background image

4

 

IDEAL CLASSIC

 - 

User’s

3.   SYSTEM WATER PRESSURE

The system pressure gauge (H - see 

page 3) indicates the central heating 

system pressure. If the pressure is seen 

to fall below the original installation 

pressure of 1-2 bar over a period of 

time and continue to fall then a water 

leak may be indicated. In this event re-

pressurise the system.  If unable to do so or if the pressure 

continues to drop a Gas Safe Registered Engineer or in IE a 

Registered Gas Installer (RGII) should be consulted.  

THE BOILER WILL NOT OPERATE IF THE PRESSURE 

HAS REDUCED TO LESS THAN 0.3 BAR UNDER THIS 

CONDITION.

4.  CONDENSATE DRAIN

This appliance is fitted with a siphonic condensate trap 

system that reduces the risk of the appliance condensate 

from freezing.  However should the condensate pipe to this 

appliance freeze, please follow these instructions:

a.  If you do not feel competent to carry out the defrosting 

instructions below please call your local Gas Safe 

Registered installer for assistance.

b.  If you do feel competent to carry out the following instructions 

please do so with care when handling hot utensils.  Do not 

attempt to thaw pipework above ground level.

If this appliance develops a blockage in its condensate pipe, 

its condensate will build up to a point where it will make a 

gurgling noise prior to locking out an “L2” fault code.  If the 

appliance is restarted it will make a gurgling noise prior to it 

locking out on a failed ignition “L2” code.

To unblock a frozen condensate pipe;

1.  Follow the routing of the plastic pipe from its exit point on 

the appliance, through its route to its termination point.

  Locate the frozen blockage.  It is likely that the pipe is 

frozen at the most exposed point external to the building 

or where there is some obstruction to flow.  This could be 

at the open end of the pipe, at a bend or elbow, or where 

there is a dip in the pipe in which condensate can collect.  

The location of the blockage should be identified as 

closely as possible before taking further action.

2.  Apply a hot water bottle, microwaveable heat pack or a 

warm damp cloth to the frozen blockage area.  Several 

applications may have to be made before it fully defrosts.  

Warm water can also be poured onto the pipe from a 

watering can or similar.  DO NOT use boiling water.

3.  Caution when using warm water as this may freeze and 

cause other localised hazards.

4. 

Once the blockage is removed and the condensate can flow 

freely, reset the appliance. (Refer to “To Light the boiler”)

5.  If the appliance fails to ignite, call your Gas Safe 

Registered engineer.

Preventative solutions

During cold weather, set the central heating temperature knob 

(C) to maximum, (Must return to original setting once cold 

spell is over).
Place the heating on continuous and turn the room 

thermostat down to 15ºC overnight or when unoccupied. 

(Return to normal after cold spell).

EFFICIENT HEATING SYSTEM OPERATION

The boiler is a high efficiency, condensing appliance which will 

automatically adjust its output to match the demand for heat.  

Therefore gas consumption is reduced as the heat demand is 

reduced.

The boiler condenses water from the flue gases when operating 

most efficiently.  To operate your boiler efficiently (using less gas) 

turn the central heating temperature knob (C) to the ‘   ‘ position 

or lower.  In winter periods it may be necessary to turn the knob 

towards the ‘

max

’ position to meet heating requirements.  This will 

depend on the house and radiators used.
Reducing the room thermostat setting by 1ºC can reduce gas 
consumption by up to 10%.

WEATHER COMPENSATION

When the Weather Compensation option is fitted to the system then 

the central heating temperature knob (C) becomes a method of 

controlling room temperature.  Turn the knob clockwise to increase 

room temperature and anti-clockwise to decrease room temperature.  

Once the desired setting has been achieved, leave the knob in this 

position and the system will automatically achieve the desired room 

temperature for all outside weather conditions.

BOILER FROST PROTECTION

The boiler is fitted with frost protection that operates in all modes, 

provided the power supply to the boiler is always turned on.  If 

the water in the boiler falls below 5ºC, the frost protection will 

activate and run the boiler to avoid freezing.  The process does not 

guarantee that all other parts of the system will be protected. 
If a system frost thermostat has been installed, the boiler must be 

set in winter mode, ‘ 

 ’, for the system frost protection to run.

If no system frost protection is provided and frost is likely during a 

short absence from home it is recommended to leave the system 

heating controls or built in programmer (if fitted) switched on and 

run at a reduced temperature setting. For longer periods, the entire 

system should be drained.

BOILER RESET

To reset the boiler, when directed in the listed fault codes 

(see section 9), turn the mode knob (A) to ‘

reset

’ position and 

IMMEDIATELY turn knob back to required setting.  The boiler will 

repeat its ignition sequence.  If the boiler still fails to start consult a 

Gas Safe Registered Engineer or in IE a Registered Gas Installer 

(RGII).

MAINS POWER OFF

To remove all power to the boiler the mains power switch must be 

turned off.

Содержание CLASSIC 24

Страница 1: ...nd performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for speci cation and maintenanc...

Страница 2: ...lectrical installation It is essential that the instructions in this booklet are strictly followed for safe and economical operation of the boiler ELECTRICITY SUPPLY This appliance must be earthed Sup...

Страница 3: ...he external controls to OFF The domestic hot water preheat will operate if preheat is enabled shown by indicator light F Boiler Off Set the mode knob A to off The boiler mains power supply must be lef...

Страница 4: ...o ignite call your Gas Safe Registered engineer Preventative solutions During cold weather set the central heating temperature knob C to maximum Must return to original setting once cold spell is over...

Страница 5: ...t once a year by a Gas Safe Registered Engineer or in IE a Registered Gas Installer RGII 6 MECHANICAL 24 HOUR TIMER 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 13 1 4 1 5 1 6 1 7 1 8 19 2 0 2 1 2 2 23 24 ON PERIOD...

Страница 6: ...ovide central heating Check the time settings on the timer are as you require and adjust if necessary Check the timer is in an ON position and the room thermostat is turned up NO HOT WATER OR CENTRAL...

Страница 7: ...for hot water but the appliance has reached the desired temperature set on the boiler The boiler is operating in central heating mode The boiler is operating in pre heat mode The boiler is operating i...

Страница 8: ...on at the meter and or pre payment meter has credit If the boiler fails to operate then please contact Ideal Boilers if under warranty or alternatively a Gas Safe Registered Engineer if outside of th...

Отзывы: