TECHNICAL DATA
6.1
MAIN TECHNICAL DATA
Description
KERS 50 heat
recovery
ventilation unit with
remote control
Codice
-
Air flow at maximum speed
mc/h
50
Air exchange
mc/h
25
Heat recovery efficiency
%
Fino a 97%
Noise level at maximum speed (at 1m)
dB(A)
30
Noise level at maximum speed (at 3 m) dB(A)
21
Noise level at minimum speed (at 1m)
dB(A)
20
Noise level at minimum speed (at 3 m)
dB(A)
11
Temperature working range
°C
-20 / + 50
Electrical power consumption
–
max
speed
W
5.2
Electrical Current
–
max speed
A
0,031
On board filters
-
2
Filter class EN 779
G3 (F7 as optional)
Power
V/ph/
Hz
230/1/50
Protection
-
IP 24
Table of flow rates and acoustic performance of Kers
Recuperatore
KERS 50
u.m.
-
Speed III
Air flow in supply/extraction
m3/h
50
Air exchange rate
m3/h
25
Noise level at 1 m
dB(A)
30
Noise level at 3 m
dB(A)
21
Speed II
Air flow in supply/extraction
m3/h
30
Air exchange rate
m3/h
15
Noise level at 1 m
dB(A)
27
Noise level at 3 m
dB(A)
18
Speed I
Air flow in supply/extraction
m3/h
15
Air exchange rate
m3/h
7,5
Noise level at 1 m
dB(A)
20
Noise level at 3 m
dB(A)
11
Acoustic insulation of outdoor noise (fan off)
dB(A)
42