Technical Data
HR9Z-B2192 8/2020
23
Environmental Conditions For Operation
The device complies with class 3K5 and special class 3Z11 as per IEC 60721-3-3 (climatic
conditions):
The device complies with class 3M4 as per IEC 60721-3-3 (mechanical conditions):
The devices complies with the following vibration and shock values as per IEC 60947-1:
Characteristic
Value
Maximum installation altitude above mean sea level
2000 m (6562 ft)
Installation required in control cabinet/enclosure with
degree of protection
IP54
Characteristic
Value
Ambient temperature
-25 ... 55 °C (-13 ... 131 °F), no icing
Rate of change of temperature
0.5 °C/min (0.9 °F/min)
Ambient humidity
5 ... 95 % relative humidity, no condensation
Characteristic
Value
Vibration, sinusoidal, displacement amplitude
2 ... 9 Hz
3 mm
Vibration, sinusoidal, acceleration amplitude
9 ... 200 Hz
10 m/s
2
Shock, shock pulse shape: half-sine, peak
acceleration
100 m/s
2
Characteristic
Value
Vibration, sinusoidal, displacement amplitude
2 ... 13 Hz
1 mm
Vibration, sinusoidal, acceleration amplitude
13.2 ... 100 Hz
7 m/s
2
Shock, shock pulse shape: half-sine, peak
acceleration
150 m/s
2
Содержание HR6S-AF
Страница 1: ...http www idec com HR6S AF Safety Module Original instructions HR9Z B2192...
Страница 8: ...8 HR9Z B2192 8 2020...
Страница 14: ...14 HR9Z B2192 8 2020...
Страница 20: ...Introduction 20 HR9Z B2192 8 2020...
Страница 46: ...Engineering 46 HR9Z B2192 8 2020...
Страница 56: ...Installation 56 HR9Z B2192 8 2020...
Страница 82: ...Diagnostics 82 HR9Z B2192 8 2020...
Страница 88: ...Accessories Service Maintenance and Disposal 88 HR9Z B2192 8 2020...