IDEC MicroSmart pentra FC5A-D12K1E Скачать руководство пользователя страница 58

4: O

PERATION

 B

ASICS

4-12

W

EB

 S

ERVER

 CPU M

ODULE

 U

SER

S

 M

ANUAL

FC9Y-B1278

Simulate Operation

Before downloading the user program, you can simulate the operation on the WindLDR screen without connecting the 
Web server CPU module.
From the WindLDR menu bar, select 

Online

 > 

Simulation

. The Simulation screen appears.

To change an input status, place the mouse pointer on the input and right-click the mouse. In the pop-up menu, select 
Set or Reset to set or reset the input.
To quit simulation, from the WindLDR menu bar, select 

Online

 > 

Simulation

.

Download Program

You can download the user program from WindLDR running on a PC to the Web server CPU module.
From the WindLDR menu bar, select 

Online

 > 

Download

. The Download Dialog appears, then click the

 OK

 button. The 

user program is downloaded to the Web server CPU module.

Note: 

When downloading a user program, all values and 

selections in the Function Area Settings are also 
downloaded to the Web server CPU module.

Note: 

The Download Dialog is also shown by selecting 

Home > Download

.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание MicroSmart pentra FC5A-D12K1E

Страница 1: ...FC5A SERIES FC9Y B1278 User s Manual Web Server CPU Module Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 3: ...hile moving or transporting the Web server CPU module otherwise damage or malfunction of the Web server CPU module will result Prevent metal fragments and pieces of wire from dropping inside the Web server CPU module housing Put a cover on the Web server CPU modules during installation and wiring Ingress of such fragments and chips may cause fire hazard damage or malfunction Use a power supply of ...

Страница 4: ...2011 B 1278 1 Error code 8 is added in the error code table for EMAIL instruction Notes for devices of EMAIL and PING instructions are updated January 2013 B 1278 2 Descriptions for pass through over Modbus RTU is added in chapter 7 Wrong descriptions are revised Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 5: ... Chapter 10 E mail Detailed description on configurations and procedure to configure e mail function in WindLDR Chapter 11 PING Instruction Detailed description on PING instruction Chapter 12 Web Server Detailed descriptions on Web server function and system library for user s web pages Chapter 13 Troubleshooting Procedures to determine the cause of trouble and actions to be taken when any trouble...

Страница 6: ...ntra User s Manual Advanced Volume Describes instruction list move instructions data comparison instructions binary arithmetic instructions boolean computation instructions shift rotate instructions data conversion instructions week programmer instructions interface instructions program branching instructions refresh instructions interrupt control instructions coordinate conversion instructions av...

Страница 7: ...s 2 5 CPU Module Terminal Arrangement and I O Wiring Diagrams Slim Type Web Server 2 10 Dimensions 2 11 CPU Modules Slim Type Web Server 2 11 CHAPTER 3 Installation and Wiring Installation Location 3 1 Assembling Modules 3 2 Disassembling Modules 3 2 Installing the HMI Module 3 3 Removing the HMI Module 3 4 Securing USB Extension Cable Using Cable Tie 3 5 Mounting on DIN Rail 3 6 Removing from DIN...

Страница 8: ... Program 4 8 Start WindLDR 4 8 Disable Tag Function 4 9 Edit User Program Rung by Rung 4 9 Simulate Operation 4 12 Download Program 4 12 Monitor Operation 4 13 Quit WindLDR 4 13 CHAPTER 5 Function Area Settings Function Area Settings 5 1 Program Capacity Selection 5 2 Applications 5 2 Description of Functions 5 2 Programming WindLDR 5 2 Watchdog Timer Setting 5 3 Applications 5 3 Description of fu...

Страница 9: ...ew 9 1 Modbus TCP Client 9 1 Modbus TCP Client Specifications 9 1 Programming WindLDR Modbus TCP Client 9 3 Processing Requests 9 6 Modbus TCP Server 9 7 Modbus TCP Server Specifications 9 7 Programming WindLDR Modbus TCP Server 9 8 Modbus TCP Communication Format 9 9 CHAPTER 10 E mail EMAIL Send E mail 10 1 Operation Details 10 1 Valid Devices 10 1 Devices in EMAIL Instruction 10 1 Special Data R...

Страница 10: ...aph 12 16 JavaScript Functions 12 18 Reading Device Data 12 18 Writing Device Data 12 18 CHAPTER 13 Troubleshooting ERR LED 13 1 Reading Error Data 13 2 Special Data Registers for Error Information 13 3 General Error Codes 13 3 CPU Module Operating Status Output and ERR LED during Errors 13 4 Error Causes and Actions 13 4 User Program Execution Error 13 6 Troubleshooting Diagrams 13 8 APPENDIX CGI...

Страница 11: ...ucture and powerful communication functions as well as convenient functions The Web server CPU module has the compatibility with the other FC5A Series MicroSmart and can use all optional modules The Web server CPU module has 12 I O terminals transistor output and operates on 24V DC Using expansion I O modules the I O points can be expanded to a maximum of 492 The program capacity of the Web server...

Страница 12: ...odule even after the memory cartridge is removed Clock Cartridge An optional clock cartridge can be installed on the CPU module to store real time calendar clock data for use with advanced instructions to perform time scheduled control Function Description Maintenance Communication Server The user program can be downloaded uploaded or monitored using WindLDR via Ethernet Server Connection Modbus T...

Страница 13: ...uple types K J and T and resistance thermometer Pt100 Pt1000 Ni100 and Ni1000 signals The output channel generates voltage 0 to 10V DC or 10 to 10V DC and current 4 to 20 mA signals AS Interface Master Module One or two AS Interface master modules can be mounted to communicate with a maximum of 124 slaves or 496 inputs and 372 outputs such as actuators and sensors through the AS Interface bus PID ...

Страница 14: ... the Web server CPU module via Internet As the security measures be sure to use a firewall to restrict parts and IP addresses of the network devices that can connect to the Web server CPU module Use WindLDR to configure the Web server CPU module W ĨŽƌ DĂŝŶƚĞŶĂŶĐĞ W ĨŽƌ ƌŽǁƐŝŶŐ ZŽƵƚĞƌ dŽƵĐŚ ĐƌĞĞŶ ĨŽƌ DŽŶŝƚŽƌŝŶŐ ͻ ŽǁŶůŽĂĚŝŶŐ ͻ hƉůŽĂĚŝŶŐ ͻ DŽŶŝƚŽƌŝŶŐ ͻ ĞƚƚŝŶŐƐ ĐŚĂŶŐĞƐ ͻ DŽŶŝƚŽƌŝŶŐ ĞĂĐŚ ƌĞŐŝƐƚĞƌ ͻ tƌŝ...

Страница 15: ...rver and Modbus TCP server The communication protocol for the client connections can be selected from user communication client and Modbus TCP client SNTP Obtain Current Time It is possible to perform calculations using year month day and time information obtained from an SNTP server The current time can be obtained from the specified SNTP server The time obtained from the SNTP server can also be ...

Страница 16: ...downloaded to the Web server CPU module The downloaded pages can be displayed in a web browser on your PC It is possible to show the device values data registers or internal relays on the web page using JavaScript EĞƚǁŽƌŬ DĂŝů ƐĞŶƚ ƚŽ ŵĂŝů ƐĞƌǀĞƌ tĞď ĞƌǀĞƌ Wh DŽĚƵůĞ džƚĞƌŶĂů W WŽƌƚĂďůĞ ƚĞƌŵŝŶĂů DĂŝů ƐĞƌǀĞƌ DĂŝů ƐĞŶƚ ƚŽ ĞdžƚĞƌŶĂů W DĂŝů ƌĞĐĞŝǀĞĚ DĂŝů ƐĞŶƚ ĨƌŽŵ W DĂŝů ƌĞĐĞŝǀĞĚ EĞƚǁŽƌŬ ĞŶĚ dD ƉĂŐĞ ŝŵĂŐ...

Страница 17: ...d can mount an optional RS232C or RS485 communication module for 1 N computer link user communication data link communication and Modbus ASCII RTU communication The HMI base module can also be mounted to install an optional HMI module and a communication adapter Every slim type CPU module has two cartridge connectors to install an optional memory cartridge and a clock cartridge CPU Module Type Num...

Страница 18: ...rograms written in WindLDR can be downloaded to the PLC 11 Ethernet Port For connecting a LAN cable to communicate with PCs PLCs or any other network devices 12 Link LED Orange Turns on when the CPU module is connected to another network device using a LAN cable 13 Network LED Green Flashes when CPU module sends or receives data from the Ethernet port 14 Analog Potentiometer Sets a value of 0 thro...

Страница 19: ... lid to gain access to the cartridge connectors 1 and 2 analog potentiometer and analog voltage input connector 20 Dummy Cartridge Remove the dummy cartridge when using an optional memory cartridge or clock cartridge 21 USB Port Cover Open this cover to use the USB port 22 Expansion Connector Seal Remove the expansion connector seal when connecting an expansion module Phone 800 894 0412 Fax 888 72...

Страница 20: ...on each of three mutually perpendicular axes IEC 61131 2 Shock Resistance 147 m s2 15G 11 ms duration 3 shocks per axis on three mutually perpendicular axes IEC 61131 2 ESD Immunity Contact discharge 4 kV Air discharge 8 kV IEC 61000 4 2 Weight 200g Rated Power Voltage 24V DC Allowable Voltage Range 20 4 to 26 4V DC including ripple Maximum Input Current 700 mA 26 4V DC Maximum Power Consumption N...

Страница 21: ...of the basic volume page A 5 Internal Relay 2 048 Shift Register 256 Timer 256 1 sec 100 ms 10 ms 1 ms Counter 256 adding dual pulse reversible up down selection reversible Data Register 2 000 Expansion Data Register 6 000 Extra Data Register 40 000 Input Filter Without filter 3 to 15 ms selectable in increments of 1 ms Catch Input Interrupt Input Four inputs I2 through I5 can be designated as cat...

Страница 22: ...0 kΩ 0 to 255 8 bits Pulse Output 3 points Maximum frequency 100 kHz Communication Port Communication connector for port 2 Cartridge Connector 2 points for connecting a memory cartridge 32KB 64KB or 128KB and a clock cartridge Mode Output Internal Relay Shift Register Counter Data Register Expansion DR Extra DR Timer Current Value Keep Type Clear Type Run Operating Operating Operating Operating St...

Страница 23: ...ted User programs can be downloaded from the memory cartridge to the CPU module User programs can also be uploaded to the memory cartridge from the CPU module Accuracy 30 sec month typical at 25 C Backup Duration Approx 30 days typical at 25 C after backup battery fully charged Battery Lithium secondary battery Charging Time Approx 10 hours for charging from 0 to 90 of full charge Battery Life App...

Страница 24: ...anent damage may be caused Cable Length 3m 9 84 ft in compliance with electromagnetic immunity Connector on Mother Board MC1 5 16 G 3 81BK Phoenix Contact Connector Insertion Removal Durability 100 times minimum Input Operating Range The input operating range of the Type 1 IEC 61131 2 input module is shown below Input Internal Circuit I O Usage Limits When using the FC5A D12K1E S1E at an ambient t...

Страница 25: ...on Inrush Current 1A maximum Leakage Current 0 1 mA maximum Clamping Voltage 39V 1V Maximum Lamp Load 8W Inductive Load L R 10 ms 28 8V DC 1 Hz External Current Draw Sink output 100 mA maximum 24V DC power voltage at the V terminal Source output 100 mA maximum 24V DC power voltage at the V terminal Isolation Between output terminal and internal circuit Photocoupler isolated Between output terminal...

Страница 26: ...ransistor Source High speed Output Type CPU Module Applicable Terminal Blocks FC5A PMTS16EP supplied with the CPU module Outputs Q0 to Q3 are transistor source outputs COM and COM terminals are not interconnected COM terminals are interconnected Connect a fuse appropriate for the load For wiring precautions see Input Wiring and Output Wiring on page 3 11 2 wire Sensor Load Fuse Terminal No 1 2 3 4...

Страница 27: ...FC9Y B1278 2 11 2 MODULE SPECIFICATIONS Dimensions CPU Modules Slim Type Web Server FC5A D12K1E FC5A D12S1E NN XIFO UIF DMBNQ JT QVMMFE PVU All dimensions in mm Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 28: ...2 MODULE SPECIFICATIONS 2 12 WEB SERVER CPU MODULE USER S MANUAL FC9Y B1278 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 29: ...damage or malfunction Do not touch the connector pins with hand otherwise electrostatic discharge may damage the internal elements Keep the Web server CPU module wiring away from motor lines Caution The Web server CPU module must be installed correctly for optimum performance The Web server CPU module is designed for installation in a cabinet Do not install the Web server CPU module outside a cabi...

Страница 30: ...latches Assemble Web server CPU modules together before mounting the modules onto a DIN rail Attempt to assemble modules on a DIN rail may cause damage to the modules Turn off the power to the Web server CPU module before assembling the modules Failure to turn power off may cause electrical shocks Caution Unlatch Button 1 If the modules are mounted on a DIN rail first remove the modules from the D...

Страница 31: ... the latch clicks 3 Remove the communication connector cover from the slim type CPU module See Removing the Communication Connector Cover on page 3 10 4 Place the HMI base module and CPU module side by side With the communication connectors aligned correctly and the blue unlatch button in the down position press the HMI base module and CPU module together until the latches click to attach the modu...

Страница 32: ...ntil the tip of the screwdriver bottoms 2 While turning the screwdriver in the direction as shown disengage the latch on the HMI module and pull out the HMI module 3 Remove the HMI module from the HMI base module Turn off the power to the Web server CPU module before installing or removing the HMI module to prevent electrical shocks Do not touch the connector pins with hand otherwise electrostatic...

Страница 33: ...C This section describes the procedure to secure the USB extension cable to the USB port cover using the cable tie Note 1 IDEC USB extension cable for USB Mini B HG9Z XCE21 is recommended Note 2 HellermanTyton cable tie T18R 1000 is recommended 1 Open the USB port cover and insert the USB extension cable into the USB port 2 Pass a cable tie around the USB cable cover and the USB extension cable ta...

Страница 34: ...anel surface Applicable DIN rail IDEC s BAA1000PN10 or BAP1000PN10 1000mm 39 4 long Caution Groove 35 mm wide DIN Rail Clamp 1 Insert a flat screwdriver into the slot in the clamp 2 Pull out the clamps from the modules 3 Turn the Web server CPU modules bottom out 35 mm wide DIN Rail Clamp Web server CPU modules can also be mounted on a panel surface inside a console When mounting a slim type CPU m...

Страница 35: ...nd use M4 screws 6 or 8 mm long to mount the Web server CPU modules on the panel surface FC5A D12K1E FC5A D12S1E All dimensions in mm Removing the Direct Mounting Strip 1 Insert a flat screwdriver under the latch of the direct mounting strip to release the latch A 2 Pull out the direct mounting strip B B A Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 36: ...o IEC 60664 1 When installing the Web server CPU modules in a control panel take the convenience of operation and maintenance and resistance against environments into consideration Always mount the slim type CPU modules horizontally on a vertical plane as shown on the preceding page Any other mounting directions are not allowed SPOU 1BOFM NN NJOJNVN 8JSJOH VDU NN NJOJNVN NN NJOJNVN NN NJOJNVN NN N...

Страница 37: ...k on the left first then remove the longer one on the right 2 When removing the longer terminal block hold the center of the terminal block and pull it out straight 3 Do not pull one end of the longer terminal block otherwise the terminal block may be damaged Turn off the power to the Web server CPU module before installing or removing the terminal blocks to prevent electrical shocks Use the corre...

Страница 38: ...on connector cover will come out as shown at left below Push in this end 3 Then the opposite end 3 will come out If the end does not come out insert a thin screwdriver into the gap and pull out the end 3 Hold the communication connector cover at 3 and pull off the communication connector cover to break bridges B When using a thin screwdriver to pull out the communication connector cover insert the...

Страница 39: ...avy accidents provide a monitor circuit outside the Web server CPU module Connect a fuse to the output module selecting a fuse appropriate for the load Use proper wires for output wiring All in one type CPU modules UL1015 AWG22 or UL1007 AWG18 Slim type CPU and I O modules UL1015 AWG22 When equipment containing the Web server CPU module is intended for use in European countries insert an IEC 60127...

Страница 40: ...is protection circuit can be used when the load impedance is smaller than the RC impedance in an AC load power circuit R Resistor of approximately the same resistance value as the load C 0 1 to 1 µF Inductive Load Output Q COM C R This protection circuit can be used for both AC and DC load power circuits R Resistor of approximately the same resistance value as the load C 0 1 to 1 µF Inductive Load...

Страница 41: ...d external devices which can be a possible noise source Use a thick wire for grounding the Web server CPU module and make the grounding wire as short as possible to make sure that noises from external devices can be conducted to the ground effectively Use a power supply of the rated value Use of a wrong power supply may cause fire hazard The allowable power voltage range for the slim type Web serv...

Страница 42: ...ule and the communication device Take the following measures depending on the operating environment Use a separate power supply for the external device generating noises so that a loop circuit to induce noises can not be formed Disconnect the functional ground terminal of the communication device from the ground line This measure may result in deterioration of EMC characteristics When taking this ...

Страница 43: ...is not included in the calculation of the total current draw by expansion modules Note 2 Values indicated in square brackets represent FC5A SIF2 earlier than version 200 CPU Module Quantity of Expansion RS232C Communication Modules Quantity of Expansion Modules Total Internal Current Draw 5V DC All in one 24 I O Type CPU Module 3 maximum Note 4 maximum 260 mA maximum Slim Type CPU Module 5 maximum...

Страница 44: ... mA Module Type No Quantity Internal Current Draw 5V DC Total Internal Current Draw Expansion RS232C Communication Module FC5A SIF2 Earlier than V200 5 85 mA 425 mA Transistor Output Module FC4A T08S1 1 10 mA 10 mA FC4A T32K3 1 20 mA 20 mA Total 7 455 mA Area Module Type No Quantity InternalCurrent Draw 5V DC TotalInternal Current Draw Expansion Expansion RS232C Communication Module FC5A SIF2 Earl...

Страница 45: ...ng the screw terminals on the Web server CPU modules These ferrules crimping tool and screwdriver are made by Phoenix Contact and are available from Phoenix Contact Type numbers of the ferrules crimping tool and screwdriver listed below are the type numbers of Phoenix Contact When ordering these products from Phoenix Contact specify the Order No and quantity listed below Quantity of Cables Cable S...

Страница 46: ...3 INSTALLATION AND WIRING 3 18 WEB SERVER CPU MODULE USER S MANUAL FC9Y B1278 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 47: ...ring the Web server CPU module operation Start by setting up the maintenance environment Then connect a PC that has WindLDR installed and the Web server CPU module with a USB cable If WindLDR is not installed on the PC install WindLDR Start WindLDR From the Start menu of Windows select Programs Automation Organizer WindLDR WindLDR WindLDR starts and a blank ladder editing screen appears with menus...

Страница 48: ... box Click OK to save the changes Press this button then the same PLC will be selected as default when WindLDR is started next time CPU Module Type No FC5A C10R2 FC5A C10R2C FC5A C10R2D FC5A C16R2 FC5A C16R2C FC5A C16R2D FC5A C24R2 FC5A C24R2C FC5A C24R2D FC5A D16RK1 FC5A D16RS1 FC5A D32K3 FC5A D32S3 FC5A D12K1E FC5A D12S1E PLC Selection Option FC5A C10R2X FC5A C16R2X FC5A C24R2X FC5A D16RX1 FC5A ...

Страница 49: ... Set Up The Communication Settings dialog box appears 2 Select USB and click OK button 3 Select Configuration from the WindLDR menu bar and then click Network Settings 4 The Function Area Settings dialog box appears Enter the IP address subnet mask and default gateway then click OK button 5 Select Online from the WindLDR menu bar and then click Download Note To communicate with the PLC using a USB...

Страница 50: ...m the WindLDR menu bar and then click Batch 9 The Batch Monitor dialog box appears Confirm that the IP address for confirured in step 4 is shown in D8330 to D8333 correctly Ethernet Connection 10 Exit Monitor then select Online from the WindLDR menu bar and then click Set Up 11 The Communication Settings dialog box appears Select the Ethernet and then click on the Browse button Phone 800 894 0412 ...

Страница 51: ...nd click OK button 14 Select Online from the WindLDR menu bar and then click Monitor The IP Address Settings dialog box appears Click OK button 15 Select Online from the WindLDR menu bar and then click Status 16 The PLC Status dialog box appears Confirm that the PLC type and the system program version are properly displayed Settings are now complete Phone 800 894 0412 Fax 888 723 4773 Web www clrw...

Страница 52: ...p button to stop operation then the start control special internal relay M8000 is turned off The PLC operation can also be started and stopped while WindLDR is in the monitor mode Select Online Monitor Monitor and click the Start or Stop button Note Special internal relay M8000 is a keep type internal relay and stores the status when power is turned off M8000 retains its previous status when power...

Страница 53: ...or off when the stop and or reset input is turned on or off When a stop or reset input is turned on during program operation the CPU stops operation the RUN LED is turned off and all outputs are turned off The reset input has priority over the stop input System Statuses at Stop Reset and Restart The system statuses during running stop reset and restart after stopping are listed below Note Expansio...

Страница 54: ...rogramming tool WindLDR and the main unit Sample User Program Create a simple program using WindLDR The sample program performs the following operation When only input I0 is turned on output Q0 is turned on When only input I1 is turned on output Q1 is turned on When both inputs I0 and I1 are turned on output Q2 flashes in 1 sec increments Start WindLDR From the Start menu of Windows select Program...

Страница 55: ...nstruction by inserting a NO contact of input I0 1 From the WindLDR menu bar select Home Basic A Normally Open 2 Move the mouse pointer to the first column of the first line where you want to insert a NO contact and click the left mouse button Note Another method to insert a NO or NC contact is to move the mouse pointer where you want to insert the contact and type A or B The Normally Open dialog ...

Страница 56: ...s programmed in the second column of the first ladder line At the end of the first ladder line program the OUT instruction by inserting a NO coil of output Q0 7 From the WindLDR menu bar select Home Basic OUT Output 8 Move the mouse pointer to the third column of the first ladder line where you want to insert an output coil and click the left mouse button Note Another method to insert an instructi...

Страница 57: ...ogram When the instruction symbols are connected correctly conversion is completed successfully If any error is found the errors are listed on the screen Then make corrections as necessary Now save the file with a new name 11 Select the WindLDR application button at the upper left corner of the WindLDR screen followed by Save and type TEST01 in the File Name field Change the Folder or Drive as nec...

Страница 58: ...r reset the input To quit simulation from the WindLDR menu bar select Online Simulation Download Program You can download the user program from WindLDR running on a PC to the Web server CPU module From the WindLDR menu bar select Online Download The Download Dialog appears then click the OK button The user program is downloaded to the Web server CPU module Note When downloading a user program all ...

Страница 59: ...the USB port may not be detected correctly by WindLDR See Troubleshooting Diagram 19 on page 13 26 Quit WindLDR When you have completed monitoring you can quit WindLDR either directly from the monitor screen or from the editing screen In both cases from the WindLDR application button click Exit WindLDR Rung 1 When both inputs I0 and I1 are on output Q0 is turned off Rung 2 When both inputs I0 and ...

Страница 60: ...4 OPERATION BASICS 4 14 WEB SERVER CPU MODULE USER S MANUAL FC9Y B1278 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 61: ...Self Diagnostic Watchdog timer value can be configured Network Settings Network settings and host name of the Web server CPU module can be configured E mail Settings Basic settings to use E mail function can be configured Network Management SNTP settings and PING timeout can be configured Connection Settings Maintenance communication server user Communication server client and Modbus TCP server cl...

Страница 62: ...an be confirmed under the Program Information in the Download dialog box The user web page size is not included in the program capacity Notes When 127 800 bytes is selected the Online Edit cannot be used When a memory cartridge is installed on the CPU module user programs exceeding the capacity of the memory cartridge cannot be downloaded For details see page 2 31 of FC5A user s manual basic volum...

Страница 63: ...watchdog timer can be reset by inserting a NOP instruction in a ladder program Caution The Watchdog Timer monitors the scan time to confirm that the system is operating normally When changing the watch dog time setting consider the safety of the system and configure the appropriate value Programming WindLDR 1 Select Configuration from the WindLDR menu bar and then click Self Diagnostic The Functio...

Страница 64: ...ule supports DNS client and network devices to which the Web server CPU module communicates can be specified using host names Programming WindLDR 1 Select Configuration from the WindLDR menu bar and then click Network Settings The Function Area settings dialog box appears Host Settings Specify the host name of the Web server CPU module A maximum of 15 ASCII characters can be entered IP Settings Sp...

Страница 65: ...ngs and DNS Settings of the Web server CPU module can be confirmed with the special data registers D8330 through D8349 Special data registers Specifying IP Settings and DNS Settings Using Special Data Registers When use special data registers is configured in the function area settings IP settings and DNS settings can be configured with special data registers D8304 through D8323 Store 0 function a...

Страница 66: ...Switching 0 3 to 255 Follow function area settings 1 Enable DHCP 2 Use special data registers D8304 D8307 IP Address When the address is aaa bbb ccc ddd each value is stored in special data registers as follows D 0 aaa D 1 bbb D 2 ccc and D 3 ddd For example when the IP address is 192 168 1 5 each value is stored as follows D8330 192 D8331 168 D8332 1 and D8333 5 D8308 D8311 Subnet Mask D8312 D831...

Страница 67: ...420 are updated with an internal timer of the Web server CPU module The Web server CPU module obtains the current time from the SNTP server and adjust the current time every 10 minutes Programming WindLDR 1 Select Configuration from the WindLDR menu bar and then click Network Management The Function Area settings dialog box appears 2 Enable Acquire the current date and time from an SNTP server 3 C...

Страница 68: ...he server The values in D8414 to D8420 calendar clock data obtained from SNTP server are automatically transferred to D8008 to D8014 calendar clock data of memory cartridge No modification is required in the ladder programs using the values in D8008 and D8014 Note When the Web server CPU module is powered it does not have time information Once the current time is obtained from the SNTP server the ...

Страница 69: ...s is GMT 9 00 and D8413 is 1 15 minutes are added to the time zone and the adjusted time zone will be GMT 09 15 When D8413 is 2 30 minutes are subtracted from the time zone and the adjusted time zone will be GMT 8 30 Special Data Registers Device Address Description Operation D8413 Time Zone Offset The time zone can be adjusted When 1 is stored in D8413 the clock will advance by 15 minutes When 1 ...

Страница 70: ...enance communication server the Web server CPU module has eight server connections that can be used for maintenance communication user communication or Modbus TCP communication Even when the maintenance communication is configured for additional server connections the user program cannot be downloaded or uploaded through those server connections When Modbus TCP is configured the same port number c...

Страница 71: ...mode of client connections as Unused if those connections are not used For details on each communication function see the corresponding chapter in this manual Special Data Registers Special Internal Relays Communication Mode Information The communication mode information of the server and client connections can be confirmed with special data registers D8278 and D8279 The communication mode informa...

Страница 72: ...ata Registers Device Address Description Details M8212 Maintenance Communication Server 1 Status While a connection is established with a client device the special internal relay will be on When no connection is established it will be off M8213 Maintenance Communication Server 2 Status M8214 Maintenance Communication Server 3 Status Device Address Description Details D8350 D8353 Maintenance Commun...

Страница 73: ...ion 3 Status Device Address Description Details D8394 D8397 Client Connection 1 Connected IP Address IP address is stored in the corresponding special data registers For example when the IP address is aaa bbb ccc ddd each value is stored as follows D8394 aaa D8395 bbb D8396 ccc and D8397 ddd D8398 D8401 Client Connection 2 Connected IP Address D8402 D8405 Client Connection 3 Connected IP Address D...

Страница 74: ...5 FUNCTION AREA SETTINGS 5 14 WEB SERVER CPU MODULE USER S MANUAL FC9Y B1278 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 75: ...t is specified with an IP address the Web server CPU module establishes connection with the remote host that has the specified IP address and the corresponding port number then communication is started When a remote host is specified with a host name the Web server CPU module tries to obtain the IP address from the specified host name using the DNS server If the IP address is successfully obtained...

Страница 76: ...the Remote Host List dialog box If you want to add additional remote hosts repeat the same procedure After adding remote hosts has been completed click on Close button 4 If you want to delete an unused remote host select that remote host in the Remote Host List dialog box and click on Delete button Once a remote host is deleted the remote host numbers of the following remote hosts are changed As a...

Страница 77: ...e communication server a total of 11 network devices supporting the maintenance communication can communicate with the Web server CPU module simultaneously The Web server CPU module also supports the pass through over Modbus RTU When the Web server CPU module is configured as Modbus RTU master it is possible for a remote computer to communicate with FC5A MicroSmart CPU modules configured as Modbus...

Страница 78: ...rt CPU module as a Modbus RTU slave for pass through configure the communication port 2 as Modbus RTU slave Note 2 Note1 Only one server connection can be configured for the pass through over Modbus RTU Note2 Only port 2 can be used for the pass through over Modbus RTU Programming WindLDR Standard Maintenance Communication Server 1 Select Configuration from the WindLDR menu bar and then click Conn...

Страница 79: ...re 0 0 0 0 no access is restricted Server Connections 4 Select Maintenance Communication Server in the Server Connection 1 through 8 pull down list boxes The Maintenance Communication Server dialog box appears The server connection will be configured as the maintenance communication server For detail about each parameter in the dialog box see the descriptions of the standard maintenance communicat...

Страница 80: ...ernet and 1 N under PLC Network Settings and then enter the slave number of the Modbus RTU slave in the Communication Settings dialog box When the pass through over Modbus RTU is enabled in Web server CPU module it is also possible for a computer to communicate with Modbus RTU slaves via the Web server CPU module using USB port Select USB and configure the network settings in the Communication Set...

Страница 81: ...erver and Modbus TCP client When using the Web server CPU module user communication server the client devices can access the Web server CPU module and the communication can be performed between the Web server CPU module and the client devices A maximum of eight server connections of the Web server CPU module can be allocated to user communication If all eight connections are allocated to user comm...

Страница 82: ...User Communication Client Receive Instruction ERXD Cancel Flag The allocation of the user communication receive instruction cancel flags for each client connection is shown in the table below For details about the user communication receive instruction cancel flag see chapter 10 of the FC5A user s manual basic volume Item User Communication Client Remote host number 1 to 255 Establish connection W...

Страница 83: ...e WindLDR menu bar and then click Connection Settings The Function Area settings dialog box appears 2 Select the User Communication Client as the communication mode for the client connection 1 The User Communication Client dialog box appears Configure the remote host number and receive timeout If you want the Web server CPU module to establish the connection when it starts to run select Make Conne...

Страница 84: ...nsmit data or ERXD Receive over Ethernet to receive data as the instruction type Select the client connection from 1 through 3 and designate S1 D1 and D2 Click OK button to close the dialog box 4 Download the user program The settings for the user communication client have been finished The specifications of Ethernet user communication instructions ETXD and ERXD instructions are identical to TXD a...

Страница 85: ...truction cancel flag see chapter 10 of the FC5A user s manual basic volume Item User Communication Server Local host port number 2102 to 2109 Can be changed between 0 and 65535 Number of clients that can simultaneously communicate with the CPU module One client per a user communication server Receive timeout 10 ms to 2550 ms 10 ms increments Device Address Description M8200 User Communication Rece...

Страница 86: ...U module 1 Select Configuration from the WindLDR menu bar and then click Connection Settings The Function Area settings dialog box appears 2 Select the User Communication Server as the communication mode for the server connection 1 The User Communication Server dialog box appears Configure the local host port number and receive timeout If you want to restrict the access using IP address configure ...

Страница 87: ...nsmit data and ERXD Receive over Ethernet to receive data as the instruction type Select the server connection from 1 through 8 and designate S1 D1 and D2 Click OK button to close the dialog box 4 Download the user program The settings for the user communication server have been finished The specifications of Ethernet user communication instructions ETXD and ERXD instructions are identical to TXD ...

Страница 88: ...8 ETHERNET USER COMMUNICATION 8 8 WEB SERVER CPU MODULE USER S MANUAL FC9Y B1278 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 89: ...access Modbus TCP server devices and read or write the data A maximum of three client connections can be configured as Modbus TCP client The Web server CPU module can communicate with multiple Modbus TCP server devices per a client connection For the specification and configuration of Modbus TCP client see Modbus TCP Client For the specification and configuration of Modbus TCP server see Modbus TC...

Страница 90: ...rom the Function Area Settings the error data of each request can be confirmed Modbus TCP Communication Request Table A maximum of 255 requests can be configured in the Modbus TCP Client Request Table Notes 10 bytes of the user program area are needed per each request Request execution devices and error status data registers are allocated in the order of request numbers When deleting a request or ...

Страница 91: ...LDR menu bar select Configuration Connection Settings The Function Area Settings dialog box appears 2 Select Modbus TCP Client as the communication mode for the client connection 1 The Modbus TCP Client Request Table dialog box appears 3 Click on the Communication Settings button The Communication Settings dialog box appears Configure the timeout and click OK button to close the Communication Sett...

Страница 92: ...us 1 to 128 bits 000001 065535 Reads bit device statuses of Q output R shift register or M internal relay 02 Read Input Status 1 to 128 bits 100001 165535 Reads bit device statuses of I input T timer contact or C counter contact 03 Read Holding Registers 1 to 64 words 400001 465535 Reads word device data of D data register T timer preset value or C counter preset value 04 Read Input Registers 1 to...

Страница 93: ...igure that port number in the Remote Host List dialog box Slave No Designate slave numbers 1 through 247 The same slave number can be designated repeatedly for different request numbers which can be 1 through 255 The slave number is usually not referred by Modbus TCP server Configure the slave number if Modbus TCP server requires Slave Address Designate data memory addresses of Modbus servers The ...

Страница 94: ... Relay Master Device Address Data Register Internal Relay M Modbus Address Master Slave Bit 0 Bit 1 Bit 2 Bit 0 Bit 1 Bit 2 Data Register D Modbus Address Master Slave Bit 0 Bit 1 Bit 2 Word 0 Word 1 Word 2 b15 b15 b15 b14 b14 b14 b2 b2 b2 b1 b1 b1 b0 b0 b0 Internal Relay M Modbus Address Master Slave Bit 0 Bit 16 Bit 32 Word 0 Word 1 Word 2 31 47 14 30 46 2 18 34 1 17 33 0 16 32 15 Data Register ...

Страница 95: ...ber of Clients that can Access Simultaneously 2 8 maximum Port Number 502 can be changed between 0 and 65535 Supported Function Code 01 Read Coil Status 02 Read Input Status 03 Read Holding Registers 04 Read Input Registers 05 Force Single Coil 06 Preset Single Register 15 Force Multiple oils 16 Preset Multiple Registers Modbus Device Name Modbus Address Map Decimal 1 Communication Frame Address M...

Страница 96: ...ttings dialog box appears 2 Select Modbus TCP Server as the communication mode for the server connection 1 The Modbus TCP Server dialog box appears 3 Configure the parameters and click on OK button 4 Download the user program to the CPU module Now programming for the Modbus TCP server is complete The specification and setting of each parameter are the same with Modbus slave communication For detai...

Страница 97: ...d When confirmation is not required designate 0 as a transaction ID Protocol ID Designate 0 to identify Modbus TCP protocol Message Length Designate the length of the following message in bytes Unit ID The unit ID is Modbus TCP slave address 1 through 247 to identify the unit The Modbus TCP server of the Web server CPU module ignores the unit ID Function Code Designate a function code such as 01 r...

Страница 98: ...9 MODBUS TCP COMMUNICATION 9 10 WEB SERVER CPU MODULE USER S MANUAL FC9Y B1278 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 99: ...relays cannot be used Devices in EMAIL Instruction S1 Source 1 Specify the e mail number A constant or data register can be specified D1 Destination 1 Specify an internal relay or output as the completion output bit When the Web server CPU module receives a reply from the sending e mail server the completion output bit is turned on The completion output bit is also turned on when there is no reply...

Страница 100: ...ays the e mails is not functioning normally 2 The e mail recipient filters the in coming e mails by specifying the e mail address or e mail domain Status Code Decimal Operation Transition State Description 16 Preparing transmission From turning on the start input for an EMAIL instruction until the e mail is sent out to the sending e mail server 32 Waiting for response From sending the e mail to th...

Страница 101: ...r is usually 25 When the SMTP authentication is enabled the port number 587 is usually used Sender E mail Address Specify the e mail address that is included in the sender field of the e mails to be sent from the Web server CPU module A maximum of 40 ASCII characters can be entered Sender Name Specify the name that is included in the sender field of the e mails to be sent from the Web server CPU m...

Страница 102: ...cify when e mail subject and body consist of western European characters Unicode UTF 8 Specify when using Unicode characters In general any characters can be used using Unicode Depending on sending e mail servers that relay the e mails or the mailer used by the recipients the e mails sent out from the Web server CPU module may not reach the recipients or may not be viewed correctly in the mailer W...

Страница 103: ...le click on the E mail Address Book in the Project Window The E mail Address Book dialog box appears 2 Click on New E mail Address or select an existing E mail address and then click Edit button The E mail Address dialog box appears E mail Address Specify the e mail address to register in the E mail Address Book dialog box A maximum of 40 ASCII characters can be entered Comment The comment for the...

Страница 104: ...on the button The selected e mail address is moved to the list box on the right and listed to the bottom of the e mails The e mail addresses for the e mail address group are shown on the list box on the right The e mail addresses are listed in the order that they were added to the e mail address group In order to remove an e mail address from the e mail address group select the e mail address to r...

Страница 105: ...mbedded data register values and then the entire text is encoded Size of encoded text must be within the maximum size of texts When only single byte ASCII characters are used approximately 200 characters can be entered for e mail subject and 1 400 characters for e mail body When multi byte characters are used approximately 100 characters can be entered for e mail subject and 700 characters for e m...

Страница 106: ...ned 31 bits value Float F The 2 word value stored in the two consecutive data registers starting with the specified data register is converted to a floating point value according to IEEE754 format Digits can be specified between 1 and 7 When word W or double D is selected the conversion type can be specified For example when a data register value is 4660 1234h the data register value is converted ...

Страница 107: ...instruction the remote host list of the Web server CPU module should be configured For details about the remote host list see Remote Host List on page 6 1 Valid Devices 1 Special internal relays cannot be used Devices in PING Instructions S1 Source 1 Specify the remote host number A constant or data register can be specified D1 Destination 1 Specify an internal relay or output as the completion ou...

Страница 108: ...nstruction is suspected Programming WindLDR 1 Select Configuration from the WindLDR menu bar and then click Network Management The Function Area settings dialog box appears 2 Enter the PING timeout The valid timeout range is between 1 and 30 seconds The default timeout is 1 second Status Code Decimal Operation Transition State Description 16 Preparing transmission From turning on the start input f...

Страница 109: ...your web page using system library parts such as numerical input bar graph or trend graph without special knowledge of JavaScript The Web server is protected with basic authentication Access from people who do not have user name and password can be prevented Folder Structure The tree structure of the web server functions in the Web server CPU module is shown below The imported files or folders in ...

Страница 110: ...rary The monitoring interval can be specified in ms Trend monitor interval ns Specify the interval for reading device data used in the trend monitor The trend monitor interval is the product of this value and the monitoring interval Options Redirect target Specify the redirect target when the system top page of the Web server CPU module is accessed When you want to be redirected to the system web ...

Страница 111: ...m device_write cgi CGI for writing device data used by JavaScript Data Type The following data types can be specified in batch monitor custom monitor or user web pages when the system library parts are used Note BIN B is used in the custom monitor when internal relay is monitored 0000 is OFF and 0001 is ON Data Type Data Size Valid Range HEX W Hexadecimal 1 word 0000 to FFFF HEX D Hexadecimal 2 wo...

Страница 112: ... of the Web server CPU module can be confirmed Operating Status Run Stop scan time and error code can be confirmed By clicking on the button in the run stop status the Web server CPU module can be started or stopped Clock Information Calendar and clock data of the clock cartridge and calendar and clock data obtained from SNTP server are shown Network Settings The network settings of the Web server...

Страница 113: ...mbers are 0 to 7800 8000 to 8300 and 10000 to 49800 If an invalid value is entered the value is corrected automatically 2 Select the monitor type to display the data registers in the desired format Data register values are shown in the format specified by the monitor type See the data type for the available data types 3 Click on a cell in which data register value is shown A dialog box to write a ...

Страница 114: ... device number in decimal such as D2058 or m0112 2 Select the monitor type to display the corresponding device in the desired format Data registers or internal relays values are shown in the format specified by the monitor type See the data type for the available data types 3 Click on a cell in Value column in which data register value is shown A dialog box to write a data is shown The entered val...

Страница 115: ...e tree structure or files can be modified Right click on the User Web Page in the Project Window and select Export The Browse For Folder dialog box appears Select the folder to export then all files and folders stored in the user web page are exported to the specified folder Adding removing web pages Each file can also be added or deleted in the Project Window Right click on the User Web Page in t...

Страница 116: ...n A new folder is created under the User Web Page If you want to rename the folder right click on the folder and select Rename Enter the name and click OK to rename the folder 5 Right click on the folder created with step 4 and select Import Files 6 Select page2 html in the Open dialog box and click Open button 7 The user web page is shown as below Phone 800 894 0412 Fax 888 723 4773 Web www clrwt...

Страница 117: ...t to remove all user web pages right click on the User Web Page in the Project Window and select Delete All Click OK button to confirm All imported files and folders will be removed Use UTF8 as encoding type of htm or html files imported to the user web page Create backup files on the PC before importing those files to WindLDR The behavior of web browser varies with type and version of each web br...

Страница 118: ... Type Specify the device type D data register can be specified Device Number Specify the device number in decimal Driver Number Reserved for the system Specify 0 Network Number Reserved for the system Specify 0 Data Type Specify the data type to show the device data in desired format Bit Button Form Button When data register monitoring is enabled and the following string is included in an html pag...

Страница 119: ...e bit state is on with the relative path Example When using Numerical Display if D2058 is 49910 C2F6h and D2059 is 59768 E978h those data register values are shown as follows on web browser W D 2058 0 0 HEX W C2F6 W D 2058 0 0 HEX D C2F6E978 W D 2058 0 0 DEC W 49910 W D 2058 0 0 DEC I 15626 W D 2058 0 0 DEC L 1024005768 W D 2058 0 0 DEC F 123 456 If the formats of strings are invalid those strings...

Страница 120: ...of the division The default color is 000000 barvgutter Specify the offset to the bar graph from the top boundary of the division in pixel The default value is 30 barwidth Specify the width of the bars in pixel The default value is 20 gutter Specify the space between the bars in pixel The default value is 20 type Specify the shape of the tips of the bars The shape can be selected from square round ...

Страница 121: ... 2040 driver 0 net_no 0 format DEC D width 300 height 300 line_col 000000 barvgutter 30 barwidth 20 gutter 20 type square scalewidth 5 bars min_val 0 max_val 100 label dev A back_col FFFFFF front_col 0000FF scale_on true scale_lbl_on true min_val 0 max_val 100 label dev B back_col FFFFFF front_col FF0000 scale_on false scale_lbl_on false div Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com E...

Страница 122: ...lor of the division The default color is 000000 barhgutter Specify the offset to the bar graph from the left boundary of the division in pixel The default value is 30 barwidth Specify the width of the bars in pixel The default value is 20 gutter Specify the space between the bars in pixel The default value is 20 type Specify the shape of the tips of the bars The shape can be selected from square r...

Страница 123: ...s 2040 driver 0 net_no 0 format DEC D width 300 height 300 line_col 000000 barhgutter 30 barwidth 20 gutter 20 type square scalewidth 5 bars min_val 0 max_val 100 label dev A back_col FFFFFF front_col 0000FF scale_on true scale_lbl_on true min_val 0 max_val 100 label dev B back_col FFFFFF front_col FF0000 scale_on false scale_lbl_on false div Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com ...

Страница 124: ...awing the trend graph in pixel The default value is 30 g_width Specify the width of the trend graph in pixel The default value is 200 g_height Specify the height of the trend graph in pixel The default value is 100 g_line_col Specify the color of the border of the trend graph The default color is the same with the line_col g_line_width Specify the width of the border of the trend graph in pixel Th...

Страница 125: ...not be inserted Non value parameters should be quoted with double quotes Insert comma between all parameters Do not insert a comma after the last parameter If the format of parameters is invalid graph is not drawn The look of the graphs may differ with each web browser The update time may be extended according to the monitoring interval or the number of plots of the trend graph marker_col Specify ...

Страница 126: ...rted between device values Note When D2058 is 49910 C2F6h and D2059 is 59768 E978h request and returned values are as follows var raw_data idec device_read D 2058 2 0 0 raw_data will be C2F6_E978 Writing Device Data var raw_data Idec device_write device address length driver net_no data device Specify the device type D data register can be specified address Specify the device number length Specify...

Страница 127: ...ogram syntax errors are found during compilation on WindLDR When an incorrect program is downloaded to the Web server CPU module user program syntax errors are still checked Errors are also checked at starting and during operation of the Web server CPU module When an error occurs the error is reported by turning on the ERR LED on the Web server CPU module and an error message can be viewed on Wind...

Страница 128: ...ror exists Error is displayed in the error status box 3 On the right of the Error Status in the PLC Status dialog box click the Details button The PLC Error Status screen appears Clearing Error Codes from WindLDR After removing the cause of the error clear the error code using the following procedure 1 From the WindLDR menu bar select Online Monitor Monitor The monitor mode is enabled 2 From the W...

Страница 129: ...he error code is stored in special data register D8005 If 1 is stored in each bit of D8005 the corresponding error is occurring Error Cleared Clear Button D8005 General Error Code D8006 User Program Execution Error Code Power failure Watchdog timer error Data link connection error User program ROM sum check error Timer counter preset value sum check error User program RAM sum check error Keep data...

Страница 130: ... WindLDR of the basic volume page 11 8 To correct this error make corrections in the Function Area Settings and download the user program to each station or connect the cable correctly Turn power off and on again for the slave station Then take one of the following actions Turn power off and on for the master station Initialize data link communication for the master station using WindLDR on a comp...

Страница 131: ... Program Writing Error This error indicates a failure of writing into the Web server CPU module ROM when downloading a user program The error code is cleared when writing into the EEPROM is completed successfully If this error occurs frequently the Web server CPU module has to be replaced When a memory cartridge is installed on the CPU module writing into the memory cartridge is checked 0200h CPU ...

Страница 132: ...XTY CVYTX have the same S1 but have different data types 13 CVXTY CVYTX has S2 exceeding the value specified in XYFS 14 Label in LJMP LCAL or DJNZ is not found 15 TXD RXD is executed while the RS232C port 1 or 2 is not set to user communication mode 16 PID instruction execution error see S1 2 Operating Status of the advanced volume page 14 4 17 Preset value is written to a timer counter whose pres...

Страница 133: ...r S1 or S2 data exceeds 32767 34 NDSRC has invalid data for source device S3 35 In the SUM instruction the execution result exceeds the valid range for the selected data type or S2 data is 0 User Program Execution Error Code D8006 Error Details Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 134: ...terrupt catch input cannot receive short pulses Diagram 9 Frequency measurement does not work Diagram 10 The calendar clock does not operate correctly Diagram 11 Analog I O module does not work END refresh type Diagram 12 Data link communication is impossible Diagram 13 Data is not transmitted at all in the user communication mode Diagram 14 Data is not transmitted correctly in the user communicat...

Страница 135: ... Is the power voltage correct The PWR LED does not go on Is the PWR LED on Supply power Is the PWR LED on Supply the rated voltage All in one type 100 240V AC 24V DC Slim type 24V DC Call IDEC for assistance END NO NO NO NO YES YES YES YES Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 136: ...8000 on Turn on M8000 using WindLDR Is the RUN LED on Turn off the stop and reset inputs Is the RUN LED on Note The Start button is found in the WindLDR menu bar Note To monitor M8000 from the WindLDR menu bar select Online Monitor Monitor then Online Custom New Custom Monitor Enter M8000 in the Device box in the Custom Monitor dialog box Note To turn on M8000 enter 1 in the Current Value box in t...

Страница 137: ...eration by clearing error codes from WindLDR See Clearing Error Codes from WindLDR on page 13 2 The ERR LED is on Clear error codes using WindLDR See Note below See General Error Codes on page 13 3 Identify the error code and correct the error Is the ERR LED turned off NO YES END Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 138: ...ut device addresses correct Correct the external device wiring Is the input LED on Correct the program Correct the input wiring Supply the rated voltage to the input terminal Input voltage range All in one CPU input mixed I O modules 20 4 to 28 8V DC Slim type CPU modules 20 4 to 26 4V DC AC input module 85 to 132V AC NO NO NO YES YES NO YES YES NO END Call IDEC for assistance YES Phone 800 894 04...

Страница 139: ...odule Output does not operate normally Check the output allocation numbers Monitor the output using WindLDR Click the Start button in WindLDR on a computer connected to the Web server CPU module Note The Start button is found in the WindLDR menu bar Is the RUN LED on Is the expansion interface module used See I O Refreshing by Expansion Interface Module Appendix of the basic volume END Call IDEC f...

Страница 140: ...Program enabled Communication between WindLDR on a computer and the Web server CPU module is not possible Is the PWR LED on Is the computer link cable connected correctly Connect the cable completely When only program download is not possible Only program download is not possible Is the Communication Settings correct See Troubleshooting Diagram 1 The PWR LED does not go on NO NO NO NO YES YES YES ...

Страница 141: ...nction Area Settings Monitor the start control special internal relay M8000 using WindLDR on a computer Turn off the start control special internal relay M8000 using WindLDR on a computer Cannot stop or reset operation Note To monitor M8000 from the WindLDR menu bar select Online Monitor Monitor then Online Custom New Custom Monitor Enter M8000 in the Device box in the Custom Monitor dialog box No...

Страница 142: ...etails see Watchdog Timer Setting on page 5 3 Watchdog timer error occurs and the CPU does not run Call IDEC for assistance YES NO Are the input ON OFF voltage levels correct The interrupt catch input cannot receive short pulses Make sure of correct input voltage ON voltage 15V DC minimum OFF voltage 5V DC maximum YES NO Call IDEC for assistance END Phone 800 894 0412 Fax 888 723 4773 Web www clrw...

Страница 143: ...re connected to correct terminals See Frequency Measurement of the basic volume page 5 30 Frequency measurement does not work Select Single phase High speed Counter in the Groups 1 through 4 Is the gate input on Is the reset input off Make sure that the gate input is on and the reset input is off Call IDEC for assistance YES YES YES NO NO NO Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com E...

Страница 144: ...ring Error Codes from WindLDR on page 13 2 The clock data is broken Set the calendar clock using WindLDR See Setting Calendar Clock Using WindLDR of the advanced volume page 9 6 Adjust the clock cartridge accuracy See Adjusting Clock Cartridge Accuracy of the advanced volume page 9 8 Monitor the PLC status using WindLDR Is the clock cartridge installed correctly Install the clock cartridge correct...

Страница 145: ...stopped and restarted Stop and restart the CPU to configure the analog I O settings Supply the rated power voltage to the analog I O module See Wiring Diagram of the basic volume page 9 19 Does the status DR store status code 3 invalid parameter Are data registers duplicated Change data register numbers to eliminate duplicated data registers NO YES NO YES YES NO YES NO Call IDEC for assistance Pho...

Страница 146: ... 12 or turn on M8007 during operation using WindLDR Are error codes cleared to 0 at all stations Clear the error codes at all stations using WindLDR See Clearing Error Codes from WindLDR on page 13 2 Data link communication is impossible M8006 Data link communication prohibit flag M8007 Data link communication initialize flag Is data link selected for port 2 correctly Is the PWR LED on See Trouble...

Страница 147: ...Is the PWR LED on Is the communication cable connected correctly Make sure of correct wiring Is the input to the TXD instruction on Turn on the input to the TXD instruction Data is not transmitted at all in the user communication mode Call IDEC for assistance YES YES YES NO NO NO Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 148: ...LDR See Programming WindLDR of the basic volume page 10 5 Make sure that the busy signal at the remote terminal does not exceed 5 sec Is the data register designated as transmit status used repeatedly Correct the program to replace the duplicate data register with a different data register Is duration of the busy signal at the remote terminal less than 5 sec Make sure that the transmit data design...

Страница 149: ...n Is the PWR LED on Is the communication cable connected correctly Make sure of correct wiring Is the input to the RXD instruction on Turn on the input to the RXD instruction Data is not received at all in the user communication mode Call IDEC for assistance YES NO NO YES YES NO Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 150: ...e format of incoming data Is an end delimiter specified in the RXD instruction Did you check the end delimiter of incoming data Is the receive timeout value set correctly using WindLDR Is one input used to start multiple RXD instructions Make sure that the receive format of the RXD instruction matches that of the incoming data Correct the program to make sure that inputs to more than 5 RXD instruc...

Страница 151: ...ttings are correct Turn on the request execution internal relay Is it clear which request has an error See the request table to find which request has an error and what error occurred See Communication Error Data of Each Request of the basic volume page 12 4 01h function error 02h access destination error 03h device quantity error 1 bit write data error 16h timeout error Make sure of the valid sla...

Страница 152: ... communication settings Open the Communication Settings dialog box in WindLDR Select USB and uncheck the Use HGxG Pass Through check box Restart the PC and try again Confirmation procedure 1 Right click on My Computer and select Properties 2 In the System Properties dialog box select the Hardware tab and click Device Manager 3 All available communication ports are displayed under Ports COM LPT Is ...

Страница 153: ... for details about the error code Note Is the EMAIL instruction error code 0 E mail is not sent NO YES YES NO The request to send e mail is not submitted to the SMTP server Confirm the error code detail Note The following two points should also be checked 1 Is the LAN cable properly connected 2 Are the network settings correct The request for sending e mail is received by the SMTP server and the e...

Страница 154: ...13 TROUBLESHOOTING 13 28 WEB SERVER CPU MODULE USER S MANUAL FC9Y B1278 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 155: ...e Data The Web server CPU module returns the following reply after receiving above request Content type text javascript json charset utf 8 STATUS 0 DEVICE D ADDRESS 080A LENGTH 0002 DRIVER 00 NET_NO 00 DATA C2F6_E978 STATUS 0 indicates normal reply Any other values indicate an error DEVICE ADDRESS LENGTH DRIVER and NET_NO The parameters in the request are stored DATA Values of the specified device...

Страница 156: ...dule returns the following reply after receiving above request Content type text javascript json charset utf 8 STATUS 0 DEVICE D ADDRESS 080A LENGTH 0002 DRIVER 00 NET_NO 00 STATUS 0 indicates normal reply Any other values indicate an error DEVICE ADDRESS LENGTH DRIVER and NET_NO The parameters in the request are stored system device_write cgi CGI file name device Specify the device type of the ta...

Страница 157: ...USB port on the FC5A D12X1E with power supplied and the PC running 2 After the message Found New Hardware appears on the PC the driver installation wizard appears Select No not this time and click Next 3 Select Install the software automatically Recommended and click Next Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 158: ...iver Signing Options in Driver Signing in the System Properties dialog box If the installation is aborted this option should be changed to Warn After changing the option to Warn reconnect the Web server CPU module and retry the installation procedure from the step 1 5 Installation is now complete Click Finish Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 159: ...Install this driver software anyway 5 Installation is complete once the message Your devices are ready to use appears in the bottom right corner of the desktop Installing on Windows 7 32 bit or 64 bit Edition 1 Connect a USB cable to the USB port on the FC5A D12X1E with power supplied and the PC running 2 The following message appears in the bottom right corner of the desktop 3 Installation is com...

Страница 160: ...APPENDIX A 6 WEB SERVER CPU MODULE USER S MANUAL FC9Y B1278 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 161: ...for output 3 12 CPU module 2 1 error 13 5 specifications 2 5 2 6 terminal arrangement 2 10 crimping tool 3 17 custom monitor 12 6 D data link connection error 13 4 DC input specifications CPU module 2 8 decimal symbol e mail 10 4 details button 13 2 DHCP server 5 5 dimensions 2 11 DIN rail 3 6 direct mounting on panel surface 3 6 strip 3 6 disassembling modules 3 2 DNS server 5 6 download program ...

Страница 162: ...6 1 9 1 client specifications 9 1 communication error 9 2 communication format 9 9 error status 9 5 function code 9 4 remote host number 9 5 request execution device 9 5 server 9 7 module HMI base 3 3 specifications 2 1 monitor operation 4 13 monitoring WindLDR 13 2 mounting hole layout for direct mounting 3 7 on DIN rail 3 6 on panel surface 3 6 strip 3 6 N network settings 5 4 normal operating c...

Страница 163: ...029 13 2 statuses at stop reset and restart 2 6 4 7 system library JavaScript functions 12 18 system setup example 1 4 system web page 12 3 language 12 2 T terminal arrangement CPU module 2 10 block removing 3 9 connection 3 17 text encoding e mail 10 4 tightening torque 3 17 time zone offset 5 9 SNTP 5 7 5 9 timeout ping 11 2 timer counter preset value sum check error 13 5 transistor output speci...

Страница 164: ...R CPU MODULE USER S MANUAL FC9Y B1278 INDEX quit 4 13 start 4 1 4 8 wiring 3 1 diagrams I O 2 10 input 3 11 output 3 11 power supply 3 13 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Отзывы: