FAULT FINDING

28

LOGIC HIU 

Installation & Servicing  / Users

60  FAULT FINDING

Fault

Indications

Possible Cause of Fault

Operations to be Performed

The water is 

not heating

DHW LED on

primary circuit isolating valve closed

open the isolating valve

modulating valve actuator connector disconnected

reconnect actuator connector

modulating valve actuator disconnected from 

valve body

reconnect actuator

modulating valve actuator faulty

call qualified personnel to have it replaced

DHW temperature probe cable inverted with 

heating probe

restore correct connection

presence of air in the system

restore correct connection

electronic controller not working

call qualified personnel to have it replaced

valve obturator blocked in closed position

call qualified personnel to have it replaced

centralised system not working

contact person in charge of system

FAULT LED lit + 

error code  

6 active

DHW temperature probe disconnected

reconnect probe

DHW temperature probe faulty

call qualified personnel to have it replaced

FAULT LED lit + 

error code  

79 active

DHW temperature probe faulty

restore correct switch setting

DHW LED off

DHW priority flow meter disconnected

reconnect flow meter

DHW priority flow meter faulty

call qualified personnel to have it replaced

all LEDs are off

electricity power supply switched off

switch on electricity supply

protection fuse burnt out

call qualified personnel to have it replaced

The water is 

hot but does 

not reach 

the desired 

temperature

DHW LED on

domestic water cycle temperature set point too 

low

increase set point

HIU strainer clogged

call qualified personnel to have it serviced

exchanger partly clogged

call qualified personnel to have it serviced

modulating valve actuator faulty

call qualified personnel to have it replaced

valve obturator blocked in intermediate position

call qualified personnel to have it replaced

modulating valve actuator connector disconnected

reconnect actuator connector

DHW temperature probe cable inverted with 

heating probe

restore correct connection

excessive demand for DHW

decrease demand

electronic controller not working

call qualified personnel to have it replaced

centralised system temperature insufficient

contact person in charge of system

primary circuit flow rate insufficient

contact person in charge of system

The hot water 

temperature 

reached is  

too high

DHW LED on

domestic water cycle temperature set point too 

high

decrease set point

DHW temperature probe cable inverted with 

heating probe

restore correct connection

modulating valve actuator faulty

call qualified personnel to have it replaced

valve obturator blocked in intermediate or open 

position

call qualified personnel to have it replaced

electronic controller not working

call qualified personnel to have it replaced

Hot water 

flow rate is 

insufficient

DHW LED on

HIU strainer clogged

call qualified personnel to have it replaced

possible domestic water system shut-off valves 

partly open

open the valves

centralised domestic circuit cold water flow rate 

insufficient

call qualified personnel to have it serviced

There is no hot 

water flow

DHW LED off

possible domestic water system shut-off valves 

closed

open the valves

no cold water in centralised domestic circuit

call qualified personnel to have it serviced

HIU strainer completely clogged

call qualified personnel to have it serviced

heat exchanger completely blocked

call qualified personnel to have it serviced

Содержание LOGIC HIU Direct MT

Страница 1: ...sured conform to the safety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature fo...

Страница 2: ...control devices e g economisers etc are directly connected to these appliances unless covered by these Installation and Servicing Instructions or as otherwise recommended by Ideal Boilers in writing...

Страница 3: ...IU to remove any particles rust incrustations lime scale welding slag and any other contaminants The water circuits must be clean and free from debris Make sure that all connection fittings are watert...

Страница 4: ...modulated CH This can be converted to under floor heating including inbuilt safety thermostat capability LOGIC HIU INDIRECT 50 Indirect wall mounted HIU with a 50kW instantaneous priority DHW and 15...

Страница 5: ...perature 42 to 60 C Domestic hot water 10 bar DHW circuit max flow rate 18 l m 0 3 l s Min flow rate to activate domestic flow sensor 2 7 l m 0 3 Max Differential pressure on domestic water modulating...

Страница 6: ...meter when fitted 4 Primary filter and heat meter probe pocket 5 Heating circuit control valve 7 Modulating primary control valve DHW 8 Plate heat exchanger DHW 9 DHW temperature sensor 10 DHW flow sw...

Страница 7: ...Servicing Users FLOW PATH Heating Primary Circuit 5 SCHEMATIC LOGIC HIU INDIRECT 75 LOGIC HIU INDIRECT 50 6 PRIMARY FLOW CHARACTERISTICS 7 PRIMARY FLOW CHARACTERISTICS FLOW PATH DHW Primary Circuit RE...

Страница 8: ...1 0 3 0 4 0 5 0 6 3 2 1 RES ET ON DH W C H FAULT 1 2 5 5 C 65 C 5 5 C 85 C 75 C 85 C 80 C 75 C 70 C 65 C 60 C HEATING SECONDRY FLOW CHARACTERISTICS LOGIC HIU INDIRECT 50 75 DHW SECONDRY FLOW CHARACTER...

Страница 9: ...ance water check valve incorporated into inlet connection The filling loop and ball valves are used to fill and pressurise the secondary heating system the filling loop must be disconnected after pres...

Страница 10: ...igure the control for different units within the range It is important that they are not changed from those shown below If they carehanged outside of these requirements it will cause the HIU to operat...

Страница 11: ...valve actuator X X 5 Thermal safety relief valve 5a Pressure switch X X 6 Thermal safety thermostat X X 7 Heating flow temperature probe X X 8 Heating valve actuator X X 9 Earth X X 10 Pump X X 11 El...

Страница 12: ...ashes On Off when in operation NOTE when in standby the display will alternate every 5 second displaying the CH and the DHW temperatures 21 DISPLAYED ERROR CODES When an error occurs on these units th...

Страница 13: ...ode 76 LOW temperature Should the operating temperature drop below the required 25 C as a result of a faulty safety valve the flashing fault LED on the electronic controller will appear and Error code...

Страница 14: ...to modulate the heating flow circuit for greater efficiency and to compensate for changes in the external environment LOGIC HIU DIRECT HT Direct wall mounted HIU with a 50kW indirect instantaneous pri...

Страница 15: ...8 l m 0 3 l s Min flow rate to activate domestic flow sensor 2 7 l m 0 3 Max Differential pressure on domestic water modulating valve p 0 9 bar Min Differential pressure on domestic water modulating v...

Страница 16: ...y filter and heat meter probe pocket 5 Heating circuit on off valve 7 Modulating primary control valve DHW 8 Plate heat exchanger DHW 9 DHW temperature sensor 10 DHW flow switch 11 Electronic control...

Страница 17: ...Kv 2 20 m3 h H m c a H m c a p bar 3 3 5 G m3 h 0 6 0 4 0 3 0 2 0 1 0 2 5 2 1 5 0 5 0 5 1 6 4 3 2 1 5 7 0 7 0 8 8 20 20 5 13 14 19 17 LOGIC HIU Installation Servicing Users 28 UPM3 AUTO L HEATING FLO...

Страница 18: ...TS 31 DOMESTIC HOT WATER OUTPUT PRIMARY FLOW PATH Primary Flow Rate l h HEATING FLOW HEATING RETURN Domestic Hot Water Flow Rate 48 C l h 18 LOGIC HIU Installation Servicing Users Kv 2 25 m3 h Flowrat...

Страница 19: ...n screw driver slot horizontal to bypass Turn Vertical to connect the HIU to the primary circuit 33 PRIMARY BALL VALVE SET Flow Control Valves with sample points Inc sealing washer to appliance CONTEN...

Страница 20: ...hazardous operational conditions To modify the factory settings and enable the HIU to support LOW temperature systems 25 to 45 C proceed as follows Electronic Control Dip Switch Settings Factory Sett...

Страница 21: ...l safety relief valve 5a Pressure switch 6 Pressure gauge CH 7 Heating flow temperature probe X X 8 Heating valve actuator X X 9 Earth X X 10 Pump X 11 Electric supply 230 V ac X X 12 Room thermostat...

Страница 22: ...when setting and displaying Flashes On Off when in operation Actual Domestic Hot Water DHW Set Point Temperature Value display permanently when in use or been set Radiator Symbol On when setting and d...

Страница 23: ...ber relating to this fault will be displayed Central Heating outlet temperature probe fault If the heating probe fails the heating will cease immediately The domestic water generation will not be affe...

Страница 24: ...charge pipework in accordance to the local by laws Electrical 1 Electric supply line 230 V ac 50 Hz 2 Time clock thermostat line potential free 3 Centralised bus line for heat meter data transmission...

Страница 25: ...Check for leaks 12 After the primary feed system has been correctly purged Check to ensure to ensure the pressure is not greater than the maximum pressure specified for these units and the system doe...

Страница 26: ...uit To clean these strainers carry out the following maintenance procedure Isolate electrics and primary valves Drain primary legs Unscrew the cap B Remove the st rainer mesh flush thoroughly with cle...

Страница 27: ...d remove the cartridge H Remove any impurities present or change the cartridge if necessary and check flow turbine and saeling washer Screw in the cartridge Reposition the flow sensor and connection W...

Страница 28: ...iced exchanger partly clogged call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced valve obturator blocked in intermediate positio...