3: D
EVICE
A
DDRESSES
3-14
FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
D8105 RS232C DSR Input Control Signal Option (Port 2 and Port 3)
Special data register D8105 is used to control data flow between the SmartAxis RS232C port 2 and port 3 and the remote terminal
depending on the DSR (data set ready) signal sent from the remote terminal.
D8106 RS232C DTR Output Control Signal Option (Port 2 and Port 3)
Special data register D8106 is used to control the DTR (data terminal ready) signal to indicate the SmartAxis operating status or
transmitting/receiving status.
D8110-D8121 Connection (1 through 3) Connected IP Address
The IP address of the remote host accessing the connection 1 through 3 is stored in special data registers.
Example) Connection 1 Connected IP Address: aaa.bbb.ccc.ddd
D8110=aaa, D8111=bbb, D8112=ccc, D8113=ddd
D8130-D8132 Connection Connected Port Number
When connections are established with other network devices, the port numbers of the connected network devices are stored in
these special data registers.
D8130 : Connection 1 Connected Port Number
D8131 : Connection 2 Connected Port Number
D8132 : Connection 3 Connected Port Number
D8148, D8157, D8166 Remote I/O Communication Error Status
When a communication error occurs between the remote I/O communication slave and master, the details of the communication
error are stored in these special data registers.
D8148 : Remote I/O Slave 1 Communication Error Status
D8157 : Remote I/O Slave 2 Communication Error Status
D8166 : Remote I/O Slave 3 Communication Error Status
D8149-D8156, D8158-D8165, D8167-D8174 Remote I/O Analog Input Values
The analog input values (0 to 10 VDC) to the remote I/O analog inputs are converted to digital values (0 to 1000) and stored in the
special data registers allocated to each remote I/O slave.
D8149=AI10, D8150=AI11, D8151=AI12, D8152=AI13, D8153=AI14, D8154=AI15, D8155=AI16, D8156=AI17
D8158=AI20, D8159=AI21, D8160=AI22, D8161=AI23, D8162=AI24, D8163=AI25, D8164=AI26, D8165=AI27
D8167=AI30, D8168=AI31, D8169=AI32, D8170=AI33, D8171=AI34, D8172=AI35, D8173=AI36, D8174=AI37
0
2
0
1
0
0
D8105
0
3
Port 2
0
5
0
4
7
8
Port 3
000:
DSR is not used for data flow control
001:
When DSR is on, SmartAxis can transmit and receive data
010:
When DSR is off, SmartAxis can transmit and receive data
011:
When DSR is on, SmartAxis can transmit data (busy control)
100:
When DSR is off, SmartAxis can transmit data
Others:
Same as 000
Bit
15
Bit
Bit
Bit
Bit
0
2
0
1
0
0
D8106
0
3
Port 2
Port 3
7
8
00:
DTR is on (off while SmartAxis is stopped)
01:
DTR is off
10:
DTR is on while SmartAxis can receive data (auto switching)
11:
Same as 00
Bit
15
Bit Bit
Bit
Bit
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...