Location 13: Stay Arming Options
Stay arming is the ability to arm the system and at the same time have selected zones bypassed
automatically. All active zones will be instant zones, including entry/exit zones.
To stay arm, press and hold [5] until armed light comes on.
Location 14: Silent Keypad Panic Options
If this option is enabled then when the panic key [P] is pressed a panic will be registered but the siren will
not sound. If the system is communicating to a security company the signal will be sent.
Value Action
0
Disable
1
Enable
Location 15: Silent Alarm
This option will register an alarm but the siren will not sound and if connected a signal will be sent to the
security company.
Value Action
0
Disable
1
Enable
Location 16: Siren Toot on Arm and Disarm
When the alarm is away armed the siren will sound once and when disarmed from the away armed state
it will sound twice
Value Siren toot
on Arm
Siren toot
on Disarm
0
Off
Off
1
On
Off
2
Off
On
3
On
On
Location 17: Siren Time-out Period
How long the siren will sound once an alarm has been triggered and a user code is not entered to cancel
the alarm.
Value Action
0
The alarm will automatically arm in the stay mode if a user code is entered but
no entry exit zone is triggered
1
The alarm will always arm in the away mode. The quick stay key [5] will be
disabled
2
The alarm will always arm in the away mode. The quick stay key [5] will be
enabled
Value Time-out Value
Time-out
Value Time-
out
0
0.25 sec
6
2 min
12
18 min
1
10 sec
7
3 min
13
21 min
2
20 sec
8
4 min
14
21 min
3
30 sec
9
5 min
15
21 min
4
45 sec
10
10 min
5
1 min
11
15 min