72
ifm
Operating Instructions IO-Link Master with EtherNet/IP interface StandardLine 4 Ports IP 69K (AL1121)
2017-05-31
Appendix
>
Mapping: Status information
23006
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
reserved
reserved
reserved
reserved
X04:
Short / OL
X03:
Short / OL
X02:
Short / OL
X01:
Short / OL
reserved
reserved
reserved
reserved
reserved
reserved
Sensor PWR
AUX PWR
Legend:
X0n:
Short / OL
Occurrence of a short circuit
or of an overvoltage on the
IO-Link port
1 bit
0x0 = without errors
0x1 = short circuit or overvoltage detected
Sensor PWR
Status of the supply voltage
US
1 bit
0x0 = supply voltage US not available
0x1 = supply voltage US available
AUX power
Status of the supply voltage
UA
1 bit
0x0 = supply voltage UA not available
0x1 = supply voltage UA not available
>
Mapping: IO-Link port information
23465
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
reserved
Wrong PD
Output Length
Wrong PD
Input Length
Wrong
Cycle Time
Wrong
VID / DID
Invalid Data
Bit
Device Conn
IOL Mode
reserved
VID (LSB)
VID (MSB)
DID (LSB)
DID
DID (MSB)
reserved
Event Mode
Event Type
Event Source
Event Instance
Event Code 1
Event Code 2
Event Mode
Event Type
Event Source
Event Instance
Event Code 1
Event Code 2
Event Mode
Event Type
Event Source
Event Instance
Event Code 1
Event Code 2
reserved
Legend:
IOL mode
Operating mode of the IO-Link
port
1 bit
0x0 = IO-Link inactive
0x1 = IO-Link active