background image

30

SERVICING

isar - 

Installation and Servicing

41

SERVICING SCHEDULE

To ensure the continued safe and efficient operation of the
appliance it is recommended that it is checked at regular
intervals and serviced as necessary.  The frequency of
servicing will depend upon the installation condition and
usage but should be carried out at least annually.
It is the law that any service work must be carried out by a
CORGI registered installer. In IE service work must be carried
out by a competent person.
Note.

Some aluminium oxide build-up on the heat exchanger
fins is usual with this type of condensing boiler.  Though
removal is recommended annually, the heat exchanger
MUST be inspected and cleaned after a MAXIMUM of 2
years operation.

1. Light the boiler and carry out a pre-service check, noting

any operational faults.

2. Check the gas consumption.
3. Connect a suitable gas analyser to the sampling point on

the top of the boiler (refer to Frame 43) or into the flue
terminal if access is possible (optional test).
For correct boiler operation, the CO/CO

2

 content of the flue

gas should not be greater than 0.004 ratio.
If this is the case, and the gas input is at least 90% of the
nominal, then no further action need be taken.  If not,
proceed to Step 5 but see note above.

4. Clean the main burner.
5. Clean the heat exchanger.
6. Check the condition of the combustion chamber

insulation. Any cracked or damaged pieces should be

replaced.

7. Check the main injector for blockage or damage.
8. Wherever possible remove and clean the condensate ‘S’

trap (refer to Frame 47) and check the drain for blockage.

9. Check that the flue terminal is unobstructed and that the

flue system is sealed correctly.

10. Check the DHW filter for blockage. Refer to Frame 25.
The servicing procedures are covered more fully in Frames
42-49 and MUST be carried out in sequence.
Note.

In order to carry out either servicing or replacement of
components the boiler front panel and sealing panel
must be removed. Refer to Frames 42 and 43.

WARNING.

Always turn OFF the gas supply at the gas

service cock, and switch OFF and disconnect the electricity
supply to the appliance before servicing.
IMPORTANT.
11. 
After completing the servicing or exchange of components

always test for gas soundness and carry out functional
checks in 3 and 4 above.

12. When work is complete the sealing panel MUST be

correctly refitted, ensuring that a good seal is made.

Do NOT OPERATE the boiler if the sealing
panel is not fitted.

13. If, for any reason, the condensate ‘S’ trap has been

removed ensure the trap is refilled with water before
reassembling.

14. Complete the service section in the Benchmark log book.

40

HANDING OVER

7. If a programmer is fitted draw attention to the Programmer

Users Instructions and hand them to the householder.

8. Loss of system water pressure

Explain that the dial underneath the boiler indicates the
central heating system pressure and that if the normal COLD
pressure of the system is seen to decrease over a period of
time then a water leak is indicated. In this event a registered
local heating installer should be consulted.

WARNING.

Do not fire the boiler if the pressure has reduced to zero from
the original setting.

9. After installation, commissioning and customer hand-over

please complete the 

 appliance log book and

leave this with the customer. For IE it is necessary to
complete a “Declaration of Conformity” to indicate
compliance to I.S. 813:2002

10. IMPORTANT

A comprehensive service should be carried out ANNUALLY.

Stress the importance of regular servicing by a CORGI
registered installer. In IE servicing work must be carried out
by a competent person.

11. As the installer you may wish to undertake the service

contract yourself or alternatively offer to the customer the
benefits of the Ideal Care Scheme, details of which are
outlined in the householder pack supplied with this boiler.

1. Hand the User Instructions to the householder and

explain his/her responsibilities under the relevant
national regulations.

2. Explain and demonstrate the lighting and shutting

down procedures.

3. The operation of the boiler and the use and adjustment

of all system controls should be fully explained to the
householder, to ensure the greatest possible fuel
economy consistent with the household requirements of
both heating and hot water consumption.

Advise the User of the precautions necessary to prevent
damage to the system and to the building, in the event
of the system remaining inoperative during frosty
conditions.

4. Explain the function and the use of the boiler heating

and domestic hot water controls.

5. Explain the function of the boiler fault mode.

Emphasise that if a fault is indicated, the boiler should
be turned off and a CORGI registered local heating
installer consulted. In IE contact a competent person.

6. Explain and demonstrate the function of time and

temperature controls, radiator valves etc., for the
economic use of the system.

After completing the installation and commissioning of the system the
installer should hand over to the householder by the following actions:

SER

VICING

Содержание he24

Страница 1: ......

Страница 2: ...dom IE Ireland Countries of destination PMS Maximum operating pressure of water C13 C33 C53 A room sealed appliance designed for connection via ducts to a horizontal or vertical terminal which admits...

Страница 3: ...a badge 11 SEDBUK No 2 Controls Time and temperature control to heating 24 Time and temperature control to hot water 24 Heating zone valves n a TRV s 8 Auto bypass 8 Boiler interlock 8 For all boilers...

Страница 4: ...t exchanger is of cast aluminium The boiler is suitable for connection to fully pumped sealed water systems ONLY Adequate arrangements for completely draining the system by provision of drain cocks MU...

Страница 5: ...d the normal appliance warranty It could also infringe the Gas Safety Regulations and the above regulations SAFE HANDLING OF SUBSTANCES Care should be taken when handling the boiler insulation panels...

Страница 6: ...copper pipe MUST be fitted to both flow and return connections from the boiler before connection to any plastic piping The central heating system should be in accordance with BS 6798 and in addition...

Страница 7: ...ia should be removed See Frame 37 Bottom clearance Bottom clearance after installation can be reduced to 5mm However 100mm must be available for servicing Where the space into which the boiler is goin...

Страница 8: ...equirement of at least 0 9kW 3000Btu h of the boiler heat output should be achieved using a room thermostat whilst other rooms are individually controlled by thermostatic radiator valves A higher prop...

Страница 9: ...es 4 When connecting to suitable showers ensure that a The cold inlet to the boiler is fitted with an approved anti vacuum or syphon non return valve b Hot and cold water supplies to the shower are of...

Страница 10: ...icially softened water however is not permitted Caradon Ideal Limited recommend the use of Fernox Qantomat GE Betz Sentinel Combiguard and Calmag CalPhos I scale reducing devices which must be used in...

Страница 11: ...11 INSTALLATION isar Installation and Servicing 8 BOILER ASSEMBLY Exploded View INSTALLATION...

Страница 12: ...with this requirement may result in damage to the fascia Hardware Pack Fittings 50mm x No 14 wood screws 4 off Wall plugs TP2B 4 off Water treatment warning label Turret clamp M5 x 10 pozi Hex screw S...

Страница 13: ...laps to gain access to Wall mounting plate Instructions Hardware pack fittings User control 4 Remove the instructions and read thoroughly before unpacking the product 5 When ready for installation lif...

Страница 14: ...the boiler and out through the condensate drain 2 If the boiler is to be installed with upward piping routed behind the boiler then the optional stand off kit should be used Care must be taken when cu...

Страница 15: ...wall and tape template B into the selected position 4 Mark onto the wall the following a The piping frame screw positions choose one from each group b The position of the flue duct hole see diagram b...

Страница 16: ...ential add 33mm to X the measured wall thickness when marking the flue this will allow for the fitted frame 1 Measure and note wall thickness X Refer to Frame 12 2 Add 90mm 3 1 2 to dimension X and me...

Страница 17: ...ng the clamp provided clamp the flue lengths together 5 Repeat steps 1 4 if a second flue extension is required 6 Measure and mark the flue length required onto the flue measuring from the ring near t...

Страница 18: ...frame To allow pipework to be taken upwards Insert wall plugs Put the screws into the wall plugs and leave 10mm proud Hang the stand off frame onto the screws and tighten up Fasten the piping frame t...

Страница 19: ...isplay unit pack A into the control box Refer to Frame 66 8 Screw the user control into position 22 CONDENSATE DRAIN Refer also to the British Gas document Guidance Notes for the Installation of Domes...

Страница 20: ...ing a cupful of water into the flue outlet A Take care to ensure that the water is only poured into the flue outlet and does not spill into the boiler casing 1 Insert the flue assembly through the pre...

Страница 21: ...he isar range is able to deliver its full output at inlet pressures well below those required by BS 6891 A boiler gas supply pipe length of 20m and not less than 15mm O D can be connected to the boile...

Страница 22: ...ould be protected c Bleed any air from the pump and ensure that it is free to rotate i Remove the vent plug ii Using a screwdriver rotate the shaft several times iii Replace the vent plug Note Some sl...

Страница 23: ...E E BS 7671 Wiring Regulations and any local regulations 1 Route the mains cable into the bottom rear centre of the boiler 2 Wire the permanent live supply into the 5 way remote plug terminals L3 N IM...

Страница 24: ...se the programmer selector switches are set to OFF and all the other controls MUST be left in the running position The frost thermostat should be sited in a cold place but where it can sense heat from...

Страница 25: ...25 INSTALLATION isar Installation and Servicing 33 PICTORIAL WIRING DIAGRAM LEGEND b blue bk black br brown gy grey or orange pk pink r red v violet w white y yellow y g yellow green INSTALLATION...

Страница 26: ...ry out the preliminary electrical system checks i e earth continuity polarity resistance to earth and short circuit using a suitable test meter B Gas Installation 1 The whole of the gas installation i...

Страница 27: ...ugh its ignition sequence until the burner is established LEGEND A Boiler On Off switch B CH thermostat knob D Burner On neon E Reset button F Injector pressure test point G Inlet pressure test point...

Страница 28: ...rom them The display should read flashing then when the burner lights Make the following checks for correct operation in 3 Close all taps except the furthest one from the boiler and check that the boi...

Страница 29: ...and vent the system add inhibitor see Frame 6 clear all air locks and again check for water soundness Affix the water treatment warning label supplied in the hardware pack in a prominent position on...

Страница 30: ...ealing panel is not fitted 13 If for any reason the condensate S trap has been removed ensure the trap is refilled with water before reassembling 14 Complete the service section in the Benchmark log b...

Страница 31: ...2 screws from the underside of the boiler 2 Pull the panel forward at the bottom and lift to disengage it from the top lugs 1 To remove the sealing panel remove the 4 screws 2 Remove the panel 3 To r...

Страница 32: ...THE CONTROL BOX IN THE SERVICING POSITION 1 Remove the 2 screws and withdraw the user control 2 Unplug the low voltage electrical lead from the back of the user control 3 Turn the clamp swing the cont...

Страница 33: ...laced down upon its face as this may cause damage to the ceramic 3 Brush off any deposits that may be on the ceramic with a SOFT brush 4 Inspect the sealing gasket around the burner and combustion cha...

Страница 34: ...and detection electrodes Ensure that they are clean and in good condition replace if necessary 6 Check the condition of the combustion chamber insulation Any cracked or damaged pieces should be replac...

Страница 35: ...Frames 42 43 3 Disconnect the electrical leads from the fan 4 Undo the gas pipe union connection to the injector housing 5 Remove the screw retaining the fan mounting bracket 6 Remove the fan and vent...

Страница 36: ...connection to the injector housing 5 Remove the screw retaining the fan mounting bracket 6 Remove the fan and venturi assembly 7 Remove the 2 injector housing screws 8 Withdraw the injector housing 9...

Страница 37: ...Remove the boiler front and sealing panels Refer to Frames 42 43 3 Unplug the flame detection lead from the electrode 4 Remove the 2 screws holding the flame detection electrode to the combustion cham...

Страница 38: ...n are replaced Reassemble in reverse order 11 Ensure the sensing tube is correctly replaced and not kinked or blocked in any way 12 Check operation of the boiler Refer to Frame 50 60 DIVERTER VALVE AC...

Страница 39: ...part 7 Remove the detection earth probe 8 Damp down the combustion chamber area containing the insulation boards 9 Remove the split pin and washer from the RHS of the combustion chamber 10 Remove the...

Страница 40: ...NT 1 Refer to Frame 50 2 Remove the casing front bottom panel Refer to Frames 42 43 3 Remove the 4 screws securing the support plate and withdraw the plate Note The M4 screws fit the casing and the se...

Страница 41: ...move the control Refer to diagram A 5 Return the control box to the working position and secure with the clamp Unscrew the mounting bracket screws to remove the bracket Refer to diagram B 6 Release th...

Страница 42: ...ion 5 Reassemble in reverse order 6 Check operation of the boiler Refer to Frame 50 66 USER CONTROL REPLACEMENT 67 PRESSURE GAUGE REPLACEMENT 1 Refer to Frame 50 2 Drain the boiler Refer to Frame 70 3...

Страница 43: ...g clip 9 Undo the 2 M5 x 10 flue spring clip retaining bracket screws and remove the bracket 10 Remove the M5 x 10 screw retaining the flue casting 11 Remove the flue casting 12 Unscrew the air vent f...

Страница 44: ...3 Drain the boiler Refer to Frame 70 4 Remove the 4 screws retaining the rear support plate and withdraw the plate Refer to Frame 68 Note The M4 screws fit the casing and the self tapping screws fit t...

Страница 45: ...ove the casing front bottom panel Refer to Frames 42 43 3 Drain the boiler Refer to Frame 70 4 Remove the 4 screws securing the rear support plate and withdraw the plate Refer to Frame 68 Note The M4...

Страница 46: ...NE REPLACEMENT 17 Remove the automatic air vent complete with the adapter Refer to Frame 69 18 Remove the edge clip securing the flue thermistor wiring 19 Remove the blind grommet to gain access to th...

Страница 47: ...me 70 3 Unscrew all the gas and water connection unions on the boiler side of the valves 4 Remove the screw from the turret clamp and remove 5 Remove the turret 6 Lift the complete boiler from the wal...

Страница 48: ...FRAME 79 ALTERNATING L A GO TO FRAME 80 ALTERNATING L 8 GO TO FRAME 81 ALTERNATING H 1 GO TO FRAME 82 ALTERNATING H 2 GO TO FRAME 83 ALTERNATING H 3 GO TO FRAME 84 ALTERNATING H 4 GO TO FRAME 85 ALTER...

Страница 49: ...fault Replace ignition electrode and associated harness as necessary NO Replace gas valve YES NO NO 79 L E or H E PCB ERROR Note Due to the wave form of the rectified voltage the reading will vary dep...

Страница 50: ...m filled with water and all isolation valves open OK NO YES NO Replace overheat thermostat 81 L 8 FAN ERROR Is nominal 330 V DC present across red and blue at the fan connector as reset button is pres...

Страница 51: ...ity between the PCB and the thermistor Remove the boiler DHW thermistor from the plate heat exchanger and disconnect thermistor wires Are the thermistor values correct Replace the thermistor NO NO YES...

Страница 52: ...r damage in the flueways Clean or replace as necessary Replace thermistor NO 87 H n PHASE REVERSAL ERROR Check wiring to the boiler for reversed live and neutral YES NO YES NO 86 H F FLAME DETECTION E...

Страница 53: ...urn 2 170 917 24 E67 502 Overheat thermostat 1 170 918 25 Ignition electrode kit 1 173 528 26 Flame detection electrode kit HE24 30 1 173 529 HE35 1 170 984 32 E67 511 Condensate S trap 1 170 926 35 U...

Страница 54: ...54 SHORT LIST OF PARTS isar Installation and Servicing 88 SHORT LIST...

Страница 55: ...anel with screws 4 Bottom panel with screws 90 CONTROLS ASSEMBLY 33 Controls assy with screws 34 Controls hinge bracket 35 User controls without item 38 36 PCB primary controls 38 User controls housin...

Страница 56: ...ecification without notice The Ideal Boilers Technical Training Centre offers a series of first class training courses for domestic commercial and industrial heating installers engineers and system sp...

Отзывы: