Manifold
The manifold incorporates an air ratio control valve through which degrees of wet or dry foam
mixture can be selected. Compressed air is then injected and the resulting foam / water / air
combination is thoroughly mixed by the X-mixers during discharge.
A By-pass valve is fitted to help obtain the required dry foam flow rate, this valve is adjusted
and set during the installation stage, it is not required during normal operation.
CAFS units are best suited for use with Fresh Water.
For salt water compatible foams, seek advice from the foam agent manufacturers.
FoamLogix - Foam Proportioning System
The FoamLogix system consists of three main components:
1) Foam Pump / Motor Assembly.
2) Control Panel (integral with main pump control panel).
3) Flow measurement and injection manifold.
All three elements combine to provide accurate foam proportioning. From the control panel
the operator can initiate the system, adjust the foam ratio, monitor
‘real time’ water flow rate
and record total water and foam concentrate usage.
The FoamLogix system is powered up when the PTO is engaged. Foam concentrate is only
injected when the
RED
ON
control button is operated.
The Foam ON light (10) will illuminate when the FoamLogix is turned on, and flash when
injecting foam.
The FoamLogix 3.3, 5.0, 6.5 system for Class A or B foams, will inject foam in the range of
0.1% to 6.0%.
Further information is available in the
FoamLogix Model 3.3/5.0/6.5
Description, Installation