rotational speed 0 60 000 RPM Pulses 0 1 1 000 0 Hz Outside the value range...

Страница 9: ...Panel for labelling F xN device with NAMUR input 4 1 Display stand by mode If no button is pressed for more than 10 minutes the device changes to the stand by mode Values and units are no longer visib...

Страница 10: ...A I 6 0mA Sensor supply 10 20 Terminal connection WARNING Do not use unconnected terminals such as terminal 9 as support point terminal 6 2 Voltage supply power Voltage supply see type label The devic...

Страница 11: ...sors The connection of mechanical switch contacts is not recommended since they tend to bounce and produce faulty pulses The terminals 5 6 can be used for the sensor supply or for the reset inputs onl...

Страница 12: ...s Note on F xN The 24 V DC signal voltage required for the reset inputs is not available to the F xN This must be taken from an external voltage source The reference point GND of the external power su...

Страница 13: ...outputs Out1 2 The transistor outputs need an external voltage of 24 V DC on terminal 3 Connect the reference point GND of the external power supply to terminal 1 of the monitor Otherwise no switching...

Страница 14: ...n the parameters arranged in columns RUN mode Parameter range and PRG mode DIM FO1 SP1 FO2 SP2 SO1 FW2 SO2 FW1 VER HY1 HY2 ST1 ST2 DT1 FT1 DT2 FT2 NC1 Input 1 RPM Hz Input 2 RPM Hz 1 2 A 3 B NC2 1 Dis...

Страница 15: ...utput blocked when the current value is above the switch point SPx error message overspeed 5 Relay is energised transistor output switched within a frequency range acceptable range 6 Relay is de energ...

Страница 16: ...Wx inactive 0 FWx active 1 FOx 5 relay de energised relay remains de energised FOx 6 relay energised relay de energised Values 0 inactive 1 active Default value 0 7 1 4 NCx Number of Cams on inputs 1...

Страница 17: ...e determines the distance between the switch off point and the switch point SPx Prevents a possible chattering of the switching output In connection with the switching functions 5 and 6 FOx an accepta...

Страница 18: ...alue is above or below the switch point for more than the time set here Values 0 0 1000 0 s Default value 0 0 no delay time 7 2 5 FTx Fleeting Time for outputs 1 2 If an event occurs the output change...

Страница 19: ...alue 5 Acknowledgement of the set parameter value Enter 3 s 6 Return to the RUN mode Enter 3 s 8 1 Programming example DT1 Delay Time output 1 Operation Display Change from the RUN mode to the paramet...

Страница 20: ...RUN mode During programming the unit internally remains in the RUN mode RUN indicator visible This means that until a new value is acknowledged with Enter the unit carries out its monitoring function...

Страница 21: ...5 KEY function locking The unit can be locked to prevent incorrect entries After locking only the actual value indication can be switched with the and buttons Parameter range and PRG mode can no longe...

Страница 22: ...the test mode Apply the operating voltage and press Enter simultaneously The display indicates the parameter range 11 and TST In addition to the system and application parameters the parameters for t...

Страница 23: ...y Values 1 5 1 fast 5 slow Default value 1 TSx Test Start on input 1 2 Initial value of the test frequency Values 1 60 000 RPM or 0 1 1000 0 Hz Default value 50 RPM TPx Test Stop on input 1 2 Final va...

Страница 24: ...types PNP NPN NAMUR NAMUR to EN 50227 Sensor supply 24 V DC 8 2 V DC Input frequency 5 kHz 5 kHz Relay outputs 2 changeover contacts potential free Switching current 6 A 6 A Switching voltage 250 V AC...

Страница 25: ...found at www ifm com Data sheet search Article number 11 2 Approvals standards EC declarations of conformity approvals etc can be downloaded at www ifm com Data sheet search Article number More inform...