Alphanumeric display 

A message on the alphanumeric display always comprises 2 lines and starts in the first line with zone and detector 
numbers, which are separated by a slash. 

If several messages  of one level are present (alarm, fault; disabled), the upper part shows, in order of time, the first 
message, and the lower part, the last message. When scrolling with the “further messages” keys, the next message 
in the upper part is indicated. After 30 seconds without any actuation, the display is automatically reset to the first 
and last messages. 

Only messages of the alarm level are immediately shown on the LCD without any operator intervention. Messages of 
the fault and disabled device levels are signalled by flashing common message LEDs and have to be called up with 
the “indication level” key. The relevant LED lights up continuously to specify the selected level. If messages of the 
fault or disabled device level are indicated, the display is automatically reset after 30 seconds, without any further 
actuation of the FAT, to the alarm level (fire alarms present ) or to normal indication (no current fire alarms).  

Indication of normal operation : 

(no alarm message) 

Indication of messages :

 

First
message

Last
message

              
      FAT  2002   
       Company
 21.02.02  12:23:56

 

First
message

Last
message

   23/12    Fire  
MCP  First floor  
  127/8     Fire  
Det.  Attic left  

 

The LCD lighting is activated every time a key is pressed or by any new event. It goes out after approximately 30 
seconds. The display remains illuminated if fire alarms are present. 

Acoustic signaller 

The acoustic signaller (Piezo buzzer) indicates alarms.  It is switched off by pressing the “Buzzer OFF / Test” key 
(double function). Any new alarm message re-activates the buzzer. 

Operating controls 

The FAT has four keys for operation: 

 

Two “Further Messages“ cursor keys to scroll the messages of one indication level 

 

One “Level” key to change the indication level (LCD) 

 

One “Buzzer OFF / Test” key (hold down key for 5 seconds 

ð

 to trigger indication test) 

Flashing LEDs in the keys signal that further information in the respective direction selected can be called up with this 
key (e.g. scrolling the messages of one level). 

The “level” key is used to change the indication level (alarm, fault, disabled). The change-over function is only active if 
messages are present at the fault and / or disabled device levels. 

The “Buzzer OFF / Test” key is used to acknowledge acoustic signals and to perform the indication test. 

Indication test 

Press the “Buzzer OFF / Test” key for more than 5 seconds to perform an indication test, which lasts at least 5 
seconds or as long as the key is held down. During this test, all dots of the LCD matrix are controlled, all LEDs and 
the LCD lighting are switched on and the buzzer is activated. 

To set the time / date 

Date and time are automatically transferred from the central fire detection device (BMZ)  and can be overwritten if 
relevant messages are sent via the interface. Manual setting is also possible.  

To enter the edit mode, press both cursor keys simultaneously with the panel in normal operation (no messages 
indicated). The digit which flashes can be edited and changed with the cursor keys. Press the “indication level“ key to 
select the next digit. The edited data will be overwritten if the time / date is transferred via the serial interface! 

To leave the edit mode, press both cursor keys or the "indication level" key when reaching the end of the line.  