7-pin plugs for connecting
to the control panel and
burner connectors
If the electrical characteristics of the burner exceed the following
values:
-
start current> 16 A or
-
P > 450 W (or 1/2 cont. hp. motor), or
-
I > 2 A cos
ϕ
= 0, 7
The burner controls must be relayed.
CONTROL PANEL
Connecting a safety thermostat alarm transfer system
The isolated pin standing by on the safety thermostat is used to
connect an alarm transfer system (thermostat with reversing
contact).
If the safety thermostat trips, a 230 V signal is active at that terminal.
Proceed as follows to connect the alarm transfer system :
-
Open the control panel (3 screws on the rear) to access the
rear of the safety thermostat.
-
Connect the alarm transfer system to the thermostat pin using
a 6.35 mm Faston clip. The other end of the cable is
connected to an indicator or sound alarm.