1    Technical details

 

1.1

 

Product specifications 

1.1.1

 

Product name : Temperature Sensor 

1.1.2

 

Model name : FI–ST4-* 

1.1.3

 

Product Overview : This product is a temperature sensor that measures fluid 
  temperature by embedding RTD-PT100 sensor. 

1.1.4

 

Product specifications 

Model Name 

FI-ST4-* 

Explosion-proof rating 

II 1G Ex ia IIC T4…T6 Ga 

Ambient Temperature 

-20℃ ~ +50℃/+65℃/+100℃ 

Process Temperature 

T6 : -20℃ ~ +50℃ 
T5 : -20℃ ~ +65℃ 

T4 : -20℃ ~ +100℃ 

Rating 

DC 3 V under, 300 mA under 

Sensor Type 

PT 100Ω 

Lead Length 

Max50,000 

Electric Strength 

Insulation Test at 500 Vac, 60sec 

Material 

Protection Tube 

SUS 304 / SUS 316 

Spring 

SUS 304 / SUS 316 

Metal Braid 

Tinned Copper 

International Protection 

IP 20 

Epoxy 

832HT (Black) 

1.1.5

 

Overview of the explosion-proof rating 

Ex 

This device is a explosion-proof device. 

ia 

The device is designed by applying a non-ignition explosion-proof structure. 

IIC  Can be installed in the place where gas corresponding to gas category IIC is used 

T6..

T4 

T6...T4 temperature grade applied according to the temperature range of the measured 
fluid. 

1.1.5.1

 

Barometric pressure : 80kPa ~ 110kPa 

1.1.5.2

 

Ambient temperature : -20℃ ~ +50℃/+65℃/+100℃ 

1.1.5.3

 

Humidity : not more than 95% 

1.1.5.4

 

Installation location : indoor or outdoor 

1.1.6

 

Application  Criteria  :  Mandatory  safety  certification  notice  for  protective  devices(Notice  No.  ISO 
9001:2015 & ISO/IEC 80079-34) 

1.1.7

 

Installation criteria :    IEC 60079-14 
Applicable standard :   
IEC 60079-20:2017, IEC 60079-11:2011, EN IEC 60079-0:2018, EN 60079-11:2012 

* Specific conditions of use.

 

i.      The equipment is intended to be connected with Zener barrier. It shall be taken into account 

to follow IEC 60079-14 when installing by the user/installer. 

ii.    The equipment shall not be instalied in a location where the external conditions are   
        conductive to the build-up of electrostatic charge on the enclosure surface. In addition, the 

equipment shall only be cleaned with a damp cloth.   

iii. The flying leads of the temperatyre sensor must be terminated within an enclosure which 
      provides a degree of protection of at least IP20 with protection suitable for area of installation. 
 

Содержание FI-ST4 Series

Страница 1: ...duct Temperature Sensor User s Guide REV 0 Date 2021 03 21 Document number FI 2021 0321 FINE ENG CO Address 507Ho E Dong 30 SongdoMirae ro Yeonsu gu Incheon Metropolitan City Korea TEL 032 433 2697 Fa...

Страница 2: ...5 2 1 Scope of application 5 2 2 scope of supply 5 2 3 Product transportation 5 2 4 Installing the product 6 2 5 Machine Operation and Precautions 7 3 Maintenance and Management 8 3 1 Inspection and...

Страница 3: ...T6 T4 T6 T4 temperature grade applied according to the temperature range of the measured fluid 1 1 5 1 Barometric pressure 80kPa 110kPa 1 1 5 2 Ambient temperature 20 50 65 100 1 1 5 3 Humidity not m...

Страница 4: ...afety certification 1 3 1 1 Product name Temperature Sensor 1 3 1 2 Model name FI ST4 S M PT PT Thread Type Meter Thread Type Standard Type Released sequence Type of sensor Company English abbreviatio...

Страница 5: ...s and shall be properly protected against rust and corrosion by using materials that can be buffered such as air caps and newspapers 2 3 1 2 Transport method 2 3 1 2 1 In principle packaged products s...

Страница 6: ...When installing an explosion proof electrical device the following specifications shall be compared to the technical specifications to verify that they are consistent a Rated voltage and current rate...

Страница 7: ...and components installed inside and outside and provide the operator with knowledge and training prior to installation to ensure safe installation 2 4 2 2 7 During the installation process of this pr...

Страница 8: ...ular inspection 3 1 3 3 Samples shall be inspected visually closely or in detail and the size and composition of all samples shall be determined according to the purpose of the inspection 3 1 3 4 Cont...

Страница 9: ...e or damage and install the product in accordance with appropriate working procedures 3 2 3 In particular this product must be careful because cracks may occur on the sealing part of the sith and do n...

Страница 10: ...9 3 2 7 Regular inspection items in Table 1 shall be classified according to the procedures in Figure 1 Figure 1 Regular inspection procedure...

Страница 11: ...uately protected from corrosion weather vibration and other adverse conditions o o o o o o o o o 3 The electrical insulator is clean and dry o o When inspecting each electric device with a explosion p...

Страница 12: ...mage caused by natural disasters fire salt earthquake storm and flood lightning artificial impact etc 3 3 2 5 A S Free service and contact information TEL 82 32 433 2697 FAX 82 32 433 2698 3 3 2 6 If...

Страница 13: ...0 0 15 0 002 x t 0 3 0 005 x t 200 0 55 1 3 100 0 35 0 8 0 0 15 0 3 100 0 35 0 8 200 0 55 1 3 300 0 75 1 8 400 0 95 2 3 500 1 15 2 8 600 1 35 3 3 Interdial line and standard winding method Wiring Meth...

Отзывы: