IDEC SmartRelay functions
IDEC SmartRelay Manual
171
The thermocouples available have the following technical
data: -30 to +70
°
C, 0 to 10 VDC.
Configuration (example):
Press
View in parameter assignment mode (example):
Application
Internal mapping
-30 to +70
°
C=0 to 10 V DC
0 to 1000
0
°
C
300
→
Offset = -30
Range of values:
-30 to +70
°
C=100
1000
→
Gain = 100/1000 = 0.1
On threshold = 15
°
C
Threshold = 15
Off threshold = 5
°
C
Threshold = 5
B3 1+
On =+00015
Off =+00005
Protection mode
On threshold
Off threshold
▲
B3 2
A
=00.10
B
=-00030
p
=0
Gain
Offset
Decimals in the message text
(if used)
B3 1
On =+00015
Off =+00005
On threshold
Off threshold
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com