background image

28

 British Gas RD1

 

Installation & Servicing

SERVICING

British Gas Services recommend that appliances are
regularly serviced at 12 month intervals.  However, where an
appliance is being constantly monitored, as is the case with
an RD technology boiler, the interval can be extended to 24
months without detriment to performance or reliability.  It is the
law that any service work must be carried out by a registered
CORGI installer.

a. Light the boiler and carry out a pre-service check, noting

any operational faults. Operate the boiler for at least 20
minutes. Check the gas consumption.

b. Connect a suitable gas analyser to the sampling point on

the top RHS of the back panel. For correct boiler operation
the CO/CO

content of the flue gas should not be greater

than 0.004 ratio. If this is the case and the gas input is at
least 90% of the nominal, then no further action need be
taken. If not, proceed to paragraph c.

c. Clean the main burner. Refer to Frame 48.

d. Clean the heat exchanger. Refer to Frame 47.

e. Clean the main and pilot injectors. Refer to Frame 48.

f.

Remove any debris from inside the base of the casing.

4. Unplug the hot surface igniter lead from printed circuit

board and withdraw it from the control box.

5. Remove the 4 screws retaining the air box/pilot assembly

to the vertical manifold and carefully remove the assembly.

1. Remove the screw retaining the front burner support strap

to the combustion chamber. Remove the M5 pozi situated
at the LH bottom rear of the burner and pull the burner
downwards to disengage the retention tab. Remove the
burner to a safe place for inspection and cleaning.

2. Remove the fixing screws and swing the control box down

into the servicing position. Refer to Frame 53.

3. Remove the hot surface igniter securing screw and

disengage from the combustion chamber.

1. If the  Sealed System Unit is fitted lift off the casing.

2. Open the controls support door and release the 2 captive screws at the

bottom of the casing.  Swing the bottom of the boiler casing out until the
controls support casing has cleared the controls, then unhook the casing
top from the pack panel. Retain the casing in a safe place. Where the
removal of the casing is impaired by a pelmet, the instruction in Frame 2
should be followed.

3. Isolate the gas supply at the service cock fitted to the boiler.

45 BOILER CASING REMOVAL

44 SCHEDULE

46 BURNER, IGNITER AND AIR BOX REMOVAL

g. Check that the flue terminal is unobstructed and that

the flue system is sealed correctly.

h. If the appliance has been installed in a compartment,

check that the ventilation areas are clear.

The servicing procedures are covered more fully in
Frames 45 to 50 and must be carried out in sequence.

WARNING.
Disconnect the electrical supply and turn off gas supply.

IMPORTANT. After completing the servicing or exchange of
components always test for gas soundness and carry out
functional checks as appropriate.

When work is complete the casing MUST be correctly
refitted, ensuring that a good seal is made.

The boiler must NOT be operated if the casing is not
fitted.

Note.

 In order to carry out either servicing or replacement

of components, the boiler casing must  be removed. Refer
to Frame 45 .

SER

VICING

Содержание British Gas 330 RD1

Страница 1: ...INSTALLATION M A N U A L British Scottish Gas RD1 the wall hung boiler Wall hung gas fired fanned flue boiler Installers guide to central heating boilers SERVICING 330 3100 RD1...

Страница 2: ...Complete range There are 7 models in the range All models include a Downward Routing Pipe Kit and an overheat thermostat Full system suitability Most models are suitable for connection to pumped open...

Страница 3: ...45 1 5 Electrical supply 230 V 50 Hz Boiler power consumption 150W Fuse rating External 3A Internal F2A to BS 4265 Water content litre gal 2 7 0 6 3 65 0 8 4 65 1 0 4 65 1 0 Dry Weight kg lb 40 9 90...

Страница 4: ...this case are concentric The fan is down stream of the combustion chamber I2H An appliance designed for use on 2nd Family gas Group H only B G Certified P I No 87 BL 27 Destination Countries GB Natura...

Страница 5: ...t water boilers of rated input not exceeding 60 kW BS 5449 Forced circulation hot water systems BS 5546 Installation of gas hot water supplies for domestic purposes 2nd Family Gases BS 7593 Treatment...

Страница 6: ...the space in which the boiler is to be installed must be at least wide enough to accommodate the tool c If using the Complete Sealed System Unit then refer to the instructions packed with the unit fo...

Страница 7: ...g Installation pipes MUST be fitted in accordance with BS 6891 Pipework from the meter to the boiler MUST be of an adequate size 3100 models should be piped in 22mm minimum The final 1 metre may be ru...

Страница 8: ...sing mains electricity should be so situated that it cannot be touched by a person using the bath or shower See Frame 31 for details the cupboard compartment at both high and low levels The air vents...

Страница 9: ...a domestic circulator capable of providing an 11 C 20 F temperature differential e g Grundfos UPS 15 50 or equivalent The vertical distance between the pump and feed expansion cistern MUST comply with...

Страница 10: ...st be connected at a point close to the inlet side of the pump the connecting pipe being not less than 15mm 1 2 nominal size and not incorporating valves of any sort b The vessel capacity must be adeq...

Страница 11: ...valve and a stop valve with an automatic air vent connected between them the stop valve being located between the system and the automatic air vent The stop valve may remain open during normal operati...

Страница 12: ...ravity horizontal pipes should be ABOVE ceiling level and as SHORT as possible A MINIMUM inclination of 25mm per 3m run 1 per 10 is required to avoid air locks If these conditions cannot be met pumped...

Страница 13: ...ted below Wall mounting template Wall mounting plate Side outlet terminal mounting plate Flue extension tube Boiler sealing ring Flue elbow Downward routing pipe kit Boiler Hardware Pack Contents 50mm...

Страница 14: ...applicable the extension flue box es 10 PACKAGING AND CASING REMOVAL 11 DOWNWARD ROUTING PIPE KIT Product Qty Downward pipe routing bracket 2 off M8 Spacing pillar 1 off M5 Spacing pillar 1 off Panel...

Страница 15: ...t with the support bracket It is MOST IMPORTANT that the boiler is installed in a vertical position Flue length mm Accessories Product No Up to 600 B Pack 1 off 150 308 600 to 1550 B Pack 1 off D Pack...

Страница 16: ...d in a separate kit must be used These brackets are secured to the wall mounting plate and it is essential to use only those holes as shown on the wall mounting template 1 An optional flue duct extens...

Страница 17: ...Flue extension ducts 1 Cut the flue hole preferably with a 125mm 5 core boring tool ensuring that the hole is square to the wall If the hole has been accurately cut with a drill then making good the...

Страница 18: ...e outer flue duct This ensures correct alignment of the flue terminal 4 Stick the self adhesive foam strip provided in the hardware pack onto the flue immediately behind the boiler sealing ring 21 FIT...

Страница 19: ...blanking plate from the direction required and use this to blank off the rear outlet Side and rear flue 2 Lift the boiler onto the wall mounting plate hooks as shown Do not use the burner controls fo...

Страница 20: ...50 B Pack 1 off D Pack 1 off see Frame 12 1550 to 2500 B Pack 1 off D Pack 2 off see Frame 12 2500 to 3000 B Pack 1 off D Pack 3 off see Frame 12 Note Side flue shown 26 FLUE EXTENSION DUCTS For flue...

Страница 21: ...Hz is required All external controls and wiring must be suitable for mains voltage Wiring should be in 3 core PVC insulated sheathed cable not less than 0 75mm2 24 x 0 2mm to BS 6500 Table 16 Wiring R...

Страница 22: ...e wired in parallel with the control s to be overridden Refer to Frame 38 4 If a proprietary system is used follow the instructions supplied by the manufacturer Advice on required modifications to the...

Страница 23: ...w or or r b b r r w w b br y y y g y g y g pky w pk y r r r w y g 34 PICTORIAL WIRING IMPORTANT No system controls to be wired in this mains supply Notes 1 Some earth wires are omitted for clarity En...

Страница 24: ...terminals on thermostats see the manufacturer s literature 3 This is a fully controlled system set the boiler thermostat to maximum 4 Switchmaster Smiths valves are similar but note that the GREY wire...

Страница 25: ...should suffice for all systems which do not use the OFF terminals of the programmer Diagram B shows a change over frost stat which will cover most systems which do use CH OFF If however on such a sys...

Страница 26: ...wing the control box back into its working position 6 Switch the electricity supply ON and check that all external controls are calling for heat 7 Press the boiler reset switch H and the overheat ther...

Страница 27: ...service contract yourself or alternatively offer to the customer the benefits of the British Gas Services details of which are outlined in the household pack supplied with this boiler After completin...

Страница 28: ...the burner downwards to disengage the retention tab Remove the burner to a safe place for inspection and cleaning 2 Remove the fixing screws and swing the control box down into the servicing position...

Страница 29: ...lue elbow and flue connector Disconnect the flue connector from the elbow and slide into the flue Remove the flue elbow 5 Disconnect the silicon rubber tube from the rear of the collector hood 6 Slack...

Страница 30: ...etailed in Frame 48 and ensuring that there is an inlet pressure of 20 mbar available the pilot does not light then contact British Gas Services Relight in accordance with Initial Lighting Frame 40 52...

Страница 31: ...of the switch 12 Press in the 2 side retaining clips and remove the switch 13 Replace and reassemble in reverse order 14 Check the operation of the boiler 54 CONTROL POTENTIOMETER THERMISTOR SENSOR LE...

Страница 32: ...he burner 4 At this stage the main burner injector can be removed checked cleaned or replaced as required Ensure that an approved jointing compound is used sparingly 5 Fit the new burner ensuring that...

Страница 33: ...hdraw from the control box 6 Fit the new PCB and reassemble in reverse order 7 Check the operation of the boiler Fuse To change the fuse prise the top off the holder and disengage the fuse Refer to Fr...

Страница 34: ...6 3 Drain the system 4 Disconnect the water connections If compression fittings are used then cut the pipes both above and below the fittings in order to allow the heat exchanger assembly to be remove...

Страница 35: ...S NO Change pressure switch Is fault corrected Is the boiler casing correctly fitted Does the main burner light NO YES YES Does the hot surface igniter turn off NO Is there a gas supply to the boiler...

Страница 36: ...71 441 18 308 317 Detection electrode complete with lead and backnut 410 mm lg 1 171 442 18 1 Hot surface igniter 330 340 1 171 973 18 2 Hot surface igniter 350 380 3100 1 171 490 19 E58 681 Control b...

Страница 37: ...ARTS LEGEND Numbers up to 51 relate to the B G spares list 10 Burner manifold 11 Air box and pilot assembly 12 Main burner 13 Main burner injector 67 BURNER ASSEMBLY Exploded View 16 Pilot shield 17 G...

Страница 38: ...LIST OF PARTS LED 1 LED 2 LED 3 LED 4 23A Fuse 21A Cla 2710 58A 26 LEGEND 19 Control box 21A Thermostat potentiometer 26 Thermostat knob 23A Printed circuit board 58A Lockout reset switch 68 CONTROL B...

Страница 39: ...British Gas RD1 Installation Servicing 39 NOTES...

Страница 40: ...British Gas by Ideal Boilers British Gas Services Limited Registered in England No 3141243 Registered Office Millstream Maidenhead Road Windsor Berkshire SL4 5GD British Gas Services Ltd has made eve...

Отзывы: