![IDEC HR6S-AF Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/idec/hr6s-af/hr6s-af_original-instructions-manual_3664627080.webp)
Diagnostics
80
HR9Z-B2192 8/2020
0010001100
Cross circuit detected at
input terminal S12.
Verify correct wiring.
Verify that the sensor/device providing the input signal is
suitable for cross circuit detection by means of
dynamization. If it is not, use an application function
without dynamization or a sensor/device suitable for
dynamization.
Verify correct operation of sensor/device providing the
input signal.
Perform a power cycle.
E
0010001111
Cross circuit detected at
input terminal S22.
Verify correct wiring.
Verify that the sensor/device providing the input signal is
suitable for cross circuit detection by means of
dynamization. If it is not, use an application function
without dynamization or a sensor/device suitable for
dynamization.
Verify correct operation of sensor/device providing the
input signal.
Perform a power cycle.
E
0010110000
Cross circuit detected at
start input.
Verify correct wiring.
Verify that the device providing the input signal is suitable
for cross circuit detection by means of dynamization. If it
is not, use a start function without dynamization or a
device suitable for dynamization.
Verify correct operation of device providing the input
signal.
Perform a power cycle.
E
0010110011
Synchronization alert.
One of the synchronized
safety-related inputs is
still deactivated, but the
synchronization time has
already elapsed.
Restore the original condition of the states of the inputs
and retry.
Verify correct operation of sensors/devices providing the
input signals.
A
0010100111
Synchronization alert.
Both synchronized
safety-related inputs
have been activated, but
not within the
synchronization time.
Restore the original condition of the states of the inputs
and retry.
Verify correct operation of sensors/devices providing the
input signals.
A
0010110111
Safety-related inputs
deactivated, safety-
related outputs
deactivated.
-
S
Bit sequence
Description
Correctives
Type
(1)
(1) Type of message: E = Error detected, A = Alert, S = Status information
Содержание HR6S-AF
Страница 1: ...http www idec com HR6S AF Safety Module Original instructions HR9Z B2192...
Страница 8: ...8 HR9Z B2192 8 2020...
Страница 14: ...14 HR9Z B2192 8 2020...
Страница 20: ...Introduction 20 HR9Z B2192 8 2020...
Страница 46: ...Engineering 46 HR9Z B2192 8 2020...
Страница 56: ...Installation 56 HR9Z B2192 8 2020...
Страница 82: ...Diagnostics 82 HR9Z B2192 8 2020...
Страница 88: ...Accessories Service Maintenance and Disposal 88 HR9Z B2192 8 2020...