11
Quick Installation Guide
4.3.4 Output Connections
Door Lock (Power Fail Safe) Connection (Relay 1)
- Connect COM port of Relay 1(Gray with Red stripe) to + 12V (Red wire)
- Connect NC port of Relay 1(Blue with White stripe) to (+) wire of Door Lock Device.
- Connect GND (Black wire) port to (-) wire of Door Lock Devices.
Door Lock (Power Fail Secure) Connection (Relay 1)
- Connect COM port of Relay 1(Gray with Red stripe) to + 12V (Red wire)
- Connect NO port of Relay 1(White with Red stripe) to (+) wire of Door Lock Device
- Connect GND (Black wire) port to (-) wire of Door Lock Devices
Alarm Device Connection (Relay 2)
- Connect COM port of Relay 2 (White) to + 12V (Red wire)
- Connect NO port of Relay 2 (Purple) to (+) wire of Alarm Devices.
- Connect GND (Black wire) port to (-) wire of Alarm Devices
Figure: Door Lock / Alarm Device Connection
CAUTION
: Please add one diode as shown above. A fast recovery diode (Current: Min. 1A), 1N4001 - 1N4007 or
similar is recommended.
Wiegand Data Connection (Applicable to Reader Mode)
-Connect DATA0 IN wire of controller to TTL1/D0 (TTL Output1) wire of
505R/FINGER007 series
(Orange with White
stripe)
- Connect DATA1 IN wire of controller to TTL2/D1 (TTL Output2) wire of
505R/FINGER007
series
(Brown with White
stripe)
CAUTION:
When
505R/FINGER007
series
is using a separate power source, make sure to connect
GND
between
the controller and
505R/FINGER007
series
.