istor system store -
Installation and Servicing
FAULT FINDING
F
AUL
T FINDING F
AUL
T FINDING F
AUL
T FINDING F
AUL
T FINDING F
AUL
T FINDING
102 H.....2..... (RETURN TEMPERATURE SENSOR)
103 H.....3..... (DHW TEMPERATURE SENSOR)
YES
Is there continuity between the PCB
and the thermistor ?
Check resistance. The sensors can be checked by
measuring their resistance, using a suitable multimeter
connected across the sensors' terminal pins
At 25
o
C
expect
9,700-10,300
Ohms
At 60
o
C
expect
2,400-2,600
Ohms
At 85
o
C
expect
1,000-1,100
Ohms
Remove the boiler return
thermistor from the CH
return pipe.
Are the thermistor values correct ?
Replace the thermistor
NO
YES
Replace PCB
Check and replace wiring
as necessary
NO
YES
Is there continuity between the PCB and
the thermistor ?
Check resistance. The sensors can be checked by
measuring their resistance, using a suitable multimeter
connected across the sensors' terminal pins
At 25
o
C
expect
9,700-10,300
Ohms
At 60
o
C
expect
2,400-2,600
Ohms
At 85
o
C
expect
1,000-1,100
Ohms
Remove the boiler DHW
thermistor from the DHW
cylinder and disconnect
thermistor wires.
Are the thermistor values correct ?
Replace the thermistor
NO
YES
Replace PCB
Check and replace wiring
as necessary
NO
Содержание istor HE260
Страница 2: ...2 istor system store Installation and Servicing...
Страница 73: ...73 istor system store Installation and Servicing...
Страница 74: ......
Страница 76: ...Gas Safe Register ID Number...
Страница 78: ...78 istor system store Installation and Servicing...
Страница 79: ...79 istor system store Installation and Servicing...