Location 22 – 40: Programmable Output Options
Outputs are used to trigger many different devices, the most common being a radio transmitter which
transmits signals back to the alarm monitoring company.
The IDS 805 has 5 positively triggered outputs. Each output triggers with, direct current (DC) 12V and
can supply approximately 100mA of current. If more current is required please use a 12V positively
triggered relay to supply current from a different power source.
Outputs can be set to pulse or latch.
Pulse: The output will rise from 0V to 12V remain at 12V for 3 seconds and return to 0V.
Latch: The output will rise from 0V to 12V and remain in this state until another trigger forces it to go
back to 0V. A light switch is an example of latching as once switched on the light will only go off
again when the switch is returned back to the off position.
Output
Value
Pulse
Latch High
Latch Low
1
1
6
11
2
2
7
12
3
3
8
13
4
4
9
14
5
5
10
15
Locations and their default values
Location Event
Value Action Output
Explanation
22
Alarm
2
Pulse
2
Burglar alarm registered
23
Panic
1
Pulse
1
Panic triggered
24
Low
Battery
0
Battery needs checking
25
Auto-test
0
Panel does a test to the monitoring company
26
Duress
1
Pulse
1
A duress code can be entered
27
AC Fail
0
Alarm loses the 16V AC
28
Close
(Arm)
8
Latch
on
3
Away armed
29
Open
(Disarm)
13
Latch
off
3
Alarm is disarmed
30
AC
Restore
0
16V AC is restored
31
Cancel
0
The alarm has triggered and a valid user code has
been entered
32
Fire
0
Triggered when the [F] key is pressed or a fire zone
triggers
33
Medical
0
[M] key is pressed
34
Strobe
0
This output will latch when an alarm is registered
and will only unlatch once a valid user code is
entered
35
Tamper
0
If tamper per zone or a zone is made a tamper
zone and the tamper condition is triggered will this
output be triggered
36
Silent
Panic
1
Pulse
1
The siren will not sound but this output will trigger
once programmed to alert the monitoring
company.
38
Chime
0
If a chime zone is triggered in the unarmed state,
this output will trigger
39
Communi
cation
Fail
0
If the alarm cannot communicate via the phone
line, this output can trigger another device to alert
the monitoring company of a problem