12
Henrad SE FF
- Installation
Safety valve setting
3.0 bar
2.5 bar
2.0 bar
Vessel charge and initial
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
system pressure
bar
bar
bar
bar
bar
bar
bar
bar
Total water content of system
Expansion vessel volume litres
25
litres
2.1
2.7
3.9
2.3
3.3
5.9
2.8
5.0
50
4.2
5.4
7.8
4.7
6.7
11.8
5.6
10.0
75
6.3
8.2
11.7
7.0
10.0
17.7
8.4
15.0
100
8.3
10.9
15.6
9.4
13.4
23.7
11.3
20.0
125
10.4
13.6
19.5
11.7
16.7
29.6
14.1
25.0
150
12.5
16.3
23.4
14.1
20.1
35.5
16.9
30.0
175
14.6
19.1
27.3
16.4
23.4
41.4
19.7
35.0
200
16.7
21.8
31.2
18.8
26.8
47.4
22.6
40.0
225
18.7
24.5
35.1
21.1
30.1
53.3
25.4
45.0
250
20.8
27.2
39.0
23.5
33.5
59.2
28.2
50.0
275
22.9
30.0
42.9
25.8
36.8
65.1
31.0
55.0
300
25.0
32.7
46.8
28.2
40.2
71.1
33.9
60.0
Multiplying factors for
other system volumes
0.0833
0.109
0.156
0.094
0.134
0.237
0.113
0.20
9
WATER TREATMENT
GENERAL
8
SEALED SYSTEM REQUIREMENTS -
continued
The SE FF boiler has an ALUMINIUM alloy heat exchanger
If water treatment is used Caradon Plumbing Limited recommend only the use of
FERNOX-COPAL or SENTINEL X100
water
treatment products, which must be used in accordance with the manufacturers' instructions. For further information contact:-
Sentinel Division
Betz Dearborn Ltd.
Widnes
Cheshire
WA8 8UD
0151 424 5351
Fernox Manufacturing. Co. Ltd,
Tandem House,
Marlowe Way,
Croydon,
Surrey CRO 4XS
Tel 0870 5601 5000
Notes.
1. It is most important that the correct concentration of the
water treatment product is maintained in accordance with
the manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable
additives
MUST be removed by thorough cleansing.
BS. 7593:1992 details the steps necessary to clean a
domestic central heating system.
3. In hard water areas, treatment to prevent lime scale
may be necessary - however, the use of artificially
softened water is
NOT permitted.
4. Under no circumstances should the boiler be fired
before the system has been thoroughly flushed.
IMPORTANT.
The application of any other treatment to this product will
render the guarantee of Caradon Plumbing Limited invalid.