IDEAL LOGIC HIU Direct MT Скачать руководство пользователя страница 24

INDIRECT & DIRECT HIU UNITS 

INSTALLATION

24

LOGIC HIU 

Installation & Servicing  / Users

46  LOCATION OF HIU

The HIU must be installed on a flat and vertical wall, capable 

of adequately supporting the weight of the boiler and any 

ancillary equipment supplied in kit form by 

Ideal Boilers

The 

HIU must not be fitted outside.

The Logic HIUs are designed for installation in a sheltered 

domestic environment (or similar), therefore cannot be 

installed or used outdoors, i.e. in areas directly exposed 

to atmospheric agents. Outdoor installation may cause 

malfunctioning and hazards. 

If the device is enclosed inside or between cabinets, sufficient 

space must be provided for routine maintenance procedures. 

It is recommended that electrical devices are NOT placed 

underneath the HIU, as they may be damaged in the event 

of discharge from the safety valve, if it is not connected to 

a discharge tundish or in the event of leaks occurring at the 

hydraulic fittings.

The device must not be exposed to water drops or humidity, 

direct sunlight, the elements, heat sources or high intensity 

electromagnetic fields.

In the event of a malfunction, fault or incorrect operation, the 

device should be deactivated; contact a qualified technician 

for assistance and Isolated from electrical and connection 

feeds to the unit. 

Note for all models:

 If a non-return valve is fitted into the 

domestic hot water (DHW cold water inlet), provison MUST be 

made to accommodate the expansion of the DHW conatined 

within the HIU. 

Preparation

After establishing the position where the HIU will be installed, 

perform the following operations:
•  Mark the holes required for securing the HIU to the wall.

•  Mark the position of the water pipe connections.
Check the measurements again before installing pipework and 

electrical cables.

Fix the HIU to the wall.

N.B.: the wall anchors (not supplied) can only guarantee 

effective support if inserted correctly (in accordance with good 

technical practice) into walls built using solid or semi-solid 

bricks. If working with walls built using perforated bricks or 

blocks, mobile dividing panels or any masonry walls other than 

those indicated, a preliminary static test must be carried out 

on the support system.

Hydraulic connections

1 Connection to the pipework from the centralised boiler plant

2 Connect to heating circuit

3 Domestic water circuit connection

4 Connect safety relief valve to discharge pipework in 

accordance to the local by laws

Electrical

1 Electric supply line 230 V (ac) - 50 Hz.

2 Time clock/thermostat line (potential-free)

3 Centralised bus line for heat meter data transmission  

(if required)

4 Centralised electric supply line for heat meter (if required)

The whole system should be thoroughly flushed to remove any 

debris that may be in the supply pipework to the HIU and to 

the domestic hot water and heating pipework in the apartment 

before connecting to the HIU.

47  ISOLATION VALVES

These units are supplied with all the necessary isolation valves 

required for the unit. We recommend that all connections 

are fitted with isolation valves to allow any maintenance 

work to be carried out safely and effectively. We would also 

recommend that the primary system is fitted with the optional 

flushing bypass valves in addition to the primary isolation valve 

supplied, immediately upstream of the HIU, to allow the primary 

system to be flushed prior to the first operation of the unit. 

48  ELECTRICAL CONNECTIONS

Make sure that the electrical system can withstand the 

maximum power consumption of the appliance, with particular 

emphasis on the cross-section of the cables.

If in doubt, contact a qualified technician to thoroughly check 

the electrical system.
Electrical safety of the appliance is only achieved when 

it is correctly connected to an effective earthing system, 

constructed as specified in current safety regulations. This is a 

compulsory safety requirement.

Connection to the main supply

The device is supplied with an electric supply cable - plug not supplied.
The device should be electrically connected to a 230 V (ac) 

single phase + earth mains supply using the three-wire cable 

marked with the label as specified below, observing the LIVE 

(L) - NEUTRAL (N) polarities and the earth connection.
This line must be connected to a circuit breaker device.

Room thermostat

Electrical supply: 

230 V (ac)±10% - 50 Hz

49  CONNECTION TO THE TIMELOCK/THERMOSTAT.

The Logic HIU includes a connection, suitable for a time clock/

thermostat, allowing the tenant to control individual apartment 

heating requirements
The connection to this device 

(potential-free contact) 

must be made with the two-wire cable marked with the label 

as specified below. Should it be necessary to extend this 

cable, use one with the same cross-section (max 1 mm²) and 

maximum length 30m. 

Electrical supply: 230 V(ac) ±10% - 50 Hz 

Label on HIU Thermostat connection

VOLT FREE ROOM

THERMOSTAT 

CONNECTION

WARNING

DO NOT CONNECT EXTERNAL VOLTAGE 

SUPPLY TO THESE TERMINALS

IMPORTANT: THIS 

CONNECTION 

MUST BE VOLT FREE

Содержание LOGIC HIU Direct MT

Страница 1: ...sured conform to the safety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature fo...

Страница 2: ...control devices e g economisers etc are directly connected to these appliances unless covered by these Installation and Servicing Instructions or as otherwise recommended by Ideal Boilers in writing...

Страница 3: ...IU to remove any particles rust incrustations lime scale welding slag and any other contaminants The water circuits must be clean and free from debris Make sure that all connection fittings are watert...

Страница 4: ...modulated CH This can be converted to under floor heating including inbuilt safety thermostat capability LOGIC HIU INDIRECT 50 Indirect wall mounted HIU with a 50kW instantaneous priority DHW and 15...

Страница 5: ...perature 42 to 60 C Domestic hot water 10 bar DHW circuit max flow rate 18 l m 0 3 l s Min flow rate to activate domestic flow sensor 2 7 l m 0 3 Max Differential pressure on domestic water modulating...

Страница 6: ...meter when fitted 4 Primary filter and heat meter probe pocket 5 Heating circuit control valve 7 Modulating primary control valve DHW 8 Plate heat exchanger DHW 9 DHW temperature sensor 10 DHW flow sw...

Страница 7: ...Servicing Users FLOW PATH Heating Primary Circuit 5 SCHEMATIC LOGIC HIU INDIRECT 75 LOGIC HIU INDIRECT 50 6 PRIMARY FLOW CHARACTERISTICS 7 PRIMARY FLOW CHARACTERISTICS FLOW PATH DHW Primary Circuit RE...

Страница 8: ...1 0 3 0 4 0 5 0 6 3 2 1 RES ET ON DH W C H FAULT 1 2 5 5 C 65 C 5 5 C 85 C 75 C 85 C 80 C 75 C 70 C 65 C 60 C HEATING SECONDRY FLOW CHARACTERISTICS LOGIC HIU INDIRECT 50 75 DHW SECONDRY FLOW CHARACTER...

Страница 9: ...ance water check valve incorporated into inlet connection The filling loop and ball valves are used to fill and pressurise the secondary heating system the filling loop must be disconnected after pres...

Страница 10: ...igure the control for different units within the range It is important that they are not changed from those shown below If they carehanged outside of these requirements it will cause the HIU to operat...

Страница 11: ...valve actuator X X 5 Thermal safety relief valve 5a Pressure switch X X 6 Thermal safety thermostat X X 7 Heating flow temperature probe X X 8 Heating valve actuator X X 9 Earth X X 10 Pump X X 11 El...

Страница 12: ...ashes On Off when in operation NOTE when in standby the display will alternate every 5 second displaying the CH and the DHW temperatures 21 DISPLAYED ERROR CODES When an error occurs on these units th...

Страница 13: ...ode 76 LOW temperature Should the operating temperature drop below the required 25 C as a result of a faulty safety valve the flashing fault LED on the electronic controller will appear and Error code...

Страница 14: ...to modulate the heating flow circuit for greater efficiency and to compensate for changes in the external environment LOGIC HIU DIRECT HT Direct wall mounted HIU with a 50kW indirect instantaneous pri...

Страница 15: ...8 l m 0 3 l s Min flow rate to activate domestic flow sensor 2 7 l m 0 3 Max Differential pressure on domestic water modulating valve p 0 9 bar Min Differential pressure on domestic water modulating v...

Страница 16: ...y filter and heat meter probe pocket 5 Heating circuit on off valve 7 Modulating primary control valve DHW 8 Plate heat exchanger DHW 9 DHW temperature sensor 10 DHW flow switch 11 Electronic control...

Страница 17: ...Kv 2 20 m3 h H m c a H m c a p bar 3 3 5 G m3 h 0 6 0 4 0 3 0 2 0 1 0 2 5 2 1 5 0 5 0 5 1 6 4 3 2 1 5 7 0 7 0 8 8 20 20 5 13 14 19 17 LOGIC HIU Installation Servicing Users 28 UPM3 AUTO L HEATING FLO...

Страница 18: ...TS 31 DOMESTIC HOT WATER OUTPUT PRIMARY FLOW PATH Primary Flow Rate l h HEATING FLOW HEATING RETURN Domestic Hot Water Flow Rate 48 C l h 18 LOGIC HIU Installation Servicing Users Kv 2 25 m3 h Flowrat...

Страница 19: ...n screw driver slot horizontal to bypass Turn Vertical to connect the HIU to the primary circuit 33 PRIMARY BALL VALVE SET Flow Control Valves with sample points Inc sealing washer to appliance CONTEN...

Страница 20: ...hazardous operational conditions To modify the factory settings and enable the HIU to support LOW temperature systems 25 to 45 C proceed as follows Electronic Control Dip Switch Settings Factory Sett...

Страница 21: ...l safety relief valve 5a Pressure switch 6 Pressure gauge CH 7 Heating flow temperature probe X X 8 Heating valve actuator X X 9 Earth X X 10 Pump X 11 Electric supply 230 V ac X X 12 Room thermostat...

Страница 22: ...when setting and displaying Flashes On Off when in operation Actual Domestic Hot Water DHW Set Point Temperature Value display permanently when in use or been set Radiator Symbol On when setting and d...

Страница 23: ...ber relating to this fault will be displayed Central Heating outlet temperature probe fault If the heating probe fails the heating will cease immediately The domestic water generation will not be affe...

Страница 24: ...charge pipework in accordance to the local by laws Electrical 1 Electric supply line 230 V ac 50 Hz 2 Time clock thermostat line potential free 3 Centralised bus line for heat meter data transmission...

Страница 25: ...Check for leaks 12 After the primary feed system has been correctly purged Check to ensure to ensure the pressure is not greater than the maximum pressure specified for these units and the system doe...

Страница 26: ...uit To clean these strainers carry out the following maintenance procedure Isolate electrics and primary valves Drain primary legs Unscrew the cap B Remove the st rainer mesh flush thoroughly with cle...

Страница 27: ...d remove the cartridge H Remove any impurities present or change the cartridge if necessary and check flow turbine and saeling washer Screw in the cartridge Reposition the flow sensor and connection W...

Страница 28: ...iced exchanger partly clogged call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced valve obturator blocked in intermediate positio...

Страница 29: ...ystem temperature insufficient contact person in charge of system electronic controller not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person i...

Страница 30: ...NOTES 30 LOGIC HIU Installation Servicing Users...