24
Installation and Servicing
FLUE OUTLET
SECTION 2 - INSTALLATION
100mm
Edge of turret
to outside face of wall plus
44mm = flue length
Centre of turret to edge of turret = 100mm
Turret has a flue insertion of 30mm
The compressed outer wall seal has protruding wall to seal mounting lip - 14mm
From centreline of turret to wall. Rear mount 155mm, side (including clearance) 200mm
NOTES
REAR
Fit
to wall
A
W
ALL
Edge of turret
to outside face of wall plus
44mm = flue length
Flue length measured from outer terminal lip
to end of outer flue
A
+ 44mm
REAR
Fit
to wall
inc. Stand
off Frame
A
W
ALL
Edge of turret
to outside face of wall plus
44mm = flue length
SIDE
Fit
to wall
A
W
ALL
Minimum clearance 5mm
....... DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED, CONT’D
FIGURE 1
Note. Maximum permissible
flue length is measured from
centre line of appliance flue
outlet to outside wall face.
2.14 CUTTING & SETTING THE FLUE LENGTH
SETTING TELESCOPIC FLUE PACKS
1. Measure the required flue length (A+44mm).
2. Measure from the outer terminal lip to end of outer flue. Pull apart flue until
desired length is achieved. ENSURE THE STOP MARK IS NOT VISIBLE,
IF IT IS, THE FLUE IS TOO SHORT AND SHOULD NOT BE USED.
3. Check that both flue seams are at the top and the outlet terminal is upper
most.
4. Drill a 3.5mm hole through one of the 2 outer side holes in the outer flue
Section into the inserted outer flue (as shown). Take care not to pierce the
inner plastic flue. Fit screw provided.
5. Seal the joint on the outer air duct with the tape provided.
6. Fit internal and external wall seals (see installing flue).