Fire Brigade Indicator Panel (FAT)
Operating Instructions
Displays and Operating Controls of the FAT
First
message
Last
message
Further messages
Power
Buzzer OFF
Test
Indication level
Common displays
Fire-Alarm
Fault
Disabled
Fire Brigade Indicator Panel
23/03 Fire
MCP First floor
127/08 Fire
Det. Attic left
Message down
Message up
Indication level
Alarm / Fault /
Disabled
Buzzer OFF / Test
The LED of the indicated level
lights up continuously.
ON : ready for operation
Flashing: internal fault
Power LED :
Keys :
Common LED displays :
LCD plain-text indication :
Message level LEDs
Alarm / Fault / Disabled :
ON: Message(s) of level
shown on LCD
Flashing: Message(s) present,
to be called up with keys
Line 1-2: first / further message
Line 3-4: last message
Alarms are immediately indicated on the LCD. Faults and disabled devices are signalled by a flashing common
message LED and have to be called up with keys. The level shown on the LCD is specified by the relevant common
LED display which lights up continuously.
Common LED displays (operating status)
LED
Colour
Function
Power
green
ON:
Ready for operation
Flashing: Operating voltage ON, no communication
OFF :
No operating voltage, FAT in programming mode
Alarm
red
ON :
Fire alarm(s) present and shown on LCD
Flashing: Fire alarm(s) present but not shown on LCD
OFF :
No fire alarm, FAT in programming mode
Fault
yellow
ON :
Fault message present and shown on LCD
Flashing: Fault message present but not shown on LCD
OFF :
No fault message, FAT in programming mode
Disabled
yellow
ON :
Disabled device message present and shown on LCD
Flashing: Disabled device message present but not shown on LCD
OFF :
No disabled device message, FAT in programming mode