background image

 
 
                                                                                                                 

   

 

 16 

 

36   

Test Alarm time set by command "26"   

37   

Test Alarm time set by command "27" 

39   

Change Chime Bell activating time 

41   

Open door unconditionally 

42   

Close door unconditionally 

43   

Enable QUICK ACCESS MODE 

44   

Disable QUICK ACCESS MODE 

45 

Enable Toggle Mode for Lock control 

46 

Disable Toggle Mode for Lock control 

47 

Enable Unlock followed by Door Contact 

48 

Disable Unlock followed by Door Contact 

51 

Disable Melody sound (turning off both the melody & keypress audio feedback) 

52 

Enable Melody sound 

60 

Change keypad lock-out time when Try-Out error detected 

61 

Set Aux Input #1 Detection from ‘L’ to ‘H’ 

62 

Set Aux Input #1 Detection from ‘H’ to ‘L’ 

63 

Set Aux Input #2 Detection from ‘L’ to ‘H’ 

64 

Set Aux Input #2 Detection from ‘H’ to ‘L’ 

65 

Set Aux Input #3 Detection from ‘L’ to ‘H’   

66 

Set Aux Input #3 Detection from ‘H’ to ‘L’   

67 

Set Exit Button Input Detection from ‘L’ to ‘H’ 

68 

Set Exit Button Input Detection from ‘H’ to ‘L’ 

69 

Set Door-Contact sensor Input Detection from ‘L’ to ‘H’   

70 

Set Door-Contact sensor Input Detection from ‘H’ to ‘L’ 

71 

Activate TTL output to ‘H’ 

72 

Activate TTL output to ‘L’ 

73 

Enable Keypad Input To Enter ID Number 

74 

Disable Keypad Input To Enter ID Number 

77 

Enable Chime Bell Output 

78 

Disable Chime Bell Output 

80 

Set delay time to activate SECURE MODE 

81 

Set Door Open time-out for Door-Contact sensor 

82 

Set number of times of Try-Out 

83 

Set input key press time-out time   

84 

Set Tamper Alarm output port 

88 

Enable Tamper Alarm 

89 

Disable Tamper Alarm 

99 

Re-Initialize and erase all setup data 

 
 
 

Содержание Star 100R

Страница 1: ...User s Manual...

Страница 2: ...ion 5 6 Identifying Supplied Parts 6 7 Installation 6 8 Wiring Color Table 7 9 System Wiring for Typical Application 9 10 Initial Setup 11 11 Operation 14 12 Setting Changes 15 13 Initialization 25 14...

Страница 3: ...ts or short out parts that could result in fire or electric shock Never spill liquid of any kind on the product 7 To reduce the risk of electric shock do not disassemble this product by yourself but t...

Страница 4: ...able to provide the system administrator with complete customized control of the system Besides the above configurable I O interfaced behaviors many of the Star 100R iPASS IP100R internal behaviors ar...

Страница 5: ...5 ports Exit Button Door Contact Aux 1 Aux 2 Aux 3 Output Port 2 ports Form C Relay Output COM NO NC DC12 18V Rating Max 2A 1 port Chime Bell Output DC5V Rating Max 500mA 1 port TTL Output DC5V Rating...

Страница 6: ...a 1ea 5ea 1copy 3 5 40 Screw 3 5 12 Screw Anchor Bolt 4ea 4ea 4ea 7 Installation 7 1 Tear off page 38 and use the provided template to drill two 6 32 holes and one 1 2 hole on the proper location of t...

Страница 7: ...all mount to lock the main unit and make sure that the main unit is locked with wall mount 8 Wiring Color Table SIGNAL COLOR Main Power 12V Red Power Ground GND Black Door Relay Out COM Gray with Red...

Страница 8: ...format you need to set the jumpers as shown above Changes when Wiegand Output Mode is applied TTL Output Orange wire with White stripe Wiegand Data0 Output Chime Bell Output Brown wire with White str...

Страница 9: ...M Grey Red banded wire Connect wire of Door Lock to Power GND wire 9 2 2 Connection of POWER FAIL SECURE Door Lock Connect Door RELAY COM Grey Red banded wire to DC 12V be sure that the existing power...

Страница 10: ...purchase required The Auto dialer function of this unit has not been evaluated by UL Connect the input wire of Auto Dialer to TTL output Orange White banded wire Connect wire of Auto Dialer to DC 12V...

Страница 11: ...do 2 Press from the keypad RF CARD ONLY MODE 3 Present RF Cards as follow to register Configuration Card and User Access Cards Configuration Card User Access Cards Configuration Card again to end tas...

Страница 12: ...ion PIN then to register for each subsequent User Access PIN at a time and then enter the Configuration PIN to complete the registration Configuration PIN User Access PIN Configuration PIN again to co...

Страница 13: ...r PIN is not recognized Alarm RELAY activates for 2sec Red LED lights on for 2sec 3 Duress Password 00 Duress Alarm to TTL output port for 03 sec 4 QUICK ACCESS MODE Disable 5 Chime Bell output Enable...

Страница 14: ...ted for 2 seconds along with sol do sol do melody Unregistered Card or PIN If you do not want to activate the Alarm in case of unregistered access attempt then you can change this setting as shown in...

Страница 15: ...d User Access PIN numbers PIN ONLY MODE 14 Delete User Access Cards or PIN 15 Add User Access Card PIN RF PIN Combination Mode 21 Change Door open time when User Access Card or PIN is granted 22 Chang...

Страница 16: ...ux Input 2 Detection from L to H 64 Set Aux Input 2 Detection from H to L 65 Set Aux Input 3 Detection from L to H 66 Set Aux Input 3 Detection from H to L 67 Set Exit Button Input Detection from L to...

Страница 17: ...Access PIN PIN ONLY MODE Configuration PIN Command PINs to be registered Configuration PIN 12 14 1 Delete User Access Cards RF CARD ONLY MODE RF CARD PIN MODE Configuration Card Command Cards to be de...

Страница 18: ...e Mode Value Activate only in Secure Mode 00 Activate in Safe Secure Mode 50 Setting Value for activating Output Port Activate Output Port Value Activate only Door Relay 01 Activate only Alarm Relay 0...

Страница 19: ...Configuration PIN 12 25 Change Alarm Time When AUX Input 1 Detected 12 26 Change Alarm Time When AUX Input 2 Detected 12 27 Change Alarm Time When AUX Input 3 Detected Refer to Table 1 for OM tt 00 99...

Страница 20: ...m Time Set By Command 26 12 37 Test Alarm Time Set By Command 27 Outputs set by command will be tested Configuration Card Command Configuration PIN 12 39 Change Chime Bell Activating Time tt 00 99 sec...

Страница 21: ...for Arm Disarm for buglar alarm system 12 46 Disable Toggle Mode for Lock Control 12 47 Enable Lock followed by Door Contact If you set Enable Lock followed by Door Contact Door only be locked follow...

Страница 22: ...figuration PIN 12 64 Set AUX 2 Input Detection from H to L AUX 2 input is detected on the falling edge of AUX 2 input Defaulted setting Configuration Card Configuration PIN 12 65 Set AUX 3 Input Detec...

Страница 23: ...put changes the state from logic 1 to logic 0 when it activates Defaulted setting Configuration Card Configuration PIN 12 73 Enable Keypad Input To Enter ID Number Keypad input is enabled to enter the...

Страница 24: ...imum tt 10 sec Configuration Card Command Keypress time out time Configuration PIN 12 84 Set Tamper Alarm Output Port Refer to Table 1 for OM Defaulted Output port 02 Alarm Relay Configuration Card Co...

Страница 25: ...out four bolts on the back 2 As the left picture make two jumpers short in state of being on power 3 3 color LED blinking with beep sound indicates success of initialization 1 Main power off 2 Connec...

Страница 26: ...ant to Part 15 of the FCC Rules These limits are designed to this equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may...

Страница 27: ...initialization Because system is the status of initialization register mode selection master card or PIN and user 1 100R Mode Selection Mode Number ENT RF Only 01 ENT RF P W 02 ENT PIN Only 03 ENT RF...

Страница 28: ...F Only 01 ENT RF P W 02 ENT PIN Only 03 ENT RF or PIN 05 ENT 2 Enter the master card or PIN 4 to 6digit mode 03 or 05 ENT 3 By modes enter the master card PIN and password 4 Enter the master card or P...

Страница 29: ...ard or PIN 4 to 6digit mode 03 or 05 ENT b Enter mode 73 ENT to Enable Keypad Input To Enter ID Number c Enter the master card or PIN 4 to 6digit mode 03 or 05 ENT d Enter 4 ENT to delete user access...

Страница 30: ...tializing connect jumper switches which are located by LEDs bottom of PCB 4 Make sure of system initialization At this time 3 LEDs should be blinked simultaneously 5 After power is off assemble the re...

Страница 31: ...application software is set up as shown below Make sure of connecting communication cables 1 Make sure that connecting communication cables between the 100R and the PC 2 Make sure of cable s maximum...

Страница 32: ...ter 60 ENT to Change Enter 2 digit of Try Out Times ENT e g 10 ENT 10 Interrupt entering a keypad for 10 min 2 Although it goes on definite time buzzer doesn t go off continuously Initialize the produ...

Страница 33: ...ta is not transferred to a computer or other data is transferred Cause A connectivity error between the exit reader and the 100R A communication error between the exit reader and the 100R An exit read...

Страница 34: ...mmunication cable with a measuring instrument Check if any noise comes from the Wiegand communication cable with a measuring instrument If a noise exists in the Wiegand communication cable enhance the...

Страница 35: ...rror in connection between the door lock and the 100R A door lock error System malfunction data damaged or lost due to an external noise or a short circuit Solution Check the connection between the do...

Страница 36: ...ervice center 5 Installation See page 6 of this manual The connection between a door lock and the 100R may vary depending on the door lock type and its operation type Normal Open Normal Close Caution...

Страница 37: ...property is located where this product will be used it would be extremely difficult to determine the actual damages that may result from a failure of the product to perform as anticipated and the low...

Страница 38: ...tion Code 1 Company Name 2 Model Name 3 Serial No 4 Original Invoice No 5 Distributor 6 Purchasing Date 7 RMA Request Date Please check your problems Card Reading Power Keypad Communication Relay LCD...

Страница 39: ...39 17 Template...

Страница 40: ...HE5X The specifications contained in this manual are subject to change without notice at any time 5F Ace Techno Tower B D 684 1 Deungchon Dong Gangseo Gu Seoul 157 030 Korea Tel 82 2 2659 0055 Fax 82...

Отзывы: