tinuity check. If conti-
nuity LED turns “On,”
the fuse is good. If the
continuity LED does
not turn “On,” the fuse
is defective. (61-086
only)
With power on: Place
tester across the “source” side of one
fuse and the load side of an adjoining
fuse. If no voltage is indicated, the fuse
next to the load side prod is blown. If
voltage is indicated, the fuse next to the
load side prod is OK. Repeat the same
test with the prods on the opposite side
of the same two fuses to check the other
fuse.
On a three phase circuit, repeat the
same test as above. An indication of no
voltage or lower than normal line volt-
age indicates the blown fuse.
• Finding Grounded Side of Line
(neutral)
Hold one test prod to the ground and
touch the other test prod to each of the
line terminals until one is found that
does not give a voltage indication. The
continuity LED should be “On.” This is
the grounded side of the line.
• Testing for “Grounded” Side of
Motor or Appliance
With power to motor or appliance “Off,”
ND 3413-1
61-086
Neon Bulb
Indicator
Left LED
Right LED
Neon Bulb
Left LED
Right LED
Indicator
Continuity
Off
On
Off
No movement.
Open
Circuit
No Voltage
Off
Off
Off
No movement.
6-65 AC
Off
On
On
No movement.
6-90 DC
Off
On if black
On if red
No movement.
prod is
prod is
on negative,
on negative,
off if it is on
off if prod is
positive. reversed.
65-110 AC
On
On
On
Little or no
movement.
90-110 DC
On
On if black
On if red
Little or no
prod is
prod is
movement.
on negative,
on negative
off if it is on
off if prod is
positive. reversed.
110-600 AC
On
On
On
Scale indicates
relative
magnitude.
110-600 DC
On
On if black
On if red
Scale indicates
prod is
prod is
relative voltage.
on negative,
on negative,
off if it is on
off if prod is
positive. reversed.
Tester Operation Table
61-086 only
- 8 -