19
ifm
Operating Instructions IO-Link Master with EtherNet/IP interface StandardLine 4 Ports IP 69K (AL1121)
2017-05-31
Electrical connection
>
6.2
IO-Link ports
8526
Ports X01...X04: For use as IO-Link port class A:
►
Con
nect the connector of the IO-Link devices with the M12 sockets
X01 ... X04.
Tightening torque: 0.6...0.8 Nm
Maximum cable length per IO-Link interface: 20 m
► For the connection, use M12 connectors with protection rating IP
69K or higher (z.B. EVF043).
► Tightening torque 0.6...0.8 Nm protective caps (art. no.: E12542).
Tightening torque 0.6...0.8 Nm
>
6.2.1
Input circuit
18629
The inputs of the M12 sockets 4 (pin 2) provide a type 2 behaviour according to standard EN61131-2,
the connected electronics must be rated for this electrically.
>
6.2.2
IO-Link circuits
1863
The IO-Link ports of the device meet the requirements of the IO-Link specification 1.0 bis 1.1.2.
The power supply of the connected IO-Link devices may only take place via the AL1121.
Further information:
→
Technical data
(
Содержание AL1121