Installation of Product
p.24
2.2K Resistor Connection for Cut Off Check
You have to connect a 2.2K resistor between the input wire (e.g. Orange wire) and the GND
to apply the Cut Off Check feature. First, select whether or not to check the cutoff status of
each device from
[F5 SETUP MENU] -> CUT OFF SET
. Second, set the desired output that wil
l be generated in the event of a cutoff from
[F5 SETUP MENU] -> CUT OFF ALARM
.
4.3
Output Connection
Door Lock (Power Fail Safe) Connection (Door Relay)
1.
Connect COM wire of Door Relay (Gray wire with Red stripe) to +12V.
2.
Connect NC wire of Door Relay (Blue wire with White stripe) to (+) wire of Door Lock.
3.
Connect GND wire to (-) wire of Door Lock.
Door Lock (Power Fail Secure) Connection (Door Relay)
1.
Connect COM wire of Door Relay (Gray wire with Red stripe) to +12V.
2.
Connect NO wire of Door Relay (White wire with Red stripe) to (+) wire of Door Lock
3.
Connect GND wire to (-) wire of Door Lock.
Alarm Device Connection (Alarm Relay)
1.
Connect COM wire of Alarm Relay (White wire) to +12V.
2.
Connect NO wire of Alarm Relay (Purple wire) to (+) wire of Alarm device.
3.
Connect GND port to (-) wire of Alarm device.
Содержание LX007
Страница 1: ......
Страница 29: ...Installation of Product 8 p 21 1 Wall Mount Unit mm ...
Страница 48: ...Setting Changes 12 p 40 ...
Страница 49: ...p 41 F1 SETUP MENU 1 F1 SETUP MENU ...
Страница 53: ...p 45 F2 SETUP MENU 2 F2 SETUP MENU ...
Страница 91: ...p 83 F10 SETUP MENU 10 5 Module Version The version of the fingerprint module is displayed ...
Страница 104: ...Troubleshooting p 96 If the problem persists please contact service center ...
Страница 107: ...Index 99 ...