21
Fault finding
Cod:
Significato:
24
18
12
6
E1
Intervention of the high limit thermostat(TL)
E2
Insufficient gas pressure
E4
No flame detected during the ignition phase.
E5
Loss of flame signal during boiler operation
E6
Over high water temperature detected by the heating
sensor (SR) (>95°C)
E10
Internal failure
of the local control PCB (BMM)
E11
Flame signal detected before the ignition cycle
E12
Heating sensor failure (SR)
E13
DHW sensor failure (only if the boiler is combined
with an external storage tank)
E14
Failure of the heating return sensor (SRR)
E15
Difference between the global return heating
temperature global sensor and the heating flow
sensor > 30°C
(rp +10)
.
E16
Boiler body temperature very low: Ice forming risk
E20
Flame signal detected after burner OFF
E22
The air pressure switch doen‘t change over within 30 s
from starting of the burner ignition cycle
E23
Air pressure switch contact always closed
E24
Modulating fan speed failure: it doesn‘t reach the
correct speed within 30 s from starting of burner
ignition cycle
E26
Modulating fan speed failure: it doesn‘t stop within
30 s from end of operation
E27
Air pressure switch detects an anomaly during the
burner ignition cycle.
E30
Alteration of the operating parameters caused by
EMC disturbances
E32
Mains supply voltage < 190 Vac
E69
E8: F5 – Flow temperature sensor heating circuit 2
E70
E8: F11 – Flow temperature sensor heating circuit 1
E71
E8: F1 – Lower storage temperature sensor (Buffer)
E72
E8: F3 – Higher storage temperature sensor (Buffer)
E75
E8: F9 – Outer temperature sensor (AF)
E76
E8: F6 – DHW storage temperature sensor (SPF)
E78
E8: F8 – Boiler temperature sensor (KF)
E80
E8: F2 – Room temperature sensor heating circuit 1
E81
E8: EEPROM fault. The invalid value has been
replaced by the standard value
E83
E8: F15 – Room temperature sensor heating circuit 2
E90
E8: BUS addresses 0 and 1. The BUS codes 0 and 1
cannot be used at the same time.
E91
E8: BUS code occupied. The set BUS code is
already used by another appliance
E99
E8: Internal failure
E135
E8: F12 – Lower DHW storage temperature sensor
MF2
E136
E8: F13 – Boiler 2, Manifold 2 MF 3
E137
E8: F14 – Manifold 1, Multifunction 4.
E200
E8: Intervention os safety devices (fans rotating at
maximum speed) / communication error module 1
E201
E8: communication error module 2
E203
E8: communication error module 3
E204
E8: communication error module 4
E205
E8: communication error module 5
E206
E8: communication error module 6
E207
E8: communication error module 7
6.3 - DISPLAY OF ERROR CODES ON HEATING CONTROLLER E8
If a fault or error occurs in the heating system a blinking warning
triangle and the related error code will appear on the E8 display.
Here below are listed the boiler’s error codes, relative meanings
and corrective actions.
For the error codes relative to the heating system please refer
to the paragraph “Fault finding” in the “Users guide” supplied
together with the heating controller E8.5064 V1.