Vertical and horizontal models
•
High efficiency 85% (gross)
•
Low NOx emissions (class 5)
•
50kW Modules
•
Sequence controlled
•
Compact size
•
Complete package gas/water headers
Model 50/V
100/V 150/V 150/VA 200/V 250/V 250/H 300/V 300/H 350/V 400/V 450/V 450/H 500/V 500/H 550/V 550/H
600V
600H
Modules
1
2
3
3
4
5
5
6
6
7
8
9
9
10
10
11
11
12
12
Output (kW)
50
100
150
150
200
250
250
300
300
350
400
450
450
500
500
550
550
600
600
Height
782
1432
1912
1487
1487
1967
1443
1972
1443
1618
1618
2144
1345
2144
1345
2144
1345
2144
1345
Width
439
701
701
1171
1171
1171
1783
1171
1783
1822
1822
1833
2393
1833
2393
1833
2392
1833
2393
Depth
698
698
698
698
698
698
698
698
698
1350
1350
1350
1350
1350
1350
1350
1350
1350
1350
Flow/Return Connections (DN flange)
40
50
65
65
65
80
80
80
80
100
100
125
125
125
125
125
125
125
125
Gas Inlet (BSP)
RC
3
/
4
RC1
RC1
1
/
4
RC1
1
/
4
RC1
1
/
4
RC1
1
/
2
RC1
1
/
2
RC1
1
/
2
RC1
1
/
2
RC2
RC2
RC2
RC2
RC2
RC2
RC2
RC2
RC2
RC2
Flue Size (mm)
125
175
200
200
250
250
250
300
300
350
350
400
400
400
400
450
450
450
450
Maximum Working Pressure (bar)
6
Water Content (L)
4.5
11.9
20.7
21.7
26.2
37.7
39.7
44.5
44.5
63.3
68.1
97.6
92.6
102.4
97.4
107.2 102.2
112
107
Approx Dry Weight (kg)
82.1
187.7 274.1 296.4
348
461
411.2 511.2 513.7
765
813
985
972
1033
1020
1080
1067
1129
1115
Front (mm)
950
Back (mm)
25
25
25
25
25
25
25
25
25
950
950
950
950
950
950
950
950
950
950
Left (mm)
450
900
900
900
900
900
900
900
900
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
Right (mm) 450
900
900
900
900
900
900
900
900
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
General Data Super Series 4 (50 - 600)
Option Kits
Boiler
Water flow switch for boiler protection in
the event of pump failure
External sequencer control kit
Module blanking off pack
Super Series 4
✓
✓
✓
Boiler
Clearances
Super Series 4
50 - 600kW
14