
32
istor system store -
Installation and Servicing
INSTALLATION
FLUE OUTLET
rf8394-1
690mm
Fixed
300mm
min
38 FLUE TERMINAL POSITION
rf8393-1
300mm
min
300mm
min
625mm
Fixed
Flat roof - with structure
The terminal should be positioned so that products of
combustion can safely disperse at all times.
Pluming may occur at the termination so, where
possible, terminal positions where this could cause
a nuisance should be avoided.
Minimum dimensions are shown below
Terminal Position
Minimum Dimension
Directly below an opening,
air brick, windows, etc.
300 mm
Below plastic / painted gutters
300 mm
Painted surface
300 mm
Below eaves or balcony
500 mm
Below velux window
2000 mm
Above or side of velux window
600 mm
rf8392
RF9807
A
A
B
A
A = 600mm
B = 2000mm
The flue terminal shall not penetrate the shaded area of the roof
Содержание istor HE260
Страница 2: ...2 istor system store Installation and Servicing...
Страница 73: ...73 istor system store Installation and Servicing...
Страница 74: ......
Страница 76: ...Gas Safe Register ID Number...
Страница 78: ...78 istor system store Installation and Servicing...
Страница 79: ...79 istor system store Installation and Servicing...