Fan Coils

INSTALLATION, OPERATION, & MAINTENANCE MANUAL

8

SECTION ONE — Receipt & Initial Installation, Cont'd.

some location where an indication of drain flow restriction 
may be readily observed. Units furnished with a “tell-tale” 
connection should be sloped very slightly towards the 
drain outlets. The differential height of the trap inlet to 
outlet must be at least one inch greater than the total 
static pressure on the unit. The height from the drain 
outlet to the bottom of the trap must not be less than 
the total static pressure. The condensate drain hose 
should be secured with a clamp after installing.

Ductwork Connections

All ductwork and/or supply and return grilles should 
be installed in accordance with the project plans and 
specifications. If not included on the unit or furnished from 
the factory, supply and return grilles should be provided as 
recommended in the product catalog.

For units with no return-air ductwork, check local code 
requirements for possible application restrictions. All units 
must be installed in areas that are non-combustible.

Some models are designed to be connected to duct-work 
with a MINIMUM amount of external static pressure. 
These units may be damaged by operation without 
the proper ductwork connected. Consult the approved 
submittals and the product catalog for unit external static 
pressure limitations.

Units provided with outside air for ventilation should have 
some form of low-temperature protection to prevent coil 
freeze-up. This protection may be any of several methods 
such as a low-temperature thermostat to close the outside 
air damper or a preheat coil to temper the outside air 
before it reaches the unit.

It should be noted that none of these methods will 
adequately protect a coil in the event of power failure. 
The safest method of freeze protection is to use glycol in 
the proper percent solution for the coldest expected air 
temperature.

Horizontal plenum type CPY Short Ship Time (SST) units 
may be shipped with a bottom return-air inlet. These units 
may be converted to rear return by removing the bottom 
inlet filter retainer clips and filter, then removing the 

plenum rear panel. The rear panel must then be moved to 
the bottom of the unit and reversed so that the top edge 
(when rear mounted) is toward the supply end of the unit 
and reinstalled on the bottom of the plenum. The panel 
should be positioned towards the drain pan to expose 
the one-inch wide filter slot for unit-mounted filters. The 
panel should be positioned against the rear bottom brace 
completely covering the bottom of the plenum on units 
with remote filters.

Hi-Performance plenum-type models HPY SST units may 
be shipped with a bottom return-air inlet. These units 
may be converted to rear return by simply exchanging the 
bottom and rear plenum panels.

Flexible duct connections should be used on all air 
handling equipment to minimize vibration transmissions. 
All ductwork and insulation should be installed to allow 
proper access to all components for service and repair 
such as filters, motor/blower assemblies, etc.

The manufacturer assumes no responsibility for 
undesirable system operation due to improper design, 
equipment or component selection, and/or installation 
of base unit, ductwork, grilles, and other related 
components.

Electrical Connections

The unit serial plate lists the unit electrical characteristics 
such as the required supply voltage, fan and heater 
amperage and required circuit ampacities. The unit wiring 
diagram shows all unit and field wiring. Since each project 
is different and each unit on a project may be different, 
the installer must be familiar with the wiring diagram and 
serial plate on the unit BEFORE beginning any wiring.

All components furnished for field installation by either the 
factory or the controls contractor should be located and 
checked for proper function and compatibility. All internal 
components should be checked for shipping damage, and 
any loose connections should be tightened to minimize 
problems during start-up.

Any devices such as fan switches or thermostats that 
have been furnished from the factory for field installation 

Содержание C Y 02 Series

Страница 1: ...ice Life Fan Coils INSTALLATION OPERATION MAINTENANCE MANUAL Energy efficient compact blower coils Ideal for educational hospitality multi family or other commercial environments Designed for ducted applications Nominal CFM range of 600 to 3 000 CFM ...

Страница 2: ...oducts International Environmental Corporation IEC works continually to improve its products As a result the design and specifications of each product may be changed without notice and may not be as described herein Please contact IEC for information regarding current design and product specifications Statements and other information contained herein are not express warranties and do not form the ...

Страница 3: ...g SECTION TWO Start Up 9 General 10 Cooling Heating System 10 Air System Balancing 10 Eco telligent Motor 11 Water Treatment 12 Water System Balancing 12 Controls Operation SECTION THREE Normal Operation Periodic Maintenance 12 General 13 Motor Blower Assembly 13 Coil 13 Electric Resistance Heater Assembly Table of Contents 13 Electrical Wiring and Controls 14 Valves and Piping 14 Filters Throwawa...

Страница 4: ...s such as clear water or dry nitrogen to avoid possible damage or injury in the event of a leak or component failure during testing Always protect adjacent flammable material when welding or soldering Use a suitable heat shield material to contain sparks or drops of solder Have a fire extinguisher readily available The manufacturer assumes no responsibility for personal injury or property damage r...

Страница 5: ...g and after installation special care must be taken to prevent foreign material such as paint plaster and drywall dust from being deposited in the drain pan or on the motor or blower wheels Failure to do so may have serious adverse effects on unit operation and in the case of the motor and blower assembly may result in immediate or premature failure All manufacturer s warranties are void if foreig...

Страница 6: ... to the unit On those units requiring chilled water and or hot water the proper line size and water temperature should be available to the unit In the case of refrigerant cooling the proper line size and refrigerant type should be available to the unit On units with steam heating coils the proper line sizing and routing should be verified and the maximum steam pressure applied to the unit should n...

Страница 7: ...ing is contained in the drain pan or other device such as an optional extended drain pan or factory drip lip Factory drip lips are field installed and may be packaged separately from the unit Factory supplied cooling coil valve packages will be arranged to locate as much of the package as possible over a standard drip lip If none of the above factory accessories have been provided with the units a...

Страница 8: ... shipped with a bottom return air inlet These units may be converted to rear return by removing the bottom inlet filter retainer clips and filter then removing the plenum rear panel The rear panel must then be moved to the bottom of the unit and reversed so that the top edge when rear mounted is toward the supply end of the unit and reinstalled on the bottom of the plenum The panel should be posit...

Страница 9: ...wed regarding ventilation and safety equipment The manufacturer s directions should be followed for the products being used To repaint the factory baked enamel the finish should be prepared by light sanding with 280 grit sand paper or 000 or 0000 fine steel wool The surface may also be wiped with a liquid surface etch cleaning product such as No Sand or Pasceo These items should be available at mo...

Страница 10: ...g after start up operations CAUTION The air vent provided on the unit is not intended to replace the main system air vents and may not release air trapped in other parts of the system Inspect the entire system for potential air traps and vent those areas as required independently In addition some systems may require repeated venting over a period of time to properly eliminate air from the system A...

Страница 11: ...fer to Appendix B for adjustment procedure Variable Airflow for 0 10 VDC Flo 1 2 3 Terminals Flo 0 4 Terminals Com Pot Adjustment Flo 1 2 3 in the Field Pot Adjustment Flo 0 4 Contact Factory If a factory provided thermostat or DDC controller is utilized then the unit is already correctly configured IEC recommends using the specified thermostat or DDC controller to commission the unit whenever pos...

Страница 12: ...ration After the entire system is balanced these conditions will not exist on properly designed systems Controls Operation Before proper control operation can be verified all other systems must be operating properly The correct water and air temperatures must be present for the control function being tested Some controls and features are designed to not operate under certain conditions For example...

Страница 13: ...ion may result in the heater cycling on the high limit thermal cutout Sheath heaters have automatic reset switches only Open strip heaters have an automatic reset switch with a back up high limit thermal switch Automatic reset switches are as the name implies they reset automatically after the heater has cooled down High limit thermal switches must be replaced once the circuit has been broken The ...

Страница 14: ...e throwaway filters permanent filters may be cleaned and re installed in the unit instead of being discarded when dirty The optional factory permanent filter may be cleaned in hot soapy water to remove any trapped dirt It should then be set aside on edge to dry Before replacing the filter in the unit it should be recharged with some type of entrapment film such as Film Cor Recharging Oil The filte...

Страница 15: ... or left hand while facing into the air stream 4 Complete part description including any numbers On warranty replacements in addition to the information previously listed the unit shipping code which appears on the upper right hand corner of the serial plate is required Contact the factory for authorization to return any parts such as defective parts replaced in warranty All shipments returned to ...

Страница 16: ... unit Proper hot water line size to unit All services to unit in code compliance All shipping screws and braces removed Unit protected from dirt and foreign matter Cooling Heating Connections Protect valve package components from heat Mount valve packages Connect field piping to unit Pressure test all piping for leaks Install drain line and traps as required Insulate all piping as required Install...

Страница 17: ...o the DC common terminal labeled L2 above the potentiometers and to the left of the orange relay 5 Attach the red positive lead of the meter to the red wire that bridges the 0 10VDC outputs high medium and low 6 High Speed Close High speed relay by applying 24V to the High terminal Using a small screwdriver turn the VR3 potentiometer so the meter measures 4 51 Vdc This will set the ECM speed to 90...

Страница 18: ...Attach the red positive lead of the meter to the high speed Flo1 terminal below the Potentiometer 6 High Speed Using a small screwdriver turn the Flo1 potentiometer so the meter measures 4 51 Vdc This will set the ECM speed to 90 of maximum for high speed 7 Medium Speed Using a small screwdriver turn the Flo2 potentiometer so the meter measures 3 53 Vdc This will set the ECM speed to 70 of maximum...

Страница 19: ...f a breach of the Limited Express Warranty IEC will only be obligated at IEC s option to repair the failed part or unit or to furnish a new or rebuilt part or unit in exchange for the part or unit which has failed If after written notice to IEC s factory in Oklahoma City Oklahoma of each defect malfunction or other failure and a reasonable number of attempts by IEC to correct the defect malfunctio...

Страница 20: ...ATION OPERATION MAINTENANCE MANUAL Contact your local IEC Sales Representative for further details and pricing applicable to this product Visit our website iec okc com to find your local IEC Sales Rep IEC Part Number I100 90000950 IOM 100 Revision 12 1 2020 2000 2020 International Environmental Corporation IEC ...

Отзывы: